59
Bit 0 = Supply air
motor alarm
Bit 1 = Return air
motor alarm
Bit 2 = Not used
Bit 3 = Supply air filter
CF1 dirty alarm
Bit 4 = Supply air filter
CF1 blocked alarm
Bit 5 = Not used
Bit 6 = Return air filter
CF1 dirty alarm
Bit 7 = Return air filter
CF1 blocked alarm
Bit 8 = Additional filter
CF2 dirty alarm
Bit 9 = Not used
Bit 10 = Not used
Bit 11 = Not used
Bit 12 = Not used
Bit 13 = Fire alarm
Bit 14 = Antifreeze
protection alarm
Bit 15 = Electric heater
safety thermostat
alarm
Alarm 2 value:
Bit 0 = Low supply air
temperature alarm
Bit 1 = High supply air
temperature alarm
Bit 2 = Low ambient or
return air temperature
alarm
Bit 3 = High ambient
or return air
temperature alarm
Bit 4 = Humidifier
alarm
Bit 5 = Heat recovery
unit fouled alarm
Bit 6 = pLAN alarm
Bit 7 = Timer lithium
battery alarm
Bit 8 = Duct pressure
alarm
Bit 9 = Not used
Bit 10 = Not used
Bit 11 = Not used
Bit 12 = Not used
Alarme2
DPT_Value_2_Ucount
7.001
OUT
28
REG
Heating requirement
supplied by unit
Chaud
DPT_Value_2_Ucount
7.001
OUT
1281
REG
Cooling requirement
supplied by unit
Froid
DPT_Value_2_Ucount
7.001
OUT
1282
REG
Unit On/Off command
via CMS
OnoffGTC
DPT_Switch
1.001
IN
280
COIL
Unit On/Off command
return via CMS
OnoffGTC
DPT_Switch
1.001
OUT
280
COIL
Reset of alarms not
present command
ResetAlarmes
DPT_Switch
1.001
IN
281
COIL
Reset of alarms not
present command
return
ResetAlarmes
DPT_Switch
1.001
OUT
281
COIL
Electric heater load
shedding
Delestage
DPT_Switch
1.001
IN
282
COIL
Electric heater load
shedding return
Delestage
DPT_Switch
1.001
OUT
282
COIL
Temperature-
dependent machine
actuation in Eco /
Comfort mode
ConfortEcoTemp
DPT_Switch
1.001
IN
283
COIL
Temperature-
dependent machine
actuation return in
Eco / Comfort mode
ConfortEcoTemp
DPT_Switch
1.001
OUT
283
COIL
Flow rate-dependent
ConfortEcoDebit
DPT_Switch
1.001
IN
284
COIL