7 - CONNECT TOUCH CONTROL: MENU STRUCTURE
Energy Monitoring – ENERGY
Name
Status
Unit
Displayed text*
Description
COOLING MODE
Cooling mode
cPwrOut
-
kW
Cooling Power Output
Cooling Power Output
cPwrIn
-
kW
Electical Power Input
Electrical power input of Compressors and fans. Pumps excluded.
If EC fans selected : value is estimated.
eer
-
-
Energy Efficiency (EER)
Energy Efficiency (EER)
cEnergOu
-
kWh
Cooling Energy Output
Cooling Energy Output
cEnergIn
-
kWh
Electrical Energy Input
Electrical Energy Input
energEer
-
-
Integrated EER
Integrated EER
HEATING MODE
Heating mode
hPwrOut
-
kW
Heating Power Output
Heating Power Output
hPwrIn
-
kW
Electical Power Input
Electrical power input of Compressors and fans. Pumps excluded.
If EC fans selected : value is estimated.
cop
-
-
Coef. Of Perf. (COP)
Coefficient Of Perf. (COP)
hEnergOu
-
kWh
Heating Energy Output
Heating Energy Output
hEnergIn
-
kWh
Electrical Energy Input
Electrical Energy Input
energCop
-
-
Integrated COP
Integrated COP
reset_en
no/yes
-
Reset of Energy Counter
Parameter set to "yes" allows to reset the energies displayed in this table
reset_da
-
-
Last Reset Date
Last Reset Date
reset_ti
-
-
Last Reset Time
Last Reset Time
* Depends on the selected language (French by default).
** The information in this table is indicative (based on estimates) and cannot be used as a real energy meter.
The powers and energies take into account only the power of compressors and fans.
Software Options – OPT_STA
Name
Status
Unit
Displayed text*
Description
opt6
no/yes
-
OPT6: Low Brine
Parameter set to “yes” means that Low brine option which requires the Software Key is activated
opt149
no/yes
-
OPT149: BACnet
Parameter set to “yes” means that BACnet option which requires the Software Key is activated
opt149B
no/yes
-
OPT149B: Modbus
Parameter set to “yes” means that Modbus option is activated
opt119C
no/yes
-
OPT119C:Cool Floor Optim Parameter set to “yes” means that Cooling Floor Optimized option which requires the Software Key
is activated (specific circuit capacity limits are applied to heat pumps in Cooling mode)
* Depends on the selected language (French by default).