1-60
Cisco ONS 15454 DWDM Procedure Guide, R8.0
78-17704-02
Chapter 1 Install the Shelf and Common Control Cards
NTP- G11 Install an External Wire-Wrap Panel on the AEP (ANSI Only)
Step 3
Return to your originating procedure (NTP).
NTP-G11 Install an External Wire-Wrap Panel on the AEP
(ANSI Only)
Step 1
Position the lower cover over the AEP. Make sure that the AEP AMP Champ connectors protrude
through the cutouts in the lower cover (
).
Table 1-8
Craft Interface Pin Assignments
Pin Field
Contact
Function
Craft
A1
Receive
A2
Transmit
A3
Ground
A4
DTR
Purpose
This procedure connects an external wire-wrap panel to the
ONS 15454 ANSI AEP to provide the physical alarm contacts for the AEP.
Tools/Equipment
External wire-wrap panel
Prerequisite Procedures
NTP-G9 Install the Alarm Expansion Panel (ANSI Only), page 1-46
Required/As Needed
As needed
Onsite/Remote
Onsite
Security Level
None