Comelit VEDO10 Скачать руководство пользователя страница 49

 

49

1. 

Press the prog key on the keypad: the display will show the 

message 1 Config. Bus followed by two vertical arrows (up 

and down).

2. 

Press confirm  .

3. 

Enter  the  serial  number  of  the  first  keypad  by  typing  the 

digits 001 in sequence, and then press confirm.

4. 

The display now shows the message SERIAL COM. Speed: 

with the proposal "38400".

5. 

Press confirm. 

1. 

From the keypad, enter a valid user code (default 111111) 

followed by either the Partial 1 key or the Partial 2 key.

2. 

If necessary, use the up and down navigation keys to select a different 

scenario from the proposed scenario, and then press Confirm.

3. 

The  keypad  confirms  the  action  with  the  message: 

“ACTIVATED”

1. 

From the keypad, enter a valid user code (the default setting 

is 111111) and then press the ON key

2. 

The keypad asks for confirmation: “TOTAL ACTIVATION?”

3. 

Press the Confirm key to confirm.

4. 

The  keypad  confirms  the  action  with  the  message: 

“ACTIVATED”

 

To change the date and time from the keypad, you 

need to go into programming mode.

1. 

From the keypad, enter a valid installer code (default master 

code 001961).

2. 

Press Prog.

3. 

The  first  and  second  lines  of  the  display  will  show  the 

messages “Main Menu” and “Parameter Prog.” respectively, 

indicating that you can now modify the system options

4. 

Press the Confirm key to enter the respective submenus.

5. 

Using the navigation keys (up and down) select 

“ProximityKeys” submenu. Press confirm.

6. 

The display will show the message “Key 1” and below it, the 

parameter that you can modify, namely “Description”

7. 

Using the navigation keys (left and right), select the number 

of the key you intend to acquire.

8. 

Press  Confirm  if  you  intend  to  change  the  description, 

then confirm to make the change or press C to leave the 

description as it is.

9. 

Using the navigation keys (up and down), select the 

"Acquire"  submenu. Still using the navigation keys, select 

the type of peripheral from which you intend to acquire the 

key code and its bus address, then press Confirm again.

10. 

The display will show the message “Acq. Key: In progress...”

11. 

Bring the key close to the RFID reader: the message will 

change from "In progress..." to "Acquired".

12. 

Press  Confirm:  the  display  will  show  a  description  of  the 

colour of the key's plastic housing

13. 

Press  Confirm  again  to  associate  the  key  to  the  desired 

user.

14. 

Once you have finished making changes from the keypad, 

remember to transfer them to the PC by means of the 

Comelit alarm control panels configuration programme.

As installer:

As user:

1. 

Go into programming mode as an installer (see relevant 

paragraph).

2. 

Using the navigation keys, select “System Mgmt.”, then 

continue as a user.

1. 

Go into programming mode as a user (see relevant 

paragraph).

2. 

Using the navigation keys (up and down), select the 

“Options” menu on the second line of the display, and press 

Confirm.

3. 

Using the navigation keys (up and down), select the “Change 

date/time” option on the second line, and press Confirm.

4. 

The first line will show DD-MM-YY (day, month and year) 

and the second line will display the date set on the control 

panel.

5. 

Enter the date using the number keys (e.g.: 1 September 

2012 becomes 010912), then confirm.

6. 

The first line of the display now shows HH-MM (hours and 

minutes) and the second line shows the time set on the 

control panel.

7. 

Enter the time in the format displayed (e.g. 1.15 pm becomes 

1315), then confirm.

8. 

This done, the display will show the message PARAMETER 

CHANGED.

9. 

Press C to go up one level in the menu, or C repeatedly until 

the date and time appear on the keypad.

1. 

From the keypad, enter a valid user code (the default setting 

is 111111) and then press the OFF key.

2. 

The  keypad  confirms  the  action  with  the  message: 

“DEACTIVATED”

3. 

Deactivation will also deactivate any alarms in progress 

within a few seconds.

1. 

From the keypad, enter a valid user code (default 111111)

2. 

Press Prog.

3. 

The first line of the display will show the message "System 

Mgmt.” indicating that you can now modify the system 

options.

1. 

Go into programming mode as a user (see previous 

paragraph).

2. 

