7 - CONNECT TOUCH CONTROL: MENU STRUCTURE
Heat Reclaim Menu – RECLAIM
Name
Status
Default
Unit
Displayed text*
Description
1: HR water temp control
1 = valve/pump control in normal HR_LWT mode
actiMode
0 to 1
1
-
HR active mode (3WV/Fan) Heat Reclaim (3-way valve / fans)
0 : 3-way valve mode
0 = 3-way valve is controlling the HR water temperature
(fans are running to improve unit efficiency)
1 : Fan mode
1 = 3-way valve is fully opened
(fans are controlling the HR water temperature)
HR_pump
off/on
off
-
Reclaim pump command
Heat Reclaim pump command (the on/off pump on the customer side when a
3-way valve is mounted)
HRheater
off/on
off
-
Reclaim BPHE Heater
BPHE heater (optional): Please note that the heater is available only for HR
units running on water. The controller monitors the water temperature to
activate the optional heater when necessary.
* Depends on the selected language (French by default).
Hydraulic Free Cooling Menu – HYD_FC
Name
Status
Default
Unit
Displayed text*
Description
FC_DSBLE
no/yes
no
-
Free Cooling Disable?
Enable/disable Free Cooling (FC):
yes = Free Cooling disabled
no = Free Cooling enabled
fcCapT
-
-
%
Total FC Capacity
Total Free Cooling capacity (circuit A + circuit B)
wLoopPst
Mecha Cooling /
Mixed/Free
Cooling
-
-
Water Loop Position
Water loop position:
"Mecha Cooling" = when the loop is in normal position (mechanical cooling)
"Mixed/Free Cooling" = when the loop is in Mixed/Free Cooling position (the
water is passing through FC coils)
fc_ovr
-
-
-
FC Override
Free Cooling override
fcCapA
-
-
%
FC Capacity A
Free Cooling capacity, circuit A
modeCirA
0 to 3
0
-
Mode of Circuit A
Free Cooling mode, circuit A:
0 = Mechanical Cooling (MC) only
1 = Mixed Cooling (MC and FC at the same time)
2 = Controlled Free Cooling capacity (fan speed control based on water
temperature)
3 = Full power Free cooling state (fan at maximum speed)
mcCurPwA
-
-
kW
MC Current Power A
Mechanical cooling current power, circuit A
fcCurPwA
-
-
kW
FC Current Power A
Free Cooling current power, circuit A
fcMaxPwA
-
-
kW
FC Max Power A
Free Cooling maximum power, circuit A
fcCapB
-
-
%
FC Capacity B
Free Cooling capacity, circuit B
modeCirB
0 to 3
0
-
Mode of circuit B
Free Cooling mode, circuit B:
0 = Mechanical Cooling (MC) only
1 = Mixed Cooling (MC and FC at the same time)
2 = Controlled Free Cooling capacity (fan speed control based on water
temperature)
3 = Full power Free cooling state (fan at maximum speed)
mcCurPwB
-
-
kW
MC Current Power B
Mechanical cooling current power, circuit B
fcCurPwB
-
-
kW
FC Current Power B
Free Cooling current power, circuit B
fcMaxPwB
-
-
kW
FC Max Power B
Free Cooling maximum power, circuit B
fc_ev_rq
close/open
open
-
FC Evap Valve Request
Free Cooling evaporator valve request
fc_cv_rq
close/open
close
-
FC Coil Valve Request
Free Cooling coil valve request
fc_ev_st
-
-
-
FC Evap Valve Status
Free Cooling evaporator valve status
fc_cv_st
-
-
-
FC Coil Valve Status
Free Cooling coil valve status
Glycol Free Option
Free Cooling with the glycol-free module (option 305C/D) **
fc_pump
off/on
off
-
FC Coil Pump Cmd
Free Cooling coil pump command **
PMP_CAL
no/yes
no
-
Pump Pres. Calibration?
Pump pressure calibration? **
* Depends on the selected language (French by default).
** This option is currently not available.