background image

17

COMUNELLO

  ®Copyright 2014 - All right reserved

ENGLISH

L1

FOTOTEST

ON

OFF

L2

PEDESTRIAN TIME

ON

OFF

L3

DECELERATION

OFF

ON

L4

ELEC BRAKE

ON

OFF

L5

RELEASE STROKE

ON

OFF

L6

SLAM LOCK

ON

OFF

L7

COURTESY LIGHT

ON

OFF

LEV

MENU

1 FLASH

1. FOTOTEST: (Photocells test)

The control unit is factory set with the photocells test disabled. To enable the 
test, proceed as follows: make sure you have enabled Extended Menu 1, 
use the SELECT key to select blinking LED L1 then press the SET key, LED 
L1 becomes steady on and the programming procedure will be completed. 
Repeat the procedure if you wish to restore the prior configuration.

2. PED. MOT. T: (Programming of pedestrian motor time, 4 minutes 
max)

The control unit is factory set with a preset Motor time (Pedestrian) of 
10 seconds without deceleration. If the pedestrian motor time must 
be changed, programming must be carried out with the gate closed as 
follows: make sure you have enabled Extended Menu 1, use the SELECT 
key to select blinking LED L2, then press the SET key momentarily; the 
Operator will start an Opening cycle; when the gate reaches the required 
initial deceleration point press the SET key again: LED L2 will start blinking 
more slowly and the Operator performs the deceleration; when the required 
position is reached press the SET key to terminate the Opening cycle. At 
this point LED L2 returns to the normal blinking speed and the Operator 
restarts in the Closing movement; repeat the operations described above 
for the Closing movement. If you do not require the control unit to perform 
the deceleration, during programming, when the open-close cycle has 
been completed press the SET key twice consecutively rather than just 
once. During programming, instead of the SET key on the control unit you 
can use the button on the remote, providing the remote has been saved 
beforehand.

3. DECELERATION:

As mentioned earlier, the control unit allows programming of a deceleration 
stage during opening and closing. However, if no deceleration is required, 
this stage can be inhibited. If, before excluding the deceleration stage it had 
already been programmed using the Motor Times Programming function, 
programming must be repeated from the beginning. If the deceleration 
stage is to be excluded proceed as follows: make sure you have enabled 
Extended Menu 1, use the SELECT key to select blinking LED L3 and 
then press the SET key: LED L3 becomes steady on and programming will 
be completed. Repeat the procedure if you wish to restore the previous 
configuration.

4 ELECTRONIC BRAKE:

The control unit is factory set with the electronic brake function disabled. 
To enable the function, proceed as follows: make sure you have enabled 
Extended Menu 1, use the SELECT key to select blinking LED L4 then 
press the SET key, LED L4 becomes steady on and the programming 
procedure will be completed.
With this function enabled the control unit reduces coasting of the gate due 
to inertia at the time of a stop or direction reversal command. Repeat the 
procedure if you wish to restore the previous configuration.

5  RELEASE STROKE:

The control unit is factory set with the release stroke function disabled. To 
enable the Release Stroke function at maximum power, proceed as follows: 
make sure you have enabled Extended Menu 1, use the SELECT key to 
select blinking LED L5 then press the SET key, LED L5 becomes steady on 
and the programming procedure will be completed. If you wish to enable 
the Release Stroke function at the power set with the “FORCE” trimmer, 
repeat the procedure described above,
press the SELECT key twice (LED L5 will blink rapidly) rather than just once. 
Repeat the procedure if you wish to restore the initial configuration.
This procedure makes it possible to facilitate release of the gate lock and 
thus allow correct execution of the opening stroke. With this function, before 
starting the opening stroke the control unit sends a closing command for 2 
seconds with the thrust force associated with the selection made.