Using the navigation keys (up and down), select the 

“COMMANDS” menu on the second line of the display, and 

press Confirm: the message “GENERATE COMMAND” will 

appear on the first line of the display.

3. 

Using the navigation keys (up and down), select “AUTH. 

INSTALLER?” on the second line, and press Confirm: the 

message “DONE” will appear on the display.

4. 

Press C until you have exited the menus completely (i.e. 

until the date and time are displayed on the keypad).

5. 

From the keypad, enter a valid installer code (default master 

code 001961).

6. 

Press Prog.

7. 

The  first  and  second  lines  of  the  display  will  show  the 

messages “Main Menu” and “Parameter Mgmt.” indicating 

 

The installer code must be authorised by the user, so 

the procedure is as follows:

1. 

From the keypad, enter a valid user code (default 111111).

2. 

Once the code has been recognised, press the Prog key 

until the message “DONE” appears on the screen.

3. 

This will mute the alarm.

  

» Keypad number one will now be taken in charge by the 

control panel and can be used for activating, deactivating 

and configuring the system.

5.3.7 Total activation of the alarm system

5.3.13 Changing date and time

5.3.14 Acquiring an RFID key code from the keypad

5.3.8 Partial activation of the alarm system / 

execution of a scenario

5.3.9 Total deactivation of the alarm system

5.3.11 Entering programming as a User

5.3.12 Entering programming as an Installer 

(installer code authorisation)

5.3.10 Muting an alarm with the system deactivated

that you can now display or modify the system options.

8. 

From this position, you can use the navigation keys to 

select either the “System Mgmt.” menu, which corresponds 

to the user menu, or the “Parameter Prog.” menu, which is 

reserved for the installer.

9. 

Press the Confirm key to enter the respective submenus.

5.3.6 Setting the keypad serial number

At  first  start-up,  the  keypad  displays  the  message  NOT 

CONNECTED. To enable the control panel to recognise 

keypad number 1 (the only keypad that can be recognised by 

the control panel by default), proceed as follows:

Содержание VEDO10

Страница 1: ...Passion Technology Design EN TECHNICAL MANUAL Technical manual for the Vedo system...

Страница 2: ...mally closed NC 19 3 6 2 Normally open NO 19 3 6 3 Single balance 19 3 6 4 Double balance 19 3 6 5 Triple balance 20 3 6 6 Triple balance with jamming 20 3 6 7 Double zone double 20 3 6 8 Double zone...

Страница 3: ...NFIGURATION JUMPERS 31 CONNECTING VEDOCCTV WITH SWITCH HUB AND CONTROL PANEL POWER SUPPLY 31 CONNECTING THE VEDOCCTV MODULE WITH POE SWITCH HUB 31 MMS SUPPORT SYSTEM DESCRIPTION AND MINIMUM REQUIREMEN...

Страница 4: ...er code authorisation 49 5 3 13 Changing date and time 49 5 3 14 Acquiring an RFID key code from the keypad 49 5 3 15 Acquiring a radio sensor code from the keypad 50 5 3 16 Acquiring a radio control...

Страница 5: ...ontrol panel can be programmed directly from the keypad or more easily by means of dedicated software The audio messages can be modified only by using the programming software from a PC The associatio...

Страница 6: ...e CONTACT ID protocol Yes Priority in processing and indicating signals 1 Alarm Events 2 Sabotage 3 Malfunctions 4 Exclusions 5 Other events In the telephone options it is possible to set the priority...

Страница 7: ...he control panel Depends on the control panel configuration With battery Art 30076004 12V and 18Ah Grade 2 1500mA mean current absorbed by the control panel Depends on the control panel configuration...

Страница 8: ...erating temperature and Operating humidity 10 55 with warm dry air 10 40 C with max 93 RH not condensed Safety grade 2 according to EN50131 1 Environmental class II according to EN50131 1 1 2 3 Power...

Страница 9: ...or power supply unit PSU15 7 Internal fuse 250V T2A for Art PSU15 Internal fuse 250V T2 5A for PSU50 8 Cable for connecting the power supply unit to earth Art PSU15 9 High Voltage Cables 10 Cable for...

