EN - 9
AQUACIAT
POWER
4 - HARDWARE
4.7
Terminal block connections
Connections available at the user terminal block may vary
depending on the selected options. The following table summarizes
connections at the user terminal block.
IMPORTANT: Some contacts can be accessed only when
the unit operates in Remote mode.
Terminal block connections
Description
Board
Input/Output Connector Remarks
On/Off switch
SIOB/CIOB, circuit A
DI-01
J1
Used for the unit On/Off control (Remote mode)
Heat/Cool switch
SIOB/CIOB, circuit A
DI-04
J1
Used to switch between cooling and heating when the unit is in Remote
mode (Heat pumps only)
Second setpoint switch
SIOB/CIOB, circuit A
DI-02
J1
Used to switch between setpoints
Demand limit switch 1
SIOB/CIOB, circuit A
DI-03
J1
Used to control demand limit
Alarm relay
SIOB/CIOB, circuit A
DO-05
J23
Indicates alarms
Running relay
SIOB/CIOB, circuit A
DO-06
J22
Used to signal a running status (at least one compressor started)
Desuperheater demand
SIOB/CIOB, circuit B
DI-04
J1
Heat recovery is allowed (option 49)
Lock switch
SIOB/CIOB, circuit B
DI-02
J1
Used for the customer safety loops
Customer pump 1
SIOB/CIOB, circuit B
DO-05
J23
The control can regulate one or two evaporator pumps and automatically
change over between the two pumps
Customer pump 2
SIOB/CIOB, circuit B
DO-06
J22
The control can regulate one or two evaporator pumps and automatically
change over between the two pumps
Optional
Setpoint reset control
SIOB/CIOB, circuit A
AI-10
J9
Allows the user to reset the currently selected setpoint
Occupancy override
SIOB/CIOB, EMM
DI-01
J1
Used to switch between occupied (closed contact) and unoccupied mode
(open contact)
Demand limit switch 2
SIOB/CIOB, EMM
DI-02
J1
Used to control demand limit
Customer interlock
SIOB/CIOB, EMM
DI-03
J1
Used for the customer safety loops
Ice done contact
SIOB/CIOB, EMM
DI-04
J1
Used to control the setpoint for ice storage in unoccupied mode
Capacity limit control
SIOB/CIOB, EMM
AI-10
J9
Used for capacity limitation
Chiller partially shutdown
SIOB/CIOB, EMM
DO-05
J23
Indicates the shutdown of one of the circuits
Chiller totally shutdown
SIOB/CIOB, EMM
DO-06
J22
Indicates the unit shutdown
Chiller capacity running output
(0 to 10 V)
SIOB/CIOB, EMM
AO-01
J10
Reports the capacity percentage of the unit
Desuperheater customer pump
SIOB/CIOB, EMM
DO-01
J2
The control can regulate a customer pump for heat recovery.
The connection has to be done between the pin DO-01 of connector J2
and the pin IN-01 of connector J4
IN-01
J4
Heat Reclaim BPHE heater
AUX1, HR
DO-01
J2
Used to activate the optional HR condenser heater
Heat Reclaim pump command
AUX1, HR
DO-02
J2
Used to energize the HR pump
Heat Reclaim controlled water
temperature
AUX1, HR
AI-01
J6
Used to monitor the controlled water temperature (on the customer side)
Heat Reclaim leaving fluid
temperature
AUX1, HR
AI-02
J6
Used to monitor the HR condenser leaving water temperature
Heat Reclaim flow switch
AUX1, HR
AI-03
J7
Used to detect if the water flows in the BPHE condenser
Remote Heat Reclaim switch
AUX1, HR
AI-04
J8
Used to enable the Heat Reclaim mode (Remote mode)
closed = Heat Reclaim is enabled