WIRED OUTPUT CONFIGURATION
Indices
Parameters
Configurations necessary to
guarantee Grade 2 certification
1.1.1.17.x.12.1.1
Timer in And
* No timer
1.1.1.17.x.12.1.2
Timer in Or
* No timer
1.1.1.17.x.12.1.7
Events logic
* OR
1.1.1.17.x.12.1.10
Send digital dialler
Selected
1.1.1.17.x.12.1.12
Output activation only with
system activated
Selected if connected to a siren
* These apply only to outputs connected to sirens.
For standard EN50131 an output of the control panel must be activated in the case of a fault and
must not be connected to a siren.
5.5.13 User
Vedo 10
x: from 1 to 8 /
Vedo 34
x: from 1 to 32 /
Vedo 68
x: from 1 to 50
Indices
Parameters
Configurations necessary to
guarantee Grade 2 certification
1.1.1.20.x.18
Send digital dialler
Selected
The codes accepted must have 6 figures and range from 000000 to 999998. Code 999999 is
not an accepted code. The robbery code is the user code + 1.
Example: user code 111111, the corresponding robbery code is 111112. Code 119999,
robbery code = 120000. Code 123459, robbery code = 123460 - It is not possible to register
a user code corresponding to an existing user code + 1, since this new code corresponds to
the robbery code of the existing user.
In the system it is therefore possible to store up to a theoretical maximum of 999943 user
codes. The calculation is the result of the fact that it is not possible to create a user code that
is the same as an existing user code + (which is the robbery code). The actual maximum
number of user codes that can be fitted is shown in the table "USER CODES / KEYS /
REMOTE CONTROLS" on page 5.
The authorised user can perform an infinite number of changes of his user code and can
create and eliminate another user, whereas he is unable to modify any user code other than
his own.
CODE TYPE
x: from 1 to 9
Indices
Parameters
Configurations necessary to
guarantee Grade 2 certification
1.1.1.22.x.19
Request assistance
Active for at least one type of user (x
enab. inst.) and one type of installer (x
enab. manuf.)
1.1.1.22.x.20
Change Pin
Active only for installers
1.1.1.22.x.21
Reset control panel
Active for manufacturer
1.1.1.22.x.23
Fault management
Active
1.1.1.22.x.26
Programme from PC
Active for installer and manufacturer
1.1.1.22.x.42
Codes menu
Active
1.1.1.22.x.44
FW Update
Only for manufacturer
5.5.14 Installers
Vedo 10
x: from 1 to 3 /
Vedo 34
x: from 1 to 6 /
Vedo 68
x: from 1 to 6
Indices
Parameters
Configurations necessary to
guarantee Grade 2 certification
1.1.1.21.x.6
Send digital dialler
Selected
CODE TYPE
x: from 1 to 9
Indices
Parameters
Configurations necessary to
guarantee Grade 2 certification
1.1.1.22.x.19
Request assistance
Active for at least one type of user (x
enab. inst.) and one type of installer (x
enab. manuf.)
1.1.1.22.x.20
Change Pin
Active only for installers
1.1.1.22.x.21
Reset control panel
Active for manufacturer
1.1.1.22.x.23
Fault management
Active
1.1.1.22.x.26
Programme from PC
Active for installer and manufacturer
1.1.1.22.x.42
Codes menu
Active
1.1.1.22.x.44
FW Update
Only for manufacturer
5.5.15 GSM settings
Indices
Parameters
Configurations necessary to
guarantee Grade 2 certification
1.1.1.25.1.24
Jamming control
Selected
5.5.16 Telephone Options
Indices
Parameters
Configurations necessary to
guarantee Grade 2 certification
1.1.1.27.1.5
Tones recognition timeout
= 60 seconds
1.1.1.27.1.9
Telephone line parameters
(pstn)
Selected
1.1.1.27.1.10
Length of call
= 60 seconds
