35
Select
Options
from the
Zone Setup
main menu located on the main screen. See Figure below.
Enter numeric Silence Detection Timeout value, from 3 to 30 seconds.
When complete, click on the
Apply
button.
Click the
OK
button. The “
Options”
screen will close leaving the SP4 Telzone Programmer 2
main screen displayed.
Save the file by opening the File menu and
Save
as the current file name, or
Save As…
with a
new name. If a new name is chosen, notice that the file name is changed to the new name.
Complete the task by clicking on the “
Send Configuration
” command button. This sends the new
configuration to the SP4-TZC. Notice that the “Zone Controller Successfully Programmed”
message appears on the computer screen, and that the USB CONFIG
LED indicator on the SP4-
TZC PC board turns
ON
. If an Error message appears, refer to Section 5.6 for details and
corrective action.
Click the
OK
button on the “Zone Controller Successfully Programmed” message.
Test the Silence Detection Timeout.
Shut down the SP4 Telzone Programmer 2 software on the host computer.
Disconnect the USB cable from the SP4-TZC Zone Controller and the host computer.