![Comelit VEDO10 Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/comelit/vedo10/vedo10_technical-manual_2640394007.webp)
7
VEDO10
VEDO34
VEDO34M
VEDO68
VEDO68M
Dimensions (L x H x P)
260 x 280 x 80 mm
260 x 280 x 80 mm
440 x 315 x 95 mm
260 x 280 x 80 mm
440 x 315 x 95 mm
Weight (without battery)
1313g
1313g
3845 (with PSU15)
4039 (with PSU50)
1313g
3845 (with PSU15)
4039 (with PSU50)
Power supply units supported
PSU15
PSU15
PSU15
PSU50
PSU15
PSU15
PSU50
Batteries supported
Art. 30076003
12V/7Ah
Art. 30076003
12V/7Ah
Art. 30076003
12V/7Ah
Art. 30076004
12V and 18Ah
Art. 30076003
12V/7Ah
Art. 30076003
12V/7Ah
Art. 30076004
12V and 18Ah
Max. battery charging current
0.8A
Battery 80% charging time
8h
8h
8h/19h
8h
8h/19h
Low Battery Fault Generation in presence of EPS
12V
Low Battery Fault Generation in absence of EPS
11.5V
Control panel switch-off in absence of EPS for
Protection against deep discharges (the battery is
disconnected to avoid damage)
10.5V
Maximum current for V+SIR outputs
0.75A
Intervention voltage of the protection against voltage
surges: battery disconnection
15V
Maximum current for V+bus,V+AUX outputs
1.5A
Output voltage operating range (Vbus, VAUX1, VAUX2)
10 ~ 15 V
CN1 input voltage operating range
12.8 ~ 15 V
CN2 input voltage operating range (Battery)
10.5 ~ 15 V
Control panel card consumption (min./max.)
Control panel in standby:
47mA +
All active outputs:
37mA +
PSTA active and communicating:
30mA +
Audio:
1mA +
GSM:
27mA idle, 47mA communi
IP:
69mA
Maximum consumption (with audio module, IP module
active and connected, GSM module transmitting)
Control panel in alarm status with all expansions active: 230mA
Control panel in standby with all expansions active: 144mA
Maximum current available for external devices
Depends on the control panel configuration.
Grade 2:
580mA – mean current absorbed
by the control panel.
Depends on the
control panel
configuration.
With battery Art.
30076004 12V and
18Ah
Grade 2:
1500mA
– mean current
absorbed by the
control panel.
Depends on the
control panel
configuration.
Grade 2:
580mA
– mean current
absorbed by the
control panel.
Depends on the
control panel
configuration.
With battery Art.
30076004 12V and
18Ah
Grade 2:
1500mA
– mean current
absorbed by the
control panel.
Maximum current delivered to outputs TC1 and TC2
100mA
Relay contacts capacity in output exchange NO-COM-
NC
3A @ 24V
Operating temperature and Operating humidity
-10° / + 55° with warm dry air
-10° / + 40° C with max + 93% RH (not condensed)
Safety grade
2 according to EN50131-1
*
Type of power supply unit
TYPE A according to standard EN50131-6
Environmental class
II according to EN50131-1
1.2.2 Power supply unit technical specifications
Technical specifications complying with standard
EN50131-6
(new standard which establishes the required performances of a power
supply unit in alarm systems).
The control panel is certifiable up to grade 2 according to standard EN50131-1. It is possible to maintain grade 2 certification only if the
system is made of components of grade II or higher.
Articles certifiable with safety grade 2 according to standard EN50131-1:
Housings
: Art.
BOXPLASTIC, BOXMETAL
Control panel cards:
Art. PCBVEDO10, PCBVEDO34, PCBVEDO68
Internal expansions:
Art.
VEDOVOICE, VEDOGSM, VEDOIP
Keypads and activators:
Art. VEDOLCD, VEDOLCDPROX
Expansions on 485 bus:
Art.
VEDO8I8O, VEDORF
Power supply units:
Art.
PSU15, PSU50
Power supply unit management card:
Art.
PCBPSU
Isolators:
Art.
VEDOISO
Bidirectional PET Immunity infrared sensor, via radio:
Art.
RFPIRP
Magnetic contact sensor with radio transceiver:
Art. RFMAGW / RFMAGB
4-key radio control:
Art. RFREMOTE4
Self-powered internal siren:
Art. RFINTSIR
Self-powered external siren:
Art.
RFEXTSIR
* Respecting any indications for configuration and installation