C H A P T E R
2
Preparing the Site
•
Temperature Requirement, on page 5
•
Humidity Requirement, on page 5
•
Altitude Requirements, on page 5
•
Dust and Contaminants, on page 5
Temperature Requirement
This switch is rated to operate at 32 to 104°F (0 to 40°C). It can be stored at -40 to 158°F (-40 to 70°C).
Humidity Requirement
This switch is rated to operate at 8- to 80-percent relative humidity with 10-percent gradation per hour. It can
be stored in an environment that has 5- to 95-percent relative humidity.
Buildings cooled with air conditioning during warm months and warmed during cold months usually maintain
an acceptable level of humidity. However, if the site is unusually humid, use a dehumidifier to maintain the
required humidity level.
Altitude Requirements
High-altitude (low-pressure) conditions outside of 0 to 10,000 feet (0 to 3050 m) can reduce the cooling
efficiency and cause electrical problems.
Dust and Contaminants
To prevent contaminant buildup and increased internal chassis temperatures, make sure that the operating
environment is as clean as possible and free of dust and other contaminants. Do not permit smoking, food, or
drinks near the switch.
Cisco Nexus 3400 Hardware Installation Guide
5
Содержание Nexus 3400 Series
Страница 6: ...Cisco Nexus 3400 Hardware Installation Guide vi Contents ...
Страница 8: ...Cisco Nexus 3400 Hardware Installation Guide viii Preface Related Documentation ...
Страница 14: ...Cisco Nexus 3400 Hardware Installation Guide 6 Preparing the Site Dust and Contaminants ...
Страница 46: ...Cisco Nexus 3400 Hardware Installation Guide 38 Installing the Chassis Starting the Switch ...
Страница 58: ...Cisco Nexus 3400 Hardware Installation Guide 50 Replacing Modules Replacing a DC Power Supply ...
Страница 64: ...Cisco Nexus 3400 Hardware Installation Guide 56 System Specifications HVDC Power Cable Specifications ...
Страница 72: ...Cisco Nexus 3400 Hardware Installation Guide 64 Spare Parts Table Spare Parts Table ...