15
COMUNELLO
®Copyright 2014 - All right reserved
ENGLISH
TECHNICAL SPECIFICATIONS
Power supply
: 110 V
~
60Hz 1600W max.
Flashing light output
: 24 V
~
4W max.
Operator outputs
: 110 V
~
500 W max.
Photocells power supply : 24 V
~
5 W max. -
LV safeties and controls : 24 V
Working temperature
: -20 55 °C
Radio receiver
: 433 Mhz
Transmitters
: 18 Bit or Rolling Code
Max TX codes stored in memory: 120 (CODE or PED CODE) - Board
dimensions
: 100x105 mm
PRELIMINARY CHECKS
• Check that the product in the pack is intact and in good condition
• Check that the place of installation is suitable and in compliance with the
minimum dimensions shown in figure 1
INSTALLATION
• Drill the box in the four corners and then fix the control unit to the wall
(FIG. 2)
• Drill a hole in the underside of the box for the cable inlet. (FIG.3) The use
of cable glands is recommended.
CONNECTIONS
CN1:
L:
110 V
~
line input (phase).
N:
110 V
~
line input (neutral).
OPEN1: Operator 1 opening output.
COM1: Operator 1 output common.
CLOSE1: Operator 1 closing output.
CN2:
STOP:
Emergency stop input (NC)
GND:
Common GND input
LAMP+: Flashing light output (24 V
~
4W max).
FOTO+: Photocells Control and Power Supply (24V
~
5W max).
GND:
Common power supply (GND).
FCC:
Operator Closing Limit Switch Input (NC).
FCA:
Operator Opening Limit Switch Input (NC).
GND:
Common GND input
SAFE1: Safety Device Input (NC).
PP:
Pedestrian Pushbutton open-close command input (NO).
ANT:
Antenna Ground Input.
ANT+:
Antenna Hot pole input.
TRANSFORMER CONNECTIONS
CN3 1st:
1 : 110 V
~
Transformer Primary Winding Input.
2 : 110 V
~
Transformer Primary Winding Input.
CN4 2nd:
1. Transformer SEC 1 Output 12.5V 0.17A no-load voltages.
2. Transformer SEC 1 Output 12.5V 0.17A no-load voltages.
3. Transformer SEC 2 Output 24.5V 0.4A no-load voltages.
4. Transformer SEC 2 Output 24.5V 0.4A no-load voltages.
FUNCTIONAL CHARACTERISTICS
AUTOMATIC OPERATION:
When either the remote or the low voltage pushbutton is used to control the
gate, operation is as follows:
the first command opens the gate until motor time elapses or until the gate
reaches its opening limit position; the second command closes the gate; if
another command is transmitted before motor time has elapsed or before
one of the two limit stops has been reached, the control unit reverses the
movement direction during both opening and closing.
STEP-BY-STEP OPERATION:
When either the remote or the low voltage control pushbuttons are used to
control the gate, operation is as follows:
the first command opens the gate
until motor time or until the gate
reaches its opening limit position; the second command closes the gate;
if another command is transmitted before motor time has elapsed or
before one of the limit stops has been reached, the control unit stops the
movement. Another command causes the gate to start moving again in the
opposite direction.
Step-by-step 1 operations:
When either the remote or the low voltage control pushbuttons are used to
control the gate, operation is as follows:
the first command opens the gate
until motor time or until the gate
reaches its opening limit position; the second command closes the gate;
if another command is transmitted before motor time has elapsed or
before one of the limit stops has been reached, the control unit stops the
movement during both opening and closing. Another command causes the
gate to start moving again in the opposite direction.
AUTOMATIC CLOSING:
The control unit can be set up to close the gate automatically without
sending any additional commands.
The selection of this type of operation is described in Pause time
programming mode.
PEDESTRIAN OPENING:
By means of the radio remote control (CODE P. LED on) the control unit
makes it possible to drive the Operator for a programmable time, typically
to allow pedestrian access.
EMERGENCY STOP INPUT:
The control unit allows the connection of an emergency stop pushbutton
(NC). Pressing this pushbutton irrespective of the current operating mode
of the control unit will cause immediate stopping of the gate movement. An
additional gate movement command will be valid provided the emergency
stop input is deactivated and, in any case, the control unit will execute the
gate opening cycle with 5 seconds preflashing.
IMPORTANT:
Jumper this input if it is not to be used.
PHOTOCELLS:
Photocells can be powered by and connected to the control unit in
accordance with directive EN 12453. Tripping of the photocells during
opening is disregarded, while during closing it causes reversal of the
direction of movement.
To allow operation in compliance with EN 13849-1 Category 2 a photocell
test is performed before each movement. The control unit enables the
movement only if the test is passed; if it is not, the control unit inhibits
all movements and an alarm condition is signalled by blinking of all the
programming LEDs on transmission of any command.
OPERATOR FORCE ADJUSTMENT (FORCE):
The electronic control unit is equipped with a “FORCE” trimmer for
adjustment of the Force delivered by the operators, completely managed
by the microprocessor. Adjustment can be performed in a range of between
50% and 100% of maximum force. Initial starting torque can be set for each
movement by feeding the operator at full power for 2 seconds, even if
operator force control is enabled. Note: initial starting torque is disabled
automatically if the Soft Start function is enabled.
IMPORTANT:
If the “FORCE” trimmer is adjusted, the self-learning
procedure must be repeated because the movement and deceleration
times may change.
DECELERATION (SLOW):
The operators deceleration function is used on gates to prevent the moving
leaves from slamming at speed into the limit stops at the end of the opening
and closing strokes. During Motor Time programming (see Main menu)
the control unit allows programming of deceleration in the required points
(immediately before full opening and full closing); in addition, using the
“SLOW” trimmer the force intensity can be adjusted during the deceleration
phase.
OPERATION WITH TIMER:
The control unit allows a timer to be connected in place of the open – close
pushbutton. E.g.: at 08.00 am the timer closes the contact and the control
unit commands an opening movement; at 06.00 pm the timer opens the
contact and the control unit commands a closing movement. From 08.00
am - 06.00 pm at the end of the opening cycle the control unit disables the
flashing light, automatic closing and the remotes.