1-38
Cisco ONS 15454 DWDM Procedure Guide, R8.0
78-17704-02
Chapter 1 Install the Shelf and Common Control Cards
NTP- G18 Connect Office Power to the ONS 15454 ANSI
Note
If the system loses power or if both TCC2/TCC2P cards are reset, you must reset the ONS 15454 ETSI
clock. After powering down, the date defaults to January 1, 1970, 00:04:15. To reset the clock, see the
“NTP-G24 Set Up Name, Date, Time, and Contact Information” procedure on page 3-10
Step 1
Verify that the MIC-A/P FMEC is installed in Slot 23 and the MIC-C/T/P FMEC is installed in Slot 24 of the
EFCA.
Step 2
Attach the connector on the end of the power cable to the power FMEC.
Step 3
Tighten the screws of the connector on the power cable.
Step 4
Connect the power cable to the fuse panel or power source. Use the pin connections in
.
Step 5
Return to your originating procedure (NTP).
DLP-G18 Connect Office Power to the ONS 15454 ANSI
Table 1-1
Pin Connection of the Power FMECs
Pin
Function
Cable Color
A1
Battery return
Black
A2
–48 V battery
Red
A3
Ground
Green with yellow stripes
Purpose
This task connects power to the ONS 15454 ANSI shelf.
Tools/Equipment
#2 Phillips Dynamometric screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Wire wrapper
Wire cutters
Wire strippers
Crimp tool
Fuse panel
Power cable (from fuse and alarm panel to assembly), #10 AWG, copper
conductors, 194 degrees F [90 degrees C])
Ground cable #6 AWG stranded
Listed pressure terminal connectors such as ring and fork types; connectors
must be suitable for #10 AWG copper conductors
Prerequisite Procedures
DLP-G16 Connect the Office Ground to the ONS 15454 ANSI, page 1-35
Required/As Needed
Required