TDMA CONTROL 602-702 Eng Nov.doc
51
Boiler Output max
ii
Boiler Dependent
Boiler Output 0 V
ii
Boiler Dependent
Boiler Output 10 V
ii
Boiler Dependent
Control Parameter P
ii
Application Dependent
Control Parameter Tn
ii
Application Dependent
Pump Speed min
Application Dependent
Min Run Time of Boiler
2 Minutes
Boiler Pp Extended Running Time Application Dependent
Difference Buffer Logic
16
Hysteresis Buffer Logic
Solid Fuel Boiler Temp.min
17
50 °C
Difference Solid Fuel Boiler
17
4 K
Boiler off, if Solid Fuel Boiler on?
17
Application Dependent
Input T-PRO
18
:
Recommended Value Setting
Temperature Sensor 2
Application Dependent
Difference T-PRO
Application Dependent
Hysteresis T-PRO
Application Dependent
Temperature T1 min
Application Dependent
Temperature T1 max
Application Dependent
Temperature T2 min
Application Dependent
Temperature T2 max
Application Dependent
Overrun T-PRO
Application Dependent
Timer T-PRO Use?
Application Dependent
To Engineer’s Menu?
Timer T-PRO
Application Dependent
Switching Time 1
Application Dependent
Switching Time 2
Application Dependent
Switching Time 3
Application Dependent
Switching Time 4
Application Dependent
Input T-PRO 2
18
:
Recommended Value Setting
Temperatur e Sensor 2
Application Dependent
Difference T-PRO
Application Dependent
Hysteresis T-PRO
Application Dependent
Temperature T1 min
Application Dependent
Temperature T1 max
Application Dependent
Temperature T2 min
Application Dependent
Temperature T2 max
Application Dependent
Overrun T-PRO
Application Dependent
Timer T-PRO Use?
Application Dependent
To Engineer’s Menu?
Timer T-PRO
Application Dependent
Switching Time 1
Application Dependent
Switching Time 2
Application Dependent
Switching Time 3
Application Dependent
Switching Time 4
Application Dependent
Input T-PRO 3
18
:
Recommended Value Setting
Temperature Sensor 2
Application Dependent
Difference T-PRO
Application Dependent
Hysteresis T-PRO
Application Dependent
Temperature T1 min
Application Dependent
Temperature T1 max
Application Dependent
Temperature T2 min
Application Dependent
Temperature T2 max
Application Dependent
Overrun T-PRO
Application Dependent
Timer T-PRO Use?
Application Dependent
To Engineer’s Menu?
Timer T-PRO
Application Dependent
Switching Time 1
Application Dependent
Switching Time 2
Application Dependent
Switching Time 3
Application Dependent
Switching Time 4
Application Dependent
Service:
Recommended Value Setting
Consolar Con. 702 App
Software Version
Basic
Basic Version
Time
Current Time
Date
Current Date
Auto Switching Sum/Win Time
Yes
Calibrate Clock
Application Dependent
Service Tel. Nr. Insert
Application Dependent
Restore factory Settings
No
Interval SD-Recording
60 s
Input Ethernet
User Dependent
DHCP State
IP Address
Sub-network
Gateway Address
MAC Address
Manual Operation
Auto
View Outputs
Language
User Dependent
Authorisation Set?
User Dependent
Serial No…………………………..
Only if set:
1
East-West
10
Boiler Control
2
Stratification Function
≡
Auto
11
Circulation
3
Cooling
12
Yield
4
Cooling via Heating Circuit 1
13
Heat Meter
5
Two Store Priority
14
Volume Flow Meter
6
Two Store Equal
15
Hearing
7
Swimming Pool
16
Buffer logic
8
Frost Protection
17
Solid Fuel Boiler
9
DHW Heating
18
T-PRO
Note:
i
When using a flow meter set the solar flow to 0 l/min on the controller.
ii
Only with modulated boiler operation must the parameters be set.