"Energy optimisation" mode:
Deadband:
Heating:
Cooling:
Return T°
Ambient T°
Heating
authorised
Heating
setpoint
Comfort: 23°C
Eco: 18°C
Cooling authorised
Deadband
Cooling
setpoint
Comfort: 25°C
Eco: 27°C
Low
threshold
alarm
Setpoint - 5°C
High
threshold
alarm
Se 5°C
°C
Supply air
temp.
Cooling requirement (%)
0
100
50
band
Setpoint
Cooling Air supply
Comfort: 16°C
Eco: 18°C
neutral
Low
threshold
alarm
High
threshold
alarm
Setpoint
Cooling supply air
– 5°C
Comfort: 13°C
Eco: 11°C
Setpoint
Heating supply air
+ 5°C
Comfort: 31°C
Eco: 29°C
neutral
°C
Supply air
temp.Supply a
Setpoint
Heating Air supply
Comfort: 26°C
Eco: 24°CSetpoint
Heating Air supply
0
100
50
band
Heating requirement (%)
Setpoint
Cooling supply air
– 5°C
Comfort: 13°C
Eco: 11°CSetpoint
Cooling Air supply
Low
threshold
alarm
High
threshold
alarm
Setpoint
Heating supply air
+ 5°C
Comfort: 31°C
Eco: 29°C
neutral
°C
temp.
Comfort: 24°C
Eco: 26°C
Cooling requirement (%)
0
100
50
band
Heating requirement (%)
band
Comfort: 18°C
Eco: 16°C
neutral
Low
threshold
alarm
High
threshold
alarm
Setpoint
Cooling supply air
– 5°C
Comfort: 13°C
Eco: 11°C
Setpoint
Heating supply air
+ 5°C
Comfort: 31°C
Eco: 29°C