background image

 

 

 EN - 45  

AQUACIAT

POWER

2)  Water flow control based on constant water delta pressure 

(the control continuously acts on the pump speed to ensure 

a constant delta pressure).

3)  Water flow control based on constant delta T on the water 

exchanger.

Fixed speed pumps can be either low or high pressure, whereas 

variable speed pumps are always high pressure pumps.

8.4.2  Configuring pumps

The CONNECT TOUCH can control fixed speed and variable 

speed pumps as well as customer pumps. Note that variable 

speed pumps can be configured as fixed speed pumps. 

Basic pump configuration can be performed via the Configuration 

menu (PUMPCONF – Pump Configuration). Remember that 

only logged-in users may access the menu. The unit must be 

stopped.

IMPORTANT: Please note that the speed of the pump can 

be configured only by service technicians.

To set pumps sequence

1.  Navigate to the Configuration menu (logged-in users only).

2.  Select 

Pump Configuration

 (PUMPCONF).

3.  Set Pumps Sequence [pump_seq].

Pumps Sequence [pump_seq]

0

No pump

1

One pump only

2

Two pumps auto

3

Pump#1 Manual

4

Pump#2 Manual

8.4.3  Setting pumps automatically

If there are two pumps in the system controlled by the CONNECT 

TOUCH control, then the "pump reversing" functionality can be 

used. When the pump reversing option is selected, then the 

control balances the pump run time to match the configured 

pump changeover delay. In case the delay has elapsed, the 

pump reversing function is activated. 

To set pumps automatic rotation delay

1.  Navigate to the Configuration menu (logged-in users only).

2.  Select 

Pump Configuration

 (PUMPCONF).

3.  Set Pump Auto Rotation Delay [pump_del].

Pump Auto Rotation Delay [pump_del]

24 to 3000h

48h

8.4.4  Setting customer pumps

Units with customer pumps are fitted with the flow switch, 

allowing for the water flow control. 

Customer pumps have the following configurations possible:

Pump(s) available

[pump_seq]

Description

No pump

0

No pump

One single speed pump

1

One pump only

Two single speed pumps

2

Two pumps automatic

3

Pump #1 manual

4

Pump #2 manual

8.4.5  Setting pump protections

To mitigate the risk of freezing the water exchanger when the 

outside air temperature is low, the CONNECT TOUCH control 

provides a means to automatically start the pump each day at 

14:00 for 2 seconds when the unit is "Off" (especially useful 

when the unit is stopped for a long time, e.g. during the winter 

season). 

For units fitted with two pumps, the first pump is started 

on even days and the second pump is started on odd days. 

Starting the pump periodically for a few seconds extends the 

lifetime of the pump bearings and the tightness of the pump 

seal. This periodical pump quick start can be selected via the 

Configuration menu.

To set periodical pump quick start

1.  Navigate to the Configuration menu (logged-in users only).

2.  Select 

Pump Configuration

 (PUMPCONF).

3.  Set Pump Sticking Protection [pump_per].

Pump Sticking Protection [pump_per]

No/Yes

Yes

8.4.6  Setting ECO pump mode

When the unit is in Standby mode (heating or cooling demand 

is satisfied), the CONNECT TOUCH control may be configured 

to stop the pump periodically in order to save energy.

This option can be configured only by service technicians.

To verify the Eco Pump configuration

1.  Navigate to the Main menu.

2.  Select 

Miscellaneous Status

 (MSC_STAT).

3.  Verify Eco Pump Mode Active [m_ecopmp].

Eco Pump Mode Active [m_ecopmp]

No/Yes

8.5 

Hydronic kit option

The hydronic kit option allows for continuous monitoring of the 

water flow rate.

The hydronic kit provides the option to measure the following 

parameters:

 

ƒ

Inlet and Outlet water pressure.

 

ƒ

Water exchanger flow rate.

How is the water flow rate measured?

The water flow rate measurement is based on the calculation 

that takes into account the pressure difference between the 

Inlet water pressure and the Outlet water pressure as well as 

the pressure drop curves.

Hydronic kit variable speed pumps

In the case of units fitted with variable speed pumps, 

the CONNECT TOUCH control adjusts the pump speed 

automatically in order to make sure that the water flow rate is 

maintained at the correct level. 

Depending on the selected configuration, the water flow control 

can be based on compressor usage, constant delta pressure or 

constant temperature difference.

