TDMA CONTROL 602-702 Eng Nov.doc
6
3
Technical Data
3.1
Technical Data CONTROL 602
Base Unit:
Plastic housing 235 x 170 x 75 mm
Protection:
IP 20
Operating Voltage:
230 V ±10%, 50 Hz, AC
Power Consumption:
max. 10 W
Ambient Temperature
0°C...40°C
Outputs / Inputs
Switching Outputs
A1…A7: Semi-conductor Triac 230V, max. 2A, Fused with glass fuse 3
x15A slow blow, only suitable for the loads
Switch
A8: potential-free changeover relay, max. 240 V, max. 2A, not
protected
Analogue Outputs 1...2
a.)
0V ... 10V, minimum load resistance 1 kOhm
b.)
PWM, max. 1 kHz, minimum load resistance 1 kOhm
Analogue Inputs ES
0V...10V, Load resistance 10 kOhm, resolution 10 Bit
supply voltage: 18V...24V, max. 100mA
Digital Inputs D1,D2
a.)
Potential-free contacts
b.)
Open Contact: low < 10V, high > 14V
Supply voltage: 18V...24V, max. 100mA
Ethernet interface
10/100 BASE-T
Temperature sensor inputs
10 x RTD Type Pt1000, Class B
Scale range: -40°C ... 350°C
Measuring range: -20°C ... 150°C
Accuracy in measuring range: +/- 1°C
Operation:
Menu driven
Service menu:
Each output can be switched manually.
Temp. in
°C
-10
0
10
20
30
40
50
60
70
80
90
100
110
R in Ohm
961,5
1000
1038,5
1077
1115,5
1154
1192,5
1231
1269,5
1308
1346,5
1385
1423,5
Note:
The details and advice in the Technical Documentation do not claim to be
comprehensive and are not a replacement for professional planning. Errors and
omissions accepted.