4. Programming
62
496792
Output Type
Bell
(Key in 00) The control unit operates this output during
an alarm. Use Command 41 to control bell delay and 42
to control bell duration.
If you enable Alarm Confirmation (Command 89) then
use Command 162 to select whether the control unit
activates the bell on a first or a confirmed alarm.
EE Follow
(Key in 01) This output is active when the entry or exit
time starts and deactivates at the end of the entry/exit
time, or if the entry/exit time is terminated. The output
can be used for a separate entry/exit buzzer. Note that
the output does not give a tone during part set if the exit
mode is silent set or instant set.
Armed lamp
(Key in 02) The output is active continuously while the
system is full or part set.
PIR Set Latch
(Key in 03) This output is active when the system is set
and deactivates when the system is unset or an alarm
condition occurs. The output will also activate for one
second when a reset is performed or the control unit
leaves programming mode. In addition, the output is
active during a walk test.
Shock Reset
(Key in 04) This output is used to reset shock sensors,
(for example the ‘Viper’). The control unit triggers the
output at the start of the exit period. The output remains
active for a fixed time of five seconds.
Walk Test
(Key in 05) This output is active during both engineer
and user walk test and in the period between silencing
the system and resetting the system. This output type is
used on movement detectors which have the facility to
switch off the walk test LED in any state other than a
walk test.
Ready Lamp
(Key in 06) This output is active when the system is
unset, and if there are no faults. The output is inactive
when the system is full or part set, during any alarm, or
if a circuit fault prevents setting. Note that the output will
also be active when the control unit is in programming
mode.
24 Hour alarm
(Key in 07) This output will become active if a zone
designated as ’24 Hours’ is violated. The output deacti-
vates when the system is disarmed.
Содержание 9752
Страница 1: ...HARDWIRED CONTROL PANELS INSTALLATION AND PROGRAMMING GUIDE...
Страница 6: ...iv 496792 Contents...
Страница 12: ...6 496792 1 Introduction...
Страница 18: ...12 496792 2 Technical Description...
Страница 38: ...32 496792 3 Installation...
Страница 90: ...84 496792 5 Testing...
Страница 95: ...Notes...