8 - STANDARD CONTROL OPERATIONS AND OPTIONS

Содержание AQUACIATPOWER CONNECT TOUCH ILD 602R

Страница 1: ...Instruction manual 11 2022 10555 CONNECT TOUCH AQUACIAT POWER I LD 602R 4000R...

Страница 2: ...umentation 21 7 CONNECT TOUCH CONTROL MENU STRUCTURE 22 7 1 Main menu 22 7 2 Configuration menu CONFIG 33 7 3 Network Parameters menu 38 7 4 System Menu 40 7 5 Alarm Menu 42 8 STANDARD CONTROL OPERATI...

Страница 3: ...ormation provided herein is solely for the purpose of allowing customers to operate and service the equipment and it is not to be reproduced modified or used for any other purpose without the prior co...

Страница 4: ...ce engineers should be allowed to install and service the equipment 1 2 Safety precautions Only personnel qualified in accordance with IEC International Electrotechnical Commission recommendations may...

Страница 5: ...r to maintain the correct refrigerant pressure in each circuit and monitors safety devices that protect the unit against failure and guarantee its optimal functioning 2 3 Operating modes The control m...

Страница 6: ...E mail transmission Occupied Unoccupied mode management Trending Master Slave control Diagnostics Cooling control Free cooling dry cooler mgmt Heating control Boiler heating control Electric heating...

Страница 7: ...es on boards All boards continuously check and indicate the proper operation of their electronic circuits A light emitting diode LED lights on each board when it is operating properly The red LED flas...

Страница 8: ...used instead of the 3 way valve then this sensor is located on the BPHE condenser inlet Free Cooling water temperature sensor FC option The Free Cooling water temperature sensor is located at the outp...

Страница 9: ...AI 10 J9 Allows the user to reset the currently selected setpoint Occupancy override SIOB CIOB EMM DI 01 J1 Used to switch between occupied closed contact and unoccupied mode open contact Demand limi...

Страница 10: ...It is active only when the control is in Remote mode Cooling Heating Stp1 Stp2 Auto Stp1 Stp2 Auto Setpoint selection contact open closed open closed 4 7 3 Volt free demand limit selection contact Up...

Страница 11: ...Proprietary Protocol This wire is required so that all nodes on the bus share a common ground reference connection If a shield is used then the shield cable should be properly terminated and connected...

Страница 12: ...ls such as LEN Proprietary Protocol Modbus RTU It is possible to enable and disable end of line resistors via the System menu see section 7 4 One Ethernet port allows for TCP IP communication BACnet M...

Страница 13: ...nfig Main Menu Run Times DC Free Cooling Status Modes Msc Status Hydraulic Free Cooling Heat Reclaim General Parameters Pressures Temperatures Inputs Pump Status Outputs Setpoint Configuration Configu...

Страница 14: ...Alarms Current Alarms Alarm History Major Alarm History Software Info Hardware Info CPU Load Network EOL Resistor Date Time Configuration Brightness Language Unit System System Menu Home Main Menu Sys...

Страница 15: ...r Alert no action taken on the unit Steady icon Alarm s active on the unit OTHER SCREENS Login screen Parameters screen s Login Confirm advanced access login Save changes Logout Reset the user level a...

Страница 16: ...d to start if the period is occupied Network Network The unit is controlled by network commands and allowed to start if the period is occupied Remote Remote The unit is controlled by external commands...

Страница 17: ...the time of occupancy 6 When the time schedule is set the selected period will be presented in the form of the green band on the timeline 7 Press the Save button to save your changes or the Cancel bu...

Страница 18: ...utton to exit the screen without making modifications NOTE You may also leave the screen by pressing the Back button Security access settings User level security ensures that only authorised users are...

Страница 19: ...y unit parameters The Configuration menu gives access to a number of user modifiable parameters such as pump configuration schedule menu etc The Configuration menu is password protected To access the...

Страница 20: ...the Save button in the lower left part of the screen IMPORTANT Please make sure that dates are not out of range not existing dates otherwise an error message may be displayed Press or to navigate acro...

Страница 21: ...t parameters or unit configuration can be performed via the web browser interface Make sure that your network is protected from malicious attacks and any other security threats Do not provide open acc...

Страница 22: ...at Reclaim Heat Reclaim RECLAIM Hydraulic Free Cooling Hydraulic Free Cooling HYD_FC Trendings Trendings TRENDING Setpoint Configuration Setpoints configuration SETPOINT Configuration Menu Configurati...

Страница 23: ...e unit is in Network mode the minimum value will be used compared to the status of the external limit switch contact and the demand limit switch setpoint LAG_LIM 0 to 100 0 Lag Capacity Limit Value La...