Страница 10: ...rew for power supply unit Art PSU15 Optional positions a Holes for fitting supports for fixing the expansion Art VEDO8I8O b Screws for fixing and holding PAL module Art VEDOCCTV for further informatio...

Страница 11: ...ing in contact with 230V wires If the mains cable inlet hole is shared with other cables of the control panel wiring as in the picture use a mains power supply cable with double insulation 1 GSM anten...

Страница 12: ...ge 39 Art BOXPLASTIC complies with standards EN50131 1 EN50131 3 EN50131 6 EN50136 1 1 EN50136 2 1 EN 60950 1 2006 A11 2009 A1 2010 A12 2011 A2 2013 EN50130 4 Art BOXMETAL complies with standards EN50...

Страница 13: ...3 8 V self resettable fuse for protecting the power supply to the siren outputs 1 5A 13 8 V self resettable fuse for protecting the power supply to the RS485 buses 1 5A 13 8 V self resettable fuse for...

Страница 14: ...r supply negative I7 Programmable input zone 7 I8 Programmable input zone 8 V AUX Power supply positive for signal sensors Electrically connected to terminal 1 of the same terminal block Shares its li...

Страница 15: ...od ule Art VEDOVOICE Optional contains the part of the audio messages relating to the digital dialler i e contains the audio messages to be sent on the standard or GSM telephone line Equipped with a p...

Страница 16: ...ACCORDING TO STANDARD EN50136 2 1 FITTING THE GSM MODULE Insert the plastic spacers in the relevant holes Then taking care to plug the module connector into the control panel connector designated MOD...

Страница 17: ...an external antenna Art 2G50000296 For this purpose there is a pre marked section to allow easy exit of the antenna cable OK NO FITTING THE SIM CARD The SIM card must be enabled and if it is a pay as...

Страница 18: ...o the control panel card Art PCBVEDO10 Art PCBVEDO34 Art PCBVEDO68 Respecting any indications for configuration and installation SPECIFICATIONS ACCORDING TO STANDARD EN50136 2 1 Make sure the card on...

Страница 19: ...cond balancing resistor also 1 8K makes it possible to distinguish an alarm state from a line sabotage state both in the event of cutting and short circuit IMPORTANT input balancing resistors if used...

Страница 20: ...d balancing resistor 3 3K disposed in parallel to the contact of the second sensor to be monitored This configuration makes it possible to distinguish between an alarm electrical fault state and a lin...

Страница 21: ...DOLCD and keypad with RFID key reader Art VEDOLCDPROX MAIN FEATURES The LCD keypad allows an authorised user to enable and disable the system to check the system status and manage its general features...

Страница 22: ...red speed 3 Once you have set the speed set DIP switch 6 back to OFF The speed is now set 4 Set DIP switches 1 to 5 according to the address to be set Note that the standard speed of the bus for VEDO...

Страница 23: ...RS485 data bus B MEANING OF THE LEDS WHEN THE CYCLE IS IN PROGRESS LED Status Function Red On Request execution of action associated with LED Slow flash Action associated with LED requires forcing to...

Страница 24: ...of the bytes that form the unique code of the key and can have a value between 1 and 2 32 1 therefore generating a maximum number of 2 32 2 possible values Vedo Touch Minitouch is an innovative inter...

Страница 25: ...HE BUS Like any other device connected to the 485 bus the Vedo Touch Mini Touch must respond to a single address that can be configured from the display The device Mini Touch Art 20034607 must be powe...

Страница 26: ...according to EN50131 1 1 CV8 485 line termination 2 Terminal block for system connection 3 CV5 Jumper for video closure 4 CN4 CN5 Monitor bracket connectors 1 Microphone 2 Touch screen 3 Key sensor 4...

Страница 27: ...button programmable 5 Privacy Doctor key programmable 6 Self ignition key programmable 7 Open doors key 8 Video memory key 9 Key 3 programmable default off 10 Key 2 programmable default general actua...

Страница 28: ...ing with 2 self tapping screws The cover is secured to the base by means of three fasteners on the top and two spring clips at the bottom There are also two safety screws to prevent accidental opening...

Страница 29: ...and or volumetric detectors and supervised wireless sirens to the control panel 1 Dip Switch 2 Anti tear tamper 3 Anti tamper tamper Holes for fixing the VEDORF card to the metal housing Art BOXMETAL...

