496792
3
1. Introduction
Operator Controls and Displays - 9930
Figure 2. 9930 Remote Keypad.
The 9930 keypad has a single line 16 character LCD display that shows first
to alarm information, level status, and programming commands. In addition
there are three LEDs with the following functions:
a
Glows steadily when mains power is present. Flashes when the
system is working from battery backup.
f
Glows steadily if a telephone line fault is present.
s
Glows steadily if:
a) A fault or tamper circuit is active while the system is unset.
b) The system needs an engineer or remote reset.
c) A telephone line fault is present.
In user mode, the keys provide the following functions:
9
Used to start a test of the detectors.
8
Used to start a test of the sounders and strobe.
7
Used to enable or disable the Chime facility.
6
Used to set the internal clock calendar, which provides a time
stamp on log entries.
5
Used to display the log (250 events).
4
Used to change the user access codes.
0
Used to call an ARC to request a download.
y
Used to enter programming and setting/unsetting commands.
X
Used to set the system with individual zones (including 24 hour
zones) temporarily omitted.
A,B,C,D Level setting keys. Level A sets the whole system.
Содержание 9752
Страница 1: ...HARDWIRED CONTROL PANELS INSTALLATION AND PROGRAMMING GUIDE...
Страница 6: ...iv 496792 Contents...
Страница 12: ...6 496792 1 Introduction...
Страница 18: ...12 496792 2 Technical Description...
Страница 38: ...32 496792 3 Installation...
Страница 90: ...84 496792 5 Testing...
Страница 95: ...Notes...