The lower housing section is fixed to the wall by three screws. First drill and
screw two screws into the wall at 140 mm centres. Mount housing onto these
screws and then drill and insert the third screw through the lower hole and fix
to the wall.
Third screw location hole
Thereafter, the electrical connections can be made.
6.2
Electrical Connections CONTROL 602
Caution
Never remove the front cover when mains voltage is present! Danger!
In order to prevent faulty operation during commissioning, the connections
should be made in the following order:
1.
Sensor and network connections
2.
Set he system variant (see Section 5.3)
3.
Interrupt the power supply and connect all outputs.
Not following this sequence can lead to faluty operation during
commissioning, causing the ‘Restore Factory Settings’ to be implemented which
goes automatically to Variant A, which may not match the desired output
circuits.
6.2.1
Connection Board - CONTROL 602
140m
m