7 - CONNECT TOUCH CONTROL: MENU STRUCTURE
General Configuration Menu – GENCONF
Name
Status
Default
Unit
Displayed text*
Description
prio_cir
0 to 2
0
-
Cir Priority Sequence
Circuit priority
0=Auto, 1=A Prio
0 = Automatic circuit selection
1 = Circuit A priority
2=B Prio
2 = Circuit B priority
seq_typ
no/yes
no
-
Staged Loading Sequence
Staged loading sequence
ramp_sel
no/yes
no
-
Ramp Loading Select
Ramp loading selection
lim_sel
0 to 2
0
-
Demand Limit Type Select
Demand limit selection
0 = None
0 = None
1 = Switch Control
1 = Switch control
2 = 4-20mA Control
2 = 4-20 mA control
off_on_d
1 to 15
1
min
Unit Off to On Delay
Unit Off to On delay
heat_th
-17.0 to 0
1.4 to 32.0
-17.0
1.4
°C
°F
Heating OAT Threshold
Heating OAT threshold
nh_start
-
-
-
Night Mode Start Hour
Night mode start hour
nh_end
-
-
-
Night Mode End Hour
Night mode end hour
nh_limit
0 to 100
100
%
Night Capacity Limit
Night capacity limit
ice_cnfg
no/yes
no
-
Ice Mode Enable
Ice mode enabled (Energy Management Module)
both_sel
no/yes
no
-
Both Command Sel (HSM)
Both command selection (HSM)
auto_sel
no/yes
no
-
Auto Changeover Select
Automatic changeover selection
ewt_opt
no/yes
no
-
Entering Fluid Control
Entering fluid control option (if selected, the system controls unit capacity
based on the entering fluid temperature; otherwise the control is based on
the leaving fluid temperature)
* Depends on the selected language (French by default).
Pump Configuration Menu – PUMPCONF
Name
Status
Default
Unit
Displayed text*
Description
pump_seq
0 to 4
1
-
Pumps Sequence
Pumps sequence
0 = No Pump
0 = No pump
1 = One Pump Only
1 = One pump only (units with one pump)
2 = Two Pumps Auto
2 = Two pumps automatic control
3 = Pump#1 Manual
3 = Pump 1 selected (units with two pumps)
4 = Pump#2 Manual
4 = Pump 2 selected (units with two pumps)
pump_del
24 to 3000
48
hour
Pump Auto Rotation Delay
Pump automatic rotation delay
pump_per
no/yes
no
-
Pump Sticking Protection
Pump sticking protection
pump_sby
no/yes
no
-
Stop Pump During Standby
Pump stops when the unit is in standby
pump_loc
no/yes
yes
-
Flow Checked If Pump Off
Flow checked if pump is off
flow_ctl
1 to 3
1
-
Flow Control Method
Flow control method
1 = Constant Speed
1 = flow control is based on fixed pump speed
2 = Delta Temperature
2 = flow control is based on delta temperature
3 = Delta Pressure
3 = flow control is based on delta pressure
dt_stp
3.0 to 10.0
5.4 to 18.0
5.0
9.0
^C
^F
Flow Delta T Setpoint
Delta temperature setpoint
dp_stp
50.0 to 300.0
7.25 to 43.51
200.0
29.0
kPa
PSI
Flow Delta P Setpoint
Delta pressure setpoint
wtr_zval
-100.0 to 10.0
-14.5 to 1.45
-100.0
-14.5
kPa
PSI
Pressure Zero Value
Pressure zero value
pump_min
30 to 100
60
%
Pump Minimum Speed
Minimum pump speed
pump_sav
30 to 100
60
%
Pump Min Speed Cap=0%
Minimum pump speed when unit capacity is 0%
pump_max
30 to 100
100
%
Pump Maximum Speed
Maximum pump speed
MinWpThr
70.0 to 1000.05
10.15 to 145.04
100.0
14.5
kPa
PSIG
Min Water Press Thres
Minimum water pressure threshold
WtPmpMxP
96.5 to 551.5
14.0 to 80.0
500.0
72.52
kPa
PSIG
Water Pump Max Delta P
Maximum water pump delta pressure
* Depends on the selected language (French by default).