6   SLAM LOCK:

The control unit is factory set with the Slam Lock function disabled. This 
function consists in adding, in the presence of a deceleration stage during 
closing, 1 extra second at the maximum power or at the power selected 
with the “FORCE” trimmer, in such a way as to ensure positive engagement 
of the gate lock, if installed. If you wish to enable the Slam Lock function 
at maximum power, proceed as follows: make sure you have enabled 
Extended Menu 1, use the SELECT key to select blinking LED L6 and then 
press the SET key: LED L6 becomes steady on and programming will be 
completed. If you wish to enable the Slam Lock function at the power set 
with the “FORCE” Trimmer, repeat the operation described by pressing the 
SELECT key twice (LED L6 will blink rapidly) rather than once. Repeat the 
procedure if you wish to restore the initial configuration..

7. PREFLASHING/COURTESY LIGHT:

The control unit is factory set with the Preflashing and Courtesy Light 
functions disabled. If you wish to enable the Preflashing function proceed 
as follows: make sure you have enabled Extended Menu 1, press the 
SELECT key to select blinking LED L7 and then press the SET key: the LED 
becomes steady on and programming will be completed. If you wish to 
enable the Courtesy Light function, repeat the operation described above, 
pressing the SET key twice (the LED will blink rapidly) rather than once. 
Repeat the procedure if you wish to restore the initial configuration.

Preflashing Operation:

 The 24 

~

 4W max. flashing light output will 

always switch on 3 seconds before the gate starts the closing operation.

Courtesy Light Operation:

 The 24 

~

 4W max. courtesy light output will 

switch on for 3 minutes whenever an opening command is transmitted.

EXTENDED MENU 2

The control unit is factory set to allow selection exclusively of the main menu 
functions. If you wish to enable the functions described in Extended Menu 
2, proceed as follows: select blinking LED LEV and press SET twice. The 
LED will start blinking alternately 1 1 0 1 1 0 1 1 0. This means there is a 
period of 30 seconds to select the functions in Extended Menu 2 using the 
SELECT and SET keys and then, after a further 30 seconds, the control unit 
will revert to the main menu.

L1

SOFT STOP

ON

OFF

L2

SOFT START

ON

OFF

L3

SAFE 1 IN OPEN

ON

OFF

L4

HOLD-TO-RUN

ON

OFF

L5

FOLLOW ME

ON

OFF

L6

PAUSE FLASHING

ON

OFF

L7

ALWAYS CLOSE

ON

OFF

LEV

LEV

LONG FLASHING

1.  SOFT STOP:

The control unit is factory set with the Soft Stop function disabled. If you 
wish to enable the function, proceed as follows: ensure you have enabled 
Extended Menu 2 and then use the SEL key to select blinking LED L1 
and press the SET key; at the same time LED L1 becomes steady on and 
programming will be completed. With this function enabled at the end of the 
movement the control unit will reduce operator force to zero gradually in a 
2 second interval. Repeat the procedure if you wish to restore the previous 
configuration.

2.  SOFT START:

The control unit is factory set with the Soft Start function disabled. If you 
wish to enable the function, proceed as follows: ensure you have enabled 
Extended Menu 2 and then use the SELECT key to select blinking LED 
L2 and press the SET key; at the same time LED L2 becomes steady 
on and programming will be completed. With this function enabled at 
the start of each movement the control unit will regulate start-up of the 
operator, gradually increasing the force from the minimum to the value set 
by the “FORCE” trimmer during the first 2 seconds of operation. Repeat the 
procedure if you wish to restore the previous configuration.
Note: when the Soft Start function is enabled the control unit automatically 
disables the Starting Torque function, while if Soft Start is disabled then 
Starting Torque is automatically enabled.

