Table 12: Grounding Practice Guidelines
Grounding Recommendations
Electromagnetic Noise
Severity Level
Environment
All lightning protection devices must be
installed in strict accordance with
manufacturer recommendations.
Conductors carrying lightning current
should be spaced away from power and
data lines in accordance with applicable
recommendations and codes. Best
grounding practices must be closely
followed.
High
Commercial building is subjected to
direct lightning strikes.
For example, some places in the United
States, such as Florida, are prone to
more lightning strikes than other areas.
Best grounding practices must be closely
followed.
High
Commercial building is located in an
area where lightning storms occur
frequently, but is not prone to direct
lightning strikes.
Best grounding practices must be closely
followed.
Medium to High
Commercial building contains a mix
of information technology equipment
and industrial equipment, such as
welding.
Best grounding practices must be closely
followed. Determine source and cause of
noise if possible, and mitigate as closely as
possible at the noise source or reduce
coupling from the noise source to the
victim equipment.
Medium
Existing commercial building is not
subject to natural environmental noise
or man-made industrial noise. This
building contains a standard office
environment. This installation has a
history of malfunction due to
electromagnetic noise.
Best grounding practices should be
followed as closely as possible.
Electromagnetic noise problems are not
anticipated, but installing a best-practice
grounding system in a new building is often
the least expensive route, and the best way
to plan for the future.
Low
New commercial building is not subject
to natural environmental noise or
man-made industrial noise. This
building contains a standard office
environment.
Best grounding practices should be
followed as much as possible.
Electromagnetic noise problems are not
anticipated, but installing a best-practice
grounding system is always recommended.
Low
Existing commercial building is not
subject to natural environmental noise
or man-made industrial noise. This
building contains a standard office
environment.
Catalyst 6840-X Switch Series Hardware Installation Guide
27
Preparing for Installation
System Grounding
Содержание Catalyst 6816-X-LE
Страница 8: ...Catalyst 6840 X Switch Series Hardware Installation Guide viii Contents ...
Страница 32: ...Catalyst 6840 X Switch Series Hardware Installation Guide 20 Product Overview Rear Panel ...
Страница 64: ...Catalyst 6840 X Switch Series Hardware Installation Guide 52 Installing the Switch Online Diagnostics ...
Страница 96: ...Catalyst 6840 X Switch Series Hardware Installation Guide 84 Troubleshooting Finding the Serial Number ...