1-18
Cisco ONS 15454 DWDM Procedure Guide, R8.0
78-17704-02
Chapter 1 Install the Shelf and Common Control Cards
NTP- G8 Install the Air Ramp for Standard and Deep Door ONS 15454
Figure 1-5
Mounting the Air Ramp in a Rack
Step 4
Repeat this task for every shelf assembly you need to install.
Step 5
Return to your originating procedure (NTP).
DLP-G8 Install the Air Ramp for Standard and Deep Door ONS 15454
Step 1
The air ramp requires 50 mm of space in a standard 19-inch (482.6-mm) or 23-inch (584.2-mm) rack.
Locate the rack mount unit (RMU) space specified in your site plan. Refer to the “Shelf Assembly
Hardware” chapter in the
Cisco ONS 15454 DWDM Reference Manual
for more information about air
ramp placement.
Step 2
Verify the rack type of your air ramp installation. The brackets are compatible with the following racks.
•
19-inch racks as defined in IEC 297-1(2 Nos.)
•
19-inch for deep door configuration (2 Nos.)
Purpose
Use this task to install the air ramp for standard and deep door ONS 15454
Tools/Equipment
#2 Phillips Dynamometric screwdriver
Prerequisite Procedures
None
Required/As Needed
As needed
Onsite/Remote
Onsite
Security Level
None
61582
Equipment rack