Страница 24: ...mote Setpoint Switch Remote setpoint selection switch LIM_SW1 open close open Limit Switch 1 Demand limit switch 1 LIM_SW2 open close open Limit Switch 2 Demand limit switch 2 Energy Management Module...

Страница 25: ...EMEA CP_B1 off on off Compressor B1 Compressor B1 command CP_B2 off on off Compressor B2 Compressor B2 command CP_B3 off on off Compressor B3 Compressor B3 command CP_B4 off on off Compressor B4 Compr...

Страница 26: ...ta pressure setpoint delta_p kPa PSI Current Water Delta P Current water delta pressure MxDeltaP kPa PSI Cur Max Water Delta P Maximum current water delta pressure VPMP_CMD 0 to 100 0 Variable Speed P...

Страница 27: ...uction circuit A m_lowscb no yes no Low Suction Circuit B Low suction circuit B m_hidgta no yes no High DGT Circuit A High DGT circuit A m_hidgtb no yes no High DGT Circuit B High DGT circuit B m_hipr...

Страница 28: ...rs Depends on the selected language French by default Msc Status Menu MSC_STAT Name Status Default Unit Displayed text Description m_ecopmp no yes no Eco Pump Mode Active Eco pump mode status When thi...

Страница 29: ...ing override fcCapA FC Capacity A Free Cooling capacity circuit A modeCirA 0 to 3 0 Mode of Circuit A Free Cooling mode circuit A 0 Mechanical Cooling MC only 1 Mixed Cooling MC and FC at the same tim...

Страница 30: ...re Depends on the selected language French by default Quick Test 1 Menu QCK_TST1 Name Status Unit Displayed text Description Unit must be in Loff To enable the Quick Test functionality the unit must b...

Страница 31: ...aim 3Way Valve cmd 3 way valve command QHR_HTR off on Reclaim BPHE Heater Heat Reclaim BPHE heater HYDRAULIC FREE COOLING Hydraulic Free Cooling Q_FC_EV close open FC Evaporator Valve Free Cooling eva...

Страница 32: ...egrated COP Integrated COP reset_en no yes Reset of Energy Counter Parameter set to yes allows to reset the energies displayed in this table reset_da Last Reset Date Last Reset Date reset_ti Last Rese...

Страница 33: ...on USERCONF Schedule Menu Schedule menu SCHEDULE Holiday Menu Holiday menu HOLIDAY Date Time Configuration Date time configuration DATETIME Network Parameters Network parameters see section 7 3 NETWOR...

Страница 34: ...Unit Displayed text Description pump_seq 0 to 4 1 Pumps Sequence Pumps sequence 0 No Pump 0 No pump 1 One Pump Only 1 One pump only units with one pump 2 Two Pumps Auto 2 Two pumps automatic control 3...

Страница 35: ...eset value oat_hrfu 10 to 51 7 14 to 125 10 0 14 0 C F OAT Full Reset Value OAT max reset value dt_hr_no 0 to 13 9 0 to 25 0 0 C F Delta T No Reset Value Delta T no reset value dt_hr_fu 0 to 13 9 0 to...

Страница 36: ...Time UTC Location Time zone YYYY MM DD HH MM SS Date Time Current date and time must be set manually no yes Today is a Holiday Information about holidays read only Please note that holidays are set i...

Страница 37: ...ID gain int 3w valve 3 way valve pump PID integral gain kd_HR3wv 20 to 20 0 4 PID gain deri 3w valve 3 way valve pump PID derivative gain kp_HRFan 20 to 20 5 PID gain prop fan Fan PID proportional gai...

Страница 38: ...P2 0 to 255 0 SMTP IP Addr Part 2 SMTP IP address part 2 smtpP3 0 to 255 0 SMTP IP Addr Part 3 SMTP IP address part 3 smtpP4 0 to 255 0 SMTP IP Addr Part 4 SMTP IP address part 4 accP1 Account Email P...

Страница 39: ...mode 1 IR HR in 32 bit mode 1 IR HR in 32 bit mode conifnam 0 to 1 0 IP port interface name IP port interface name 0 J5 J15 0 J5 J15 1 J16 1 J16 timeout 60 to 600 120 sec Com timeout s Com timeout s i...

Страница 40: ...of Line Res J7 End of line resistor J7 disable enable disable End of Line Resistor J8 End of line resistor J8 disable enable disable End of Line Resistor J10 End of line resistor J10 Modbus Depends on...