1.1.1.27.1.12
Voice message repetition
5
1.1.1.27.1.14
Attempts
3
1.1.1.27.1.15
Send message
Press key 1
1.1.1.27.1.16
Termination with
confirmation
Selected
1.1.1.27.1.19
Tones control (pstn)
Selected
1.1.1.27.1.20
Telephone line control
(pstn)
Selected
5.5.17 Phone Book / Email
x: from 1 to 16
Indices
Parameters
Configurations necessary to
guarantee Grade 2 certification
1.1.1.28.x.1
Description
*
1.1.1.28.x.2
Phone
*
* If the digital dialler is not active, at least one user must be present
5.5.18 Digital dialler contacts list
x: from 1 to 4
Indices
Parameters
Configurations necessary to
guarantee Grade 2 certification
1.1.1.29.x.2
Periodic test
Active
1.1.1.29.x.4
Protocol
Contact ID
1.1.1.29.x.5
Test period
<=25h
1.1.1.29.x.6
Attempts
1
1.1.1.29.x.7
Number to call
If the digital dialler is not active, at
least the telephone sounder must be
correctly configured
1.1.1.29.x.8
Customer code
Valorised
1.1.1.29.x.10
Periodic test start date
Value before date of activating the
system (must be before current date)
5.5.19 Generic events
Vedo 10
x: from 1 to 20 /
Vedo 34
x: from 1 to 32 /
Vedo 68
x: from 1 to 48
Indices
Parameters
Configurations necessary to
guarantee Grade 2 certification
1.1.1.30.x.2
Event
*
1.1.1.30.x.5
Activation voice message
Active for at least one phone
1.1.1.30.x.6
Reset voice message
Active for at least one phone
* If the digital dialler is not active, the following events must be signalled:
- Robbery Alarm
- Burglar Alarm
- H24 Alarm
- Sabotage
- No network
- Radio sensor battery low
- Radio siren battery low
- Auto-activation failed
- Failed activation fault
- Zone fault
- Robbery zone fault
- Motion sensor jamming fault
Of course it must also be completed by sending the respective voice message.
5.5.20 Detailed events
x: from 1 to 8
y: from 1 to 6
Indices
Parameters
Configurations necessary to
guarantee Grade 2 certification
1.1.1.31.x.3
Dialler telephones
At least one selected
1.1.1.31.x.4
Areas
At least one selected
DETAILED EVENTS FLAGS
Indices
Parameters
Configurations necessary to
guarantee Grade 2 certification
1.1.1.31.x.6.y.2
Zone Exclusion
* Selected
1.1.1.31.x.6.y.3
Zone Isolation
* Selected
1.1.1.31.x.6.y.4
Total ON
* Only set selected
1.1.1.31.x.6.y.5
Partial 1 ON
* Only set selected
1.1.1.31.x.6.y.6
Partial 2 ON
* Only set selected
1.1.1.31.x.6.y.7
Effective activation
* Only set selected
1.1.1.31.x.6.y.8
Deactivated
* Only set selected
1.1.1.31.x.6.y.10 Burglar Alarm
* Selected
1.1.1.31.x.6.y.11 24H Alarm
* Selected
1.1.1.31.x.6.y.12 Fire Alarm
* Selected
1.1.1.31.x.6.y.13 Panic Alarm
* Selected
1.1.1.31.x.6.y.14 Robbery Alarm
* Selected
1.1.1.31.x.6.y.15 Flood alarm
* Selected
1.1.1.31.x.6.y.16 Gas Alarm
* Selected
1.1.1.31.x.6.y.17 Medical Alarm
* Selected
1.1.1.31.x.6.y.18 Zones Sabotage Tamper
* Selected
1.1.1.31.x.6.y.19 Siren tamper
* Selected
1.1.1.31.x.6.y.20 Radio device jamming
* Selected
1.1.1.31.x.6.y.21 Tamper App
* Selected
1.1.1.31.x.6.y.26 Bus I/O expansions tamper
* Selected
1.1.1.31.x.6.y.27 Bus keypad tamper
* Selected
1.1.1.31.x.6.y.28 RFID tamper
* Selected
1.1.1.31.x.6.y.29 Safetouch tamper
* Selected
1.1.1.31.x.6.y.30 Touch Tamper
* Selected
1.1.1.31.x.6.y.31 Bus power supply station or
isolator tamper
* Selected
1.1.1.31.x.6.y.32 Bus radio concentrator
tamper
* Selected
1.1.1.31.x.6.y.33 Bus siren tamper
* Selected
1.1.1.31.x.6.y.34 Alarm communication
device tamper
* Selected
1.1.1.31.x.6.y.35 IP expansion tamper
* Selected