TDMA CONTROL 602-702 Eng Nov.doc
7
3.2
Technical Data CONTROL 702
Base unit
:
Plastic housing, ca. 235 x 170 x 130 mm
Protection:
IP 20
Operating Voltage:
230 V ±10%, 50 Hz, AC
Power consumption:
max. 10 W
Ambient temperature:
0°C...40°C
Output / Input:
Switching outputs:
A1…A17: Semi-conductor Triac 230V, max. 2A, fused with glass fuse 3
x 15A slow blow, only suitable for the loads
Switch:
A18…A19: potential free changeover relay, max. 240 V, max. 2A,
not protected
Analogue outputs 1...6
The Analogue outputs 3…6 are not used
a) 0V ... 10V, ± 5 %, minimum load resistance 1 kOhm
b) PWM, max. 1 kHz, minimum load resistance 1 kOhm
Analogue inputs ES
0V...10V, load resistance 10 kOhm, resolution 10 Bit
supply voltage: 18V...24V, max. 100mA
Digital inputs D1…D6
a) potential free contacts
b) Open Contact: low < 10V, high > 14V
supply voltage: 18V...24V, max. 100mA
Ethernet interface
10/100 BASE-T
Temperature sensor inputs
24 x resistance temperature sensors Type Pt1000, class B
Scale range: -40°C ... 350°C
Measuring range: -20°C ... 150°C
Accuracy in measuring range: +/- 1°C
Operation:
Menu driven
Service menu:
Each output can be switched manually.
Temp. in
°C
-10
0
10
20
30
40
50
60
70
80
90
100
110
R in Ohm
961,5
1000
1038,5
1077
1115,5
1154
1192,5
1231
1269,5
1308
1346,5
1385
1423,5
3.3
Technical Data TR-CONTROL II Touch
Base unit:
Plastic housing, ca. 132 x 90 x 21 mm
Protection:
IP 20
Power Input
Max. 2 W
Ambient temperature:
0°C...40°C
Room sensor accuracy
+/- 0.5 oC (with wall compensation)
Note:
The details and advice in the technical documentation do not claim to be
comprehensive and are not a replacement for professional planning. Errors and
omissions excepted