Страница 30: ...lting the recorded films of the cameras on the system 4 IP cameras and one chosen analogue camera by the system manager Vedo Touch Mini Touch Icona Manager VIP or by App 1 Reserved terminals 2 Etherne...

Страница 31: ...o operate in case of temporary absence of mains power The power supply from the control panel allows the device to operate in case of temporary absence of mains power IMPORTANT In order to use the vid...

Страница 32: ...SIREN V COM V V TC1 TC2 V SIR NO NC COM M2 SELF POWERED SIREN V COM V V TC TC V S NO NC CO M 3 WIRE CONNECTION 2 WIRE CONNECTION SELF POWERED SIREN V COM V V TC1 TC2 V SIR NO NC COM M2 SELF POWERED S...

Страница 33: ...d as TC If the output is configured as a TC in standby the output will be fluctuating no voltage but in active status it will close terminal TC to positive This type of behaviour can be figured with t...

Страница 34: ...ed to 1 5A V Power supply negative output reference 485 communication BUS power supply A RS485 data BUS for connection to other devices OUT A B RS485 data BUS for connection to other devices OUT B bus...

Страница 35: ...ect the entire system The device is equipped with a dual connection to the VEDO system 485 BUS the IN port input the OUT port output The section of the system that you want to isolate from the rest mu...

Страница 36: ...package on the BUS To access dip switch S1 and jumpers JP1 and JP2 you must remove the plastic casing at the top DEFAULT The 24H terminal needs the Tamper contact to be connected in single balanced co...

Страница 37: ...HOUSING ART BOXPLASTIC 4 3 FIXING THE HOUSING ART BOXPLASTIC TO THE WALL 4 2 PREPARING THE HOUSING ART BOXPLASTIC If the control panel is already assembled you will have to remove the electronic cards...

Страница 38: ...CONTROL PANEL CARD ART PCBVEDO10 PCBVEDO34 PCBVEDO68 AND PCBPSU IN A HOUSING ART BOXPLASTIC 4 5 MOUNTING THE POWER SUPPLY UNIT PSU15 IN A HOUSING ART BOXPLASTIC 4 6 MOUNTING THE EXPANSION ART VEDO8I8...

Страница 39: ...ART BOXMETAL 4 8 FIXING THE HOUSING ART BOXMETAL TO THE WALL 2 1 1 4 9 MOUNTING THE CONTROL PANEL CARD ART PCBVEDO10 PCBVEDO34 PCBVEDO68 AND PCBPSU IN A HOUSING ART BOXMETAL 4 10 MOUNTING THE EXPANSI...

Страница 40: ...40 2 1 1 2 3 4 CLACK 1 2 2 1 3 BLOCKING OPTIONAL 4 11 MOUNTING THE POWER SUPPLY UNIT PSU15 PSU50 IN A HOUSING ART BOXMETAL 4 12 MOUNTING THE MODULE ART VEDOCCTV IN A METAL HOUSING ART BOXMETAL...

Страница 41: ...41 2 2 3 2 1 2 1 1 1 4 4 2 1 2 1 3 3 1 3 2 2 1 3 2 2 4 13 MOUNTING THE KEYPAD ART VEDOLCD ART VEDOLCDPROX ON BOX 503 4 14 MOUNTING THE KEYPAD ON THE WALL ART VEDOLCD ART VEDOLCDPROX OPENING OPENING...

Страница 42: ...42 3 150 cm 120 cm 2 1 4 4 15 MOUNTING THE VEDO TOUCH ART VEDOTOUCH MINI TOUCH ART 20034607 ON BOX 503 OPENING...

Страница 43: ...43 2 3 4 5 1 3 145 150 cm 115 125 cm 2 14 5 cm 14 5 cm 1 6 5 ALTO UP HAUT OBEN 4 9 8 1 2 2 3 7 1 3 2 4 16 MOUNTING PLANUX MONITOR ART 20034801 WITH FLUSH MOUNTED BOX ART 6117 DISASSEMBLY...

Страница 44: ...44 3 145 150 cm 115 125 cm 2 14 5 cm 14 5 cm 1 6 5 4 9 2 2 1 3 8 7 10 4 17 MOUNTING PLANUX MONITOR ART 20034801 WITH WALL SUPPORT ART 6120 DISASSEMBLY...

