TDMA CONTROL 602-702 Eng Nov.doc
38
SD – Recording
Status: On
If the Sd recoding status ‘On’ is selected, the controller records, as soon as an
SD card is put into the controller, all measured values automatically. Also all
temperature values and output states will be recorded.
It is recommended that an SD Card is left in the controller and recording, so
that in case of a failure the cause can be found from the data recorded.
Interval: 1 0 s
SD -‐ Recording
The time interval between the readings that the SD card will record.
Settings
Save?
The complete settings (selected system variant with all customer specific
adjustments) are saved to the SD card.
Settings
Upload?
Saved settings / configerations can be uploaded. This can be useful for
programming errors or for firmware updates.
Service Menu:
Ethernet Input
The IP address for the controller can either be set or read. Ifthe DHCP state:
On is selected, the controller will automatically assign an IP address when the
controller is on a network.
The remore portal MAC address, which is required for registration, can be
found here.
Manual?
Here all outputs can be switched manually.
The settings in manual mode have priority over everything else. This means
that the pumps, or mixing valves can be switched on or off, even if the function
is turned off, in another menu, or even if in a fault condition.
Example: Manual Mode of Solar Pump
On: The solar pump is switched on permanently.
Off: The solar pump is switched off.
Auto: The controller controls the pump according to the state of the system.
Note
If the DHW back-up heating and the boiler functions are activated manually to
‘On’ they switch back to ‘Auto’ operation after 10 minutes automatically.
Note:
Choosing Open, Close, Off or Auto can operate the mixing valve manually.
In the Open, Close or Off positions, the mixing valve will remain in that
position permanently until the control is switched back to Auto. You should
therefore always set it to Auto.
Caution
The manual switching (manual operation) must only be used in short periods or
for testing purposes only. Continual running in manual mode will damage the
system or components, because the safety functions are overridden.