51
5.3.4.4
Alarms
Register
hex. no.
Register
decimal
no.
Description
Format
Type
Dampers accessible in read-only mode (functions 3 or 4)
0x514
1300
Level 0 fault (critical fault)
Boolean
0 or 1
0x515
1301
Level 10 fault (Non-critical fault)
Boolean
0 or 1
0x516
1302
Supply air motor alarm
Boolean
0 or 1
0x518
1304
Filter 1 dirty alarm
Boolean
0 or 1
0x51C
1308
Fire alarm
Boolean
0 or 1
0x51D
1309
Antifreeze alarm
Boolean
0 or 1
0x51E
1310
Electric heater overheating alarm
Boolean
0 or 1
0x51F
1311
Supply air temperature too high alarm
Boolean
0 or 1
0x520
1312
Supply air temperature too low alarm
Boolean
0 or 1
0x521
1313
Room or return air temperature too high alarm
Boolean
0 or 1
0x522
1314
Room or return air temperature too low alarm
Boolean
0 or 1
0x523
1315
Return air motor alarm
Boolean
0 or 1
0x524
1316
Filter 1 blocked alarm
Boolean
0 or 1
0x526
1318
Filter 2 dirty alarm
Boolean
0 or 1
0x527
1319
Filter 2 blocked alarm
Boolean
0 or 1
0x528
1320
Filter 3 dirty alarm
Boolean
0 or 1
0x52B
1323
Heat recovery unit alarm in frosting phase
Boolean
0 or 1
0x52C
1324
Timer battery replacement alarm
Boolean
0 or 1
0x52E
1326
Duct pressure alarm
Boolean
0 or 1
0x530
1328
Humidifier alarm
Boolean
0 or 1
0x531
1329
Ambient or return air humidity too high alarm
Boolean
0 or 1
0x532
1330
Ambient or return air humidity too low alarm
Boolean
0 or 1
0x541
1345
Heat recovery unit fouled alarm
Boolean
0 or 1
Содержание AirCompact Control