Страница 45: ...3310W 4A 7 160 cm 130 cm 1 2 2 1 2 6 14 2 cm 14 7 cm 2 1 2 1 1 2 1 2 CLACK 1 2 1 3B 3A 5A 8 3C 4 18 WALL MOUNTING ICONA MANAGER VIP ART 6620 SU 503 SERIES BOX ROUND BOX DISASSEMBLY Art 6620 optional w...

Страница 46: ...6 2 1 1 1 2 CLACK 2 3 6 9 160 cm 130 cm Lmax 10 cm Lmin 6 cm 1 2 Art 20003310W 2 5 8 14 2 cm 14 7 cm 2 3 4 5 1 2 1 1 2 1 4 7 4 19 MOUNTING ICONA MANAGER VIP ON A FLUSH MOUNTED BOX ART 6117 DISASSEMBLY...

Страница 47: ...1 2 1 2 1 2 1 1 3 2 VEDO8I8O VEDORF 3 1 2 2 1 4 20 PREPARING THE PLASTIC HOUSING FOR MOUNTING THE EXPANSION ART VEDORF VEDO8I8O 4 21 WALL MOUNTING THE PLASTIC HOUSING FOR MOUNTING THE EXPANSION ART V...

Страница 48: ...next level or to confirm the entry of a new data item Press C to return to the previous menu To modify a numerical value type in the desired value following the format shown on the display omitting no...

Страница 49: ...st line will show DD MM YY day month and year and the second line will display the date set on the control panel 5 Enter the date using the number keys e g 1 September 2012 becomes 010912 then confirm...

Страница 50: ...keypad remember to transfer them to the PC by means of the Comelit alarm control panels configuration programme 1 Disconnect the siren battery if connected and disconnect the audio from its connector...

Страница 51: ...u depth level you are it is possible to use fast navigation by inserting the coordinates The coordinates are inserted in pairs of lines or columns for each navigation depth level Each coordinate is co...

Страница 52: ...on 1 1 1 7 x 2 Tamper areas At least one selected area 1 1 1 7 x 3 Technical areas At least one selected area 1 1 1 7 x 4 Tamper cycles Unlimited 1 1 1 7 x 5 Technical cycles Unlimited 1 1 1 7 x 8 Unl...

Страница 53: ...Radio zones Vedo 10 x from 1 to 16 Vedo 34 x from 1 to 64 Vedo 68 x from 1 to 96 Indices Parameters Configurations necessary to guarantee Grade 2 certification 1 1 1 13 x 3 Monitoring Maximum 20 minut...

Страница 54: ...ognition timeout 60 seconds 1 1 1 27 1 9 Telephone line parameters pstn Selected 1 1 1 27 1 10 Length of call 60 seconds 1 1 1 27 1 12 Voice message repetition 5 1 1 1 27 1 14 Attempts 3 1 1 1 27 1 15...

Страница 55: ...Action Only set selected 1 1 1 31 x 6 y 155 Panic Alarm Action Only set selected 1 1 1 31 x 6 y 156 Robbery Alarm Action Only set selected 1 1 1 31 x 6 y 157 Flood Alarm Action Only set selected 1 1...

Страница 56: ...eset alarms Selected 1 1 1 43 x 114 Stop alarms Selected 1 1 1 43 x 115 Stop telephone calls Selected 1 1 1 43 x 116 Timed activation error Selected 1 1 1 43 x 119 Technical programming Selected 1 1 1...

Страница 57: ...ES n X 0 22 mm2 0 50 0 085 8 5 n X 0 50 mm2 0 80 0 032 3 2 n X 0 75 mm2 0 90 0 026 2 6 n X 1 mm2 1 0 020 2 n X 1 5 mm2 1 28 0 013 1 3 n X 2 5 mm2 1 65 0 008 0 82 For the bus signals A and B you can us...

Страница 58: ...to go through a hub or a network switch The control panel will be connected by means of a network cable in straight configuration In many cases it will be possible to buy a standard cable of suitable...

Страница 59: ...59...

Страница 60: ...w w w c o m e l i t g r o u p c o m Passion Technology Design 3rd edition 10 2015 code 2G40001435 8 8 023903 023903 306743 306743...