Страница 41: ...tch Chinese Italian Portuguese and Custom1 Custom language The control system allows users to add new languages to the control To learn more about language customization please contact your local Serv...

Страница 42: ...m 2 index Alarm code see section 9 3 alarm_3 Current Alarm 3 index Alarm code see section 9 3 alarm_4 Current Alarm 4 index Alarm code see section 9 3 alarm_5 Current Alarm 5 index Alarm code see sect...

Страница 43: ...topped The pump is running with no mechanical cooling or heating unless configured otherwise The pump may be stopped depending on pumps configuration PUMPCONF Pump Configuration Heating Cooling Standb...

Страница 44: ...ing AQUACIATPOWER LD chillers may be fitted with a boiler that allows the unit to run in heating mode if required The boiler is active only when the unit is in Heating mode AQUACIATPOWER ILD heat pump...

Страница 45: ...ump protections To mitigate the risk of freezing the water exchanger when the outside air temperature is low the CONNECT TOUCH control provides a means to automatically start the pump each day at 14 0...

Страница 46: ...ing auto enable closed unoccupied Cooling setpoint 2 heating sp 1 Heating setpoint 1 heating sp 2 Heating setpoint 2 heating auto occupied Heating setpoint 1 heating auto unoccupied Heating setpoint 2...

Страница 47: ...he unit s maximum allowable capacity How to understand capacity limitation Capacity limitation is used to determine the maximum unit s capacity Capacity limitation is expressed in percentage where a l...

Страница 48: ...the lead circuit The selected circuit takes priority over another circuit Automatic lead lag circuit determination The control system determines the lead circuit to equalise the operating time of eac...

Страница 49: ...ed when the outside air temperature OAT Free Cooling is above the water loop temperature and the service configured threshold parameter However if it turns out that the cooling power of the dry cooler...

Страница 50: ...algorithm will ensure minimum water flow on heat exchangers and prevent water boiling It is therefore necessary to permanently guarantee the use or evacuation of the heat transferred to the hydraulic...

Страница 51: ...ree defrost is most efficient when current heating demand is below the heating capacity delivered by the unit and the outside air temperature is above 1 C IMPORTANT In the case of a large amount of fr...

Страница 52: ...thin 7 days since the first compressor start the alarm will be reset automatically and software options will be blocked The Replacement mode ends when the Software Activation Key is installed or the p...

Страница 53: ...nterface in the Reset Alarms menu The Reset alarms menu displays up to 5 alarm codes which are currently active on the unit Alarms can be reset without stopping the machine Only logged in users can re...

Страница 54: ...tor reading returns to normal Dry cooler free cooling is disabled Defective thermistor 17 15047 DC Free Cooling Leaving Water Thermistor Failure As above No action alert As above 18 15048 DC Free Cool...

Страница 55: ...ual Circuit B shuts down As above 45 10011 Circuit A Low Superheat Manual Circuit A shuts down As above 46 10012 Circuit B Low Superheat Manual Circuit B shuts down As above 47 10014 Customer Interloc...

Страница 56: ...lve Failure Automatic No action alert Valve stuck or connection failure 75 10222 FC Evaporator Valve Failure Automatic No action alert Valve stuck or connection failure 76 11201 Water Loop Pressure To...

Страница 57: ...atic in the case of cooler flow switch failure high pressure trip or cooler freeze alarm or Manual power cycle required Unit shuts down but the evaporator pump continues to operate Welded contactor of...

Страница 58: ...ct CIAT service representative to activate options Automatic if Software Activation Key is installed Automatic if Software Activation Key is not provided within 7 days since the first compressor start...

Страница 59: ...inverter OL1 As above 14 Over LOAD in motor OL2 As above 16 Overheat trip OH As above 17 Emergency stop E As above 18 EEPROM fault 1 writing operation EEP1 As above 19 EEPROM fault 2 reading operation...

Страница 60: ...que As above 10 Reserved As above 11 Cumulative operation hours reached As above 12 Reserved As above 13 Reserved As above 14 Main circuit undervoltage alarm the same as MS relay status As above 15 At...

Страница 61: ...age can occur to your equipment Your local Service Agency provides a wide range of service contracts which embrace the assistance of highly qualified HVAC engineering professionals ready to help if ne...

Страница 62: ...AQUACIATPOWER EN 62...

Страница 63: ...EN 63 AQUACIATPOWER...

Страница 64: ...Manufacturer Carrier SCS Montluel France Printed in the European Union Manufacturer reserves the right to change any product specifications without notice...

Отзывы: