Cisco ONS 15454 DWDM Procedure Guide, R8.0
78-17704-02
Chapter 1 Install the Shelf and Common Control Cards
NTP- G20 Install Alarm Wires on the MIC-A/P (ETSI Only)
Step 2
Connect the other end of the alarm and control wires according to local site practice.
Step 3
Connect the DB-62 connector to the ALARM IN/OUT connector on the MIC-A/P faceplate.
Step 4
Tighten the screws of the connector on the alarm cable.
Step 5
Return to your originating procedure (NTP).
37
ALMOUP0–
Normally open output pair number 1
38
Normally open output pair number 1
39
FGND
Ground
40
ALMOUP1–
Normally open output pair number 2
41
Normally open output pair number 2
42
ALMOUP2–
Normally open output pair number 3
43
Normally open output pair number 3
44
ALMOUP3–
Normally open output pair number 4
45
Normally open output pair number 4
46
AUDALM0–
Normally open minor audible alarm
47
Normally open minor audible alarm
48
AUDALM1–
Normally open major audible alarm
49
Normally open major audible alarm
50
AUDALM2–
Normally open critical audible alarm
51
Normally open critical audible alarm
52
FGND
Ground
53
AUDALM3–
Normally open remote audible alarm
54
Normally open remote audible alarm
55
VISALM0–
Normally open minor visible alarm
56
Normally open minor visible alarm
57
VISALM1–
Normally open major visible alarm
58
Normally open major visible alarm
59
VISALM2–
Normally open minor visible alarm
60
Normally open minor visible alarm
61
VISALM3–
Normally open minor visible alarm
62
Normally open minor visible alarm
Table 1-3
Alarm Pin Assignments (continued)
DB-62 Pin Connector
Signal Name
Function