3. SAFE 1 also in opening:

The control unit allows the operation of input DS1 to be modified. If you 
want SAFE 1 to operate also during opening (momentary stopping of the 
gate, as soon as the safety is freed the control unit resumes the opening 
movement), proceed as follows: ensure you have enabled Extended Menu 
2 and then press the SEL key to select blinking LED L3 and press the SET 

Содержание CU-110V-1M

Страница 1: ...USER S MANUAL comunello com Control units ISTRUZIONI D USO E DI INSTALLAZIONE INSTALLATIONS UND GEBRAUCHSANLEITUNG INSTRUCIONS D UTILISATION ET D INSTALLATION INSTRUCCIONES DE USO Y DE INSTALACION Co...

Страница 2: ...ON OFF L2 SOFT START ON OFF L3 SAFE 1 IN OPEN ON OFF L4 HOLD TO RUN ON OFF L5 FOLLOW ME ON OFF L6 PAUSE FLASHING ON OFF L7 ALWAYS CLOSE ON OFF LEV LEV LONG FLASHING ID LED L1 DIR Left Open Right Open...

Страница 3: ...BASIC 110V CU 110V 1M ID Description Cable type Lenght 1m to 20m Lenght 20m to 50m 1 Main power supply FG7 CEI 20 22 CEI EN 50267 2 1 3Gx1 5mm2 3Gx2 5mm2 2 Flashing light 2x0 5mm2 2x1 0mm2 4A 6A Photo...

Страница 4: ...PLY 2P T 230V 50Hz CN2 ANTENNA PULSANTE APRI CHIUDI N O PUSCH BUTTON N O ALIMENTAZIONE FOTOCELLULE PHOTOCELL POWER 24V 5W FINECORSA APRI N C END OPEN N C FINECORSA CHIUDI N C END CLOSE N C FOTOCELLULA...

Страница 5: ...like below Led opening direction OFF OPENS TO THE RIGHT Inner side view OPENING DIRECTION 1 MOTOR CONFIGURATION FORT FORT like below Led opening direction ON OPENS TO THE LEFT Inner side view BLACK ON...

Страница 6: ...ight 2014 All right reserved SALIENT SALIENT DO NOT CHANGE the configuration Opens to the left closes to the right left profile view as in the image CN1 F1 L N OP1 CM1 CL1 BROWN ON OPEN BLACK ON CLOSE...

Страница 7: ...he traspongono le seguenti direttive direttiva 2004 108 CE Direttiva EMC direttiva 2006 95 CE e che sono state applicate tutte le norme e o specifiche tecniche di seguito indicate EN61000 6 2 EN61000...

Страница 8: ...inalterate le caratteristiche di grado IP della scatola Prestare inoltre attenzione a fissare i cavi in modo che siano ancorati in modo stabile e a non danneggiare la scheda con la foratura fig 3B L i...

Страница 9: ...del raggiungimento del finecorsa chiusura la centrale effettua sempre l arresto del moto Un ulteriore comando determina la ripresa del moto in senso opposto Funzionamento Passo Passo 1 Utilizzando sia...

Страница 10: ...gio del codice da cancellare CODE o PEDONALE identificati dal rispettivo lampeggio premere e tener premuto SET per un tempo 5 s Alla fine il led si spegner per 2 sec e la procedura completata Se si el...

Страница 11: ...i SELECT e SET poi dopo ulteriori 30 secondi la centrale ritorna al men principale L1 SOFT STOP ON OFF L2 SOFT START ON OFF L3 DS1 INAPRE ON OFF L4 UOMO PRESENTE ON OFF L5 FOLLOW ME ON OFF L6 LAMP PAU...

Страница 12: ...empo di Pausa interviene dopo una mancanza di alimentazione se viene rilevato che il cancello aperto si avvia automaticamente una manovra di chiusura preceduta da 5s di prelampeggio Se si desidera tal...

Страница 13: ...directives 2004 108 EC Directive EMC Directive 2006 95 CE Directive and that all the rules and or technical specifications shown below have been applied EN61000 6 2 EN61000 6 3 EN62233 2008 EN301489...

