10
1.4 Specifications
The SP4-TZC specifications are listed in Table 2 below.
Table 2
SP4-TZC Specifications
Specification
Value
Input Voltage
24 VDC
Maximum Current
73mA
Page Input Voltage
550mVrms
BGM Input Voltage
Monaural
300mVrms at 600 Ohms
Maximum Distance between
SP4-TZC and the first SP4-
APS splitter using #18AWG
wire.
2000 ft.
The SP4-TZC factory default settings are listed in Table 3 below.
Table 3
Factory Default Settings
1.4.1 Wiring Specifications
Cable size: All terminal blocks accept #12 - #18 American Wire Gauge (AWG) for single wire connection.
Setting
Factory Default
Zone Paging (Individual Zone and Fixed Zone Group telephone paging)
Enabled
Logical Zone Group paging
Disabled
Background Music
All Zones
Silence Detection Timeout
10 seconds
Maximum Paging Duration
1 minute
Alert Page Tone
ON (Positions 1-2 Alert Page Tone)
BGM Volume
Full Clockwise (Max Volume)
Page Volume
Full Clockwise (Max Volume)