EN - 39
AQUACIAT
POWER
Name
Status
Default
Unit
Displayed text*
Description
1 = Two stop bit
1 = Two stop bit
real_typ
0 to 1
1
-
Real Type Management
Real Type Management
0 = Float X10
0 = Float X10
1 = IEE 754
1 = IEE 754
reg32bit
0 to 1
1
-
Enable 32 bits registers
Enable 32 bits registers
0 = IR/HR in 16 bit mode
0 = IR/HR in 16 bit mode
1 = IR/HR in 32 bit mode
1 = IR/HR in 32 bit mode
* Depends on the selected language (French by default).
Modbus TCP/IP Config. Menu – MODBUSIP
Name
Status
Default
Unit
Displayed text*
Description
modip_en
no/yes
no
-
TCP/IP Server Enable
TCP/IP Server Enable
ser_UID
1 to 247
1
-
Server UID
Server UID
port_nbr
0 to 65535
502
-
IP Port Number
IP Port Number
metric
no/yes
yes
-
Metric Unit
Metric Unit
swap_b
0 to 1
0
-
Swap Bytes
Swap Bytes
0 = Big Endian
0 = Big Endian
1 = Little Endian
1 = Little Endian
real_typ
0 to 1
1
-
Real Type Management
Real Type Management
0 = Float X10
0 = Float X10
1 = IEE 754
1 = IEE 754
reg32bit
0 to 1
1
-
Enable 32 bits registers
Enable 32 bits registers
0 = IR/HR in 16 bit mode
0 = IR/HR in 16 bit mode
1 = IR/HR in 32 bit mode
1 = IR/HR in 32 bit mode
conifnam
0 to 1
0
-
IP port interface name
IP port interface name
0 = J5/J15
0 = J5/J15
1 = J16
1 = J16
timeout
60 to 600
120
sec
Com. timeout (s)
Com. timeout (s)
idle
0 to 30
10
sec
Keepalive idle delay(s)
Keepalive idle delay(s)
intrvl
0 to 2
1
sec
Keepalive interval(s)
Keepalive interval(s)
probes
0 to 10
10
-
Keepalive probes nb
Keepalive probes number
* Depends on the selected language (French by default).
BACnet Standard Conf. – BACNET
Name
Status
Default
Unit
Displayed text*
Description
bacena
disable/enable
disable
-
BACnet Enable
BACnet Enable
bacunit
no/yes
yes
-
Metric Unit?
Metric Unit?
network
1 to 4000
1600
-
Network
Network
udpport
47808 to 47823
47808
-
UPD Port Number
UPD Port Number
bac_id
1 to 4194302
1600001
-
Device Id Manual
Device Id Manual
auid_opt
disable/enable
disable
Device Id Auto Option
Device Id Auto Option
balmena
disable/enable
enable
-
Alarm reporting
Alarm reporting
mng_occ
no/yes
no
-
BACnet Manage Occupancy
BACnet Manage Occupancy
conifnam
0 to1
0
-
IP port Interface name
IP port Interface name
0 = J5/J15
0 = J5/J15
1 = J16
1 = J16
* Depends on the selected language (French by default).
Modbus RTU Config. Menu – MODBUSRS (continued)
7 - CONNECT TOUCH CONTROL: MENU STRUCTURE
Содержание AQUACIATPOWER CONNECT TOUCH ILD 602R
Страница 1: ...Instruction manual 11 2022 10555 CONNECT TOUCH AQUACIAT POWER I LD 602R 4000R...
Страница 62: ...AQUACIATPOWER EN 62...
Страница 63: ...EN 63 AQUACIATPOWER...