Страница 14: ...ar of the box is equipped with knockouts for wall fixing knockouts for fixing holes using anchor bolts or holes for fixing with screws Take all the measures required to ensure the installation procedu...

Страница 15: ...ommand is transmitted before motor time has elapsed or before one of the limit stops has been reached the control unit stops the movement during both opening and closing Another command causes the gat...

Страница 16: ...code type the receiver will subsequently accept both fixed code remotes and rolling code remotes although only the fixed part of the latter will be controlled thus effectively relinquishing the securi...

Страница 17: ...de 6 SLAM LOCK The control unit is factory set with the Slam Lock function disabled This function consists in adding in the presence of a deceleration stage during closing 1 extra second at the maximu...

Страница 18: ...iance with standard EN 12453 point 5 1 1 6 At each operating cycle a functional test of the connected photocell is performed In the case of an open circuit and or malfunctioning of the photocell the c...

Страница 19: ...Richtlinie 2004 108 EG EMV Richtlinie Richtlinie 2006 95 CE und dass alle folgenden Normen und oder technischen Spezifikationen angewendet wurden EN61000 6 2 EN61000 6 3 EN62233 2008 EN301489 1 EN3014...

Страница 20: ...oder zur Befestigung mit Schrauben Es sind alle Vorkehrungen f r eine Installation ohne Ver nderung des IP Schulzgrades vorzusehen und zu implementieren Falls eine Druckknopftafel f r die manuelle Be...

Страница 21: ...ewegung falls zuvor eine Pausezeit programmiert wurde steuert sie bei Ablauf das erneute automatische Schlie en Eine weitere Schaltung bewirkt die Wiederaufnahme der Bewegung in die entgegengesetzte R...

Страница 22: ...1 1 0 um auf die aktive Speicherung des Fu g ngercodes hinzuweisen Durch Senden des gew hlten Codes mit der gew nschten Funksteuerung bleibt die LED CODE L3 permanent eingeschaltet um darauf hinzuweis...

Страница 23: ...aste SELECT auf das Blinken der LED L3 stellen und auf die Taste SET dr cken Die LED L3 schaltet permanent ein und die Programmierung wird beendet Zur R ckstellung auf die vorherige Konfiguration den...

Страница 24: ...nn bereits eine Pausezeit programmiert wurde und wird nach einem Versorgungsmangel aktiviert wenn erfasst wird dass das Tor ge ffnet ist beginnt automatisch ein Schlie man ver mit einem vorherigen 5 S...

Страница 25: ...ant les directives suivantes Directive 2004 108 CE Directive EMC Directive 2006 95 CE Et qui ont t soumis toutes les norms et ou sp cifications techniques ci apr s indiqu es EN61000 6 2 EN61000 6 3 EN...

Страница 26: ...r vu pour une fixation murale orifices de fixation pour chevilles ou vis Adopter toutes les pr cautions n cessaires en vue d une installation conforme l indice IP pr vu En cas de montage d un clavier...

Страница 27: ...elle commande d clenche la reprise du mouvement en sens inverse Fonctionnement du Pas Pas 1 En utilisant et le radiocommande et les claviers de commande en basse tension pour l actionnement du portail...

Страница 28: ...des la r p tition de l op ration de programmation entra ne le clignotement de tous les LED de programmation pour indiquer qu aucune nouvelle m morisation n est possible Effacement Au moyen de la touch...

Страница 29: ...ED L3 s allume fixe et la programmation est termin e R p ter l op ration pour r tablir la configuration pr c dente 4 FREIN LECTRONIQUE La logique de commande est configur e en usine avec la fonction F...

Страница 30: ...nnement Fermeture syst matique cette fonction uniquement programmable si un temps de pause a t pr vu intervient apr s une panne d alimentation si le syst me d tecte que le portail est ouvert la fermet...

Страница 31: ...ones legales que transponen las seguientes directivas Directiva 2004 108 CE Directiva EMC Directiva 2006 95 CE Y que han sido aplicadas todas las normas y o especificaciones t cnicas en lo sucesivo in...

