4. Programming
496792
49
days after you return the control unit to user mode. If the
zone is opened while the system is set then the Service
LED glows and the control unit logs the event as a “Soak
Test Fail Zn” (n is the zone number) without sounding any
bells or starting signalling. The Service LED stays alight
until the Engineer resets the system. After midnight on the
14th day the control unit returns the zone to normal use.
Note: Soak test is available only for Normal Alarm, Entry Route, Technical and
Shock Analyser zone types.
Double
Knock (2)
(Key in
X
3) Zones with this attribute will cause an alarm
condition only if one or more sensors generate two alarms
events within a five minute time window, or if one zone
remains open for more than 10 seconds. Programming a
zone as ‘Double Knock’ is a way of reducing false alarms
caused by environmental changes, but is not normally
recommended.
Notes:
1.‘Double Knock’ is available only for Normal Alarm and Entry Route zone types.
2. Do not apply ‘Double Knock’ to radio zones with a PIR detector. The radio PIR
uses a lockout timer and the detector will not send a second activation within the
Double Knock time window.
Omit Allow (O)
(Key in
X
4) When applied to a zone, this attribute allows
the user to omit the zone.
Part Set B (b)
(Key in
X
5) When applied, the zone will be armed when
the user selects Part Set B. Zones not selected will be
omitted.
Part Set C (c)
(Key in
X
6) When applied, the zone will be armed when
the user selects Part Set Level C. Zones not selected will
be omitted.
Sensitivity
(Key in
X
7) When you use this Command you must also
enter an extra digit in the range 1 to 6 in order to set the
sensitivity of the shock sensor. 1 is least sensitive, 6 is
most sensitive. Note that to use this attribute you must
make one of zones 1 to 4 a shock analyser type. To
adjust the sensitivity you must enter the complete Com-
mand, for example to change the sensitivity to 3 you must
key in:
X
7 + 3.
Part Set D (d)
(Key in
X
8) 9752 only. When applied, the zone will be
armed when the user selects Part Set Level D. Zones not
selected will be omitted.
Содержание 9752
Страница 1: ...HARDWIRED CONTROL PANELS INSTALLATION AND PROGRAMMING GUIDE...
Страница 6: ...iv 496792 Contents...
Страница 12: ...6 496792 1 Introduction...
Страница 18: ...12 496792 2 Technical Description...
Страница 38: ...32 496792 3 Installation...
Страница 90: ...84 496792 5 Testing...
Страница 95: ...Notes...