7 - CONNECT TOUCH CONTROL: MENU STRUCTURE
Quick Test #1 Menu – QCK_TST1 (continued)
Name
Status
Unit
Displayed text*
Description
Q_EXV_A
0 to 100
%
EXV Position Circuit A
EXV position, circuit A
100% = EXV fully open
Q_HD_HTA
off/on
-
Compressor Head Heater A
Compressor head heater test, circuit A
Q_RV_B
off/on
-
Reverse Vlv Output Cir B
Reverse valve test, circuit B
Q_FAN_B1
off/on
-
Fan B1 Output
Fan stage B1, circuit B
Q_FAN_B2
off/on
-
Fan B2 Output
Fan stage B2, circuit B
Q_FAN_B3
off/on
-
Fan B3 Output
Fan stage B3, circuit B
Q_FAN_B4
off/on
-
Fan B4 Output
Fan stage B4, circuit B
Q_FAN_B5
off/on
-
Fan B5 Output
Fan stage B5, circuit B
Q_FAN_B6
off/on
-
Fan B6 Output
Fan stage B6, circuit B
Q_VFAN_B
0 to 100
%
Variable Fan Speed B
Variable speed fan test, circuit B
Q_EXV_B
0 to 100
%
EXV Position Circuit B
EXV position, circuit B
100% = EXV fully open
Q_HD_HTB
off/on
-
Compressor Head Heater B
Compressor head heater test, circuit B
HP_TEST
0 to 4
-
High Pressure Test
High Pressure test: When activated, the unit will run until the High Pressure
Safety Switch is open (0 = No test)
1: HP test on cir A
1 = High Pressure test, circuit A
2: HP test on cir B
2 = High Pressure test, circuit B
3: N/A
3 =
Not applicable
4: HP test on both cir
4 = High Pressure test on both circuits
HEAT RECLAIM
Heat Reclaim test
QHR_PMP
off/on
-
Reclaim pump command
Heat Reclaim pump command
QHR_3WV
0 to 100
%
Reclaim 3Way Valve cmd
3-way valve command
QHR_HTR
off/on
-
Reclaim BPHE Heater
Heat Reclaim BPHE heater
HYDRAULIC FREE COOLING
Hydraulic Free Cooling
Q_FC_EV
close/open
-
FC Evaporator Valve
Free Cooling evaporator valve test
Q_FC_CV
close/open
-
FC Coil Valve
Free Cooling coil valve test
Q_FC_PMP
off/on
-
FC Coil Pump
Free Cooling coil pump test
* Depends on the selected language (French by default).
IMPORTANT: To enable the Quick Test functionality, the unit
must be stopped (Local off mode).
Trendings – TRENDING
Name
Status
Unit
Displayed text*
Description**
GENUNIT_CAPA_T
0 to 100
%
Cir A Total Capacity
Total capacity, circuit A
GENUNIT_CAPB_T
0 to 100
%
Cir B Total Capacity
Total capacity, circuit B
GENUNIT_CTRL_PNT
-
°C / °F
Control Point
Control point
TEMP_OAT
-
°C / °F
Outdoor Air Temp
Outdoor air temperature
TEMP_EWT
-
°C / °F
Cooler Entering Fluid
Evaporator entering water temperature
TEMP_LWT
-
°C / °F
Cooler Leaving Fluid
Evaporator leaving water temperature
TEMP_SCT_A
-
°C / °F
Saturated Cond Tmp cir A
Saturated condensing temperature, circuit A
TEMP_SCT_B
-
°C / °F
Saturated Cond Tmp cir B
Saturated condensing temperature, circuit B
TEMP_SST_A
-
°C / °F
Saturated Suction Temp A
Saturated suction temperature, circuit A
TEMP_SST_B
-
°C / °F
Saturated Suction Temp B
Saturated suction temperature, circuit B
TEMP_HR_CtrWat
-
°C / °F
Reclaim controlled water
Heat Reclaim control water temperature
TEMP_HR_LWT
-
°C / °F
HR Leaving Fluid temp
Heat Reclaim leaving fluid temperature
* Depends on the selected language (French by default).
** The list of trending points cannot be modified. Trending points can only be enabled or disabled.