Страница 32: ...cuando fije los cables de manera que queden bien fijados La cubierta de la parte trasera est preparada para la fijaci n a la pared predisposici n para la fijaci n con tacos u orificios para la fijaci...

Страница 33: ...o o del alcanzar al final de carrera el cuadro de control siempre efectua el cierre Un mando adicional determina la reanudaci n del movimiento en el sentido contrario Funcionamento paso a paso 1 Utili...

Страница 34: ...o que se completar la programaci n Si se han memorizado los 120 c digos repitiendo la operaci n de programaci n todos los LED de programaci n comenzar n a destellar se alando que no es posible memoriz...

Страница 35: ...ecer la configuraci n anterior 4 FRENO ELECTR NICO El cuadro de control se suministra de f brica con la funci n Freno Electr nico inhabilitada Si se desea habilitar la funci n proceda de la siguiente...

Страница 36: ...e configurar el funcionamiento Cerrar Siempre dicha funci n que se puede programar solo si se ha programado un Tiempo de Pausa se activa despu s de un corte de alimentaci n si se detectara que la puer...

Страница 37: ...2008 n 50 100 11235 Rev 01 CE COMUNELLO LUCA F lli COMUNELLO spa Via Cassola 64 36027 Ros VI Italy CU 110V 1M 2004 108 CE 2006 95 CE EN61000 6 2 EN61000 6 3 EN62233 2008 EN301489 1 EN301489 3 EN30022...

Страница 38: ...38 COMUNELLO Copyright 2014 All right reserved 110 III 5 2 9 EN 12453 EN 60204 1 5 2 7 EN 12453 14 H05RN F 1 2 110V SELV 110V SELV 4 1 3 IP IP 5 2 7 EN 12453 D S 2 5 1 1 6 EN 12453 8 3...

Страница 39: ...CH 100x105 1 2 3 CN1 L 110 N 110 OPEN1 1 COM1 1 CLOSE1 1 CN2 STOP NC GND GND LAMP 24 4 FOTO 24 5 GND GND FCC NC FCA NC GND GND SAFE1 NC PP P P NA ANT ANT CN3 1 1 110 2 110 CN4 2 1 SEC 1 12 5 0 17A 2 S...

Страница 40: ...ECT LED DIREZ APRE SET LED DIREZ APRE 2 STEP BY STEP LED 2 SEL LED 2 SET LED 2 1 1 SEL 2 3 CODE TX 120 SELECT LED L3 1 SET 1 0 1 0 LED CODE SELECT LED L3 CODE 2 SET 1 1 0 1 1 0 LED L3 CODE 120 SELECT...

Страница 41: ...L6 L7 LEV 1 1 1 SELECT L1 SET LED L1 2 4 10 1 SELECT LED L2 SET SET LED L2 SET LED L2 SET SET 3 1 SELECT L3 SET L3 4 1 SELECT L4 SET LED L4 5 1 SELECT L5 SET LED L5 FORCE SELECT LED L5 2 6 1 FORCE 1...

Страница 42: ...2 3 SAFE 1 DS1 SAFE 1 2 SEL LED L3 SET LED L3 4 2 SELECT LED L4 SET LED L4 5 5 SAFE1 5 2 SELECT LED L5 SET LED L5 6 1 SELECT LED L6 SET L6 7 5 2 SELECT LED L7 SET LED L7 SEL SET 5 1 1 6 EN 12453 2 EN...

Страница 43: ...43 COMUNELLO Copyright 2014 All right reserved...

Страница 44: ...FRATELLI COMUNELLO S P A AUTOMATION GATE DIVISION Via Cassola 64 C P 79 36027 Ros Vicenza Italy Tel 39 0424 585111 Fax 39 0424 533417 info comunello it www comunello com...

Отзывы: