9 - DIAGNOSTICS
JBus
code Code Alarm description
Reset type
Action taken
Possible cause
Service and factory
95 70nn
Illegal Factory Configuration Number #1 to nn
List of illegal configurations:
01: Unit size unknown (FACTORY_unitsize).
02: Fan type unavailable for the configured unit
size.
03: Pump configuration failure. Pump doesn't
exist for the configured unit size.
04: This configuration is not available for the unit
– unavailable type of refrigerant selected
(FACTORY_refrig). Please note that the correct
configuration of FACTORY_refrig parameter
depends on the software version:
• FACTORY_refrig = 1 (R32) for software version
3.0 or lower
• FACTORY_refrig = 3 (R32) for software version
4.0 or higher
Automatic,
if configuration is
corrected
Unit cannot be started
Incorrect unit
configuration
96 8000
No Factory Configuration
Automatic,
if configuration is
provided
Unit cannot be started
No factory configuration
Compressor failure
97 1199
Compressor A1 Failure
Manual
Compressor A1 shuts down Compressor temperature
too high, high pressure
switch opened,
compressor not started
98 1299
Compressor A2 Failure
Manual
Compressor A2 shuts down As above
99 1399
Compressor A3 Failure
Manual
Compressor A3 shuts down As above
100 1499
Compressor A4 Failure
Manual
Compressor A4 shuts down As above
101 2199
Compressor B1 Failure
Manual
Compressor B1 shuts down As above
102 2299
Compressor B2 Failure
Manual
Compressor B2 shuts down As above
103 2399
Compressor B3 Failure
Manual
Compressor B3 shuts down As above
104 2499
Compressor B4 Failure
Manual
Compressor B4 shuts down As above
105 6001
Circuit A Welded Contactor Failure
Automatic in the case
of cooler flow switch
failure, high pressure
trip or cooler freeze
alarm or Manual
(power cycle required)
Unit shuts down, but the
evaporator pump continues
to operate
Welded contactor of a
compressor
106 6002
Circuit B Welded Contactor Failure
As above
As above
As above
Software failure
107 55001 Database Module Failure
Manual
Unit shuts down
Software problem.
Contact Service
technicians
108 56001 Lenscan Module Failure
Manual
Unit shuts down
Software problem.
Contact Service
technicians
Service and factory
109 90nn
Master Chiller Configuration Error Number #1 to
nn
Automatic, if master/
slave configuration
returns to normal or
the unit returns to the
standalone mode
Master/slave operation is
disabled and the unit
returns to the stand-alone
mode
Configuration failure
Service maintenance warning
110 13nnn Service Maintenance Alert Number # nn
004: Maintenance Servicing Required
Manual
Depending on the severity
of the alarm, the unit may
continue to operate or the
unit shuts down
Servicing action required.
Contact Service
technicians
111 13005 Fgas check needed, call your maintenance
company
Manual
As above
As above
VFD drive failure
113 170nn Circuit A VFD Fan Drive 1 Failure
Automatic or
Manual (motor
overload)
Units with one drive on the
circuit: Circuit A shuts down
Units with two drives on the
circuit: Circuit A continues to
run as long as one of two
drives is operating
Speed controller fault
114 180nn Circuit A VFD Fan Drive 2 Failure
As above
As above
As above
115 190nn Circuit B VFD Fan Drive 1 Failure
As above
Units with one drive on the
circuit: Circuit B shuts down
Units with two drives on the
circuit: Circuit B continues
to run as long as one of two
drives is operating
As above
116 200nn Circuit B VFD Fan Drive 2 Failure
As above
As above
As above