Chapter 1 Install the Shelf and Common Control Cards
NTP- G371 Install the Ethernet Adapter Panel
Step 2
Verify that the mounting brackets attached to the unit are correct for your rack size. Complete the
“DLP-G3 Reverse the Mounting Bracket to Fit a 19-inch (482.6-mm) Rack (ANSI Only)” task on
page 1-10
as required.
Step 3
Align the chassis with the rack mounting screw holes, insert the four screws, and tighten.
Step 4
Return to your originating procedure (NTP).
DLP-G371 Install the Ethernet Adapter Panel
Step 1
The EAP requires 1 RU in a standard 19-inch (482.6-mm), 23-inch (584.2-mm)/600 mm x 600mm, or
600 mm x 300 mm rack. Locate the RMU space specified in your site plan. Refer to the “Shelf Assembly
Hardware” chapter in the
Cisco ONS 15454 DWDM Reference Manual
for common ANSI and ETSI site
configurations.
Step 2
Verify that the mounting brackets attached to the unit are correct for your rack size. Complete the
“DLP-G3 Reverse the Mounting Bracket to Fit a 19-inch (482.6-mm) Rack (ANSI Only)” task on
page 1-10
as required.
Step 3
Align the chassis with the rack mounting screw holes, insert the four screws, and tighten.
Caution
Any paint between the EAP mounting ears and the frame of the metal rack must be removed. The area
must then be cleaned and coated with an antioxidant.
Step 4
Repeat Steps
for the second EAP.
Step 5
Return to your originating procedure (NTP).
Purpose
This task installs an Ethernet adapter panel (EAP) in an ANSI or ETSI
equipment rack. The EAP is used in multishelf node configurations to
connect the MS-ISC-100T and the TCC2/TCC2P cards in the subtending
nodes. Two EAPs are required in a multishelf configuration, one for each
MS-ISC-100T card.
Tools/Equipment
#2 Phillips Dynamometric screwdriver
Prerequisite Procedures
None
Required/As Needed
As needed
Onsite/Remote
Onsite
Security Level
None