28
Configuration c6
Level 3 access
Supply air fan
K = -----
Return air fan
K = -----
Supply air fan
: K coefficient values for the Supply air fan
Return air fan
: K coefficient values for the Return air fan
2.4
Adjustment parameters menu
lg
Level 1 access
Language ------------
Controller language selection (French)
t0
Level 1 access
Setting
of the clock
Time -- :--
Clock time correction value
Date --/--/--
Clock date correction value
Supply air p1
Level 2 access
Cooling DB 00.0
Deadband value for Supply air temperature control in cooling mode
CLG band 0005.0
Proportional band for Supply air temperature control in cooling mode
T I 0150s T D 0000s
Integral time and derivative time for Supply air temperature control in cooling mode
Heating DB 00.0
Deadband value for Supply air temperature control in heating mode
HTG band 0005.0
Proportional band for Supply air temperature control in heating mode
T I 0150s T D 0000s
Integral time and derivative time for Supply air temperature control in heating mode
Return air p2
Level 2 access
Differential
Value for the Return or Ambient air temperature control differentials
Cooling Heating
In cooling mode
In heating mode
0.0 0.0
p3
Level 2 access
Fan management
--------
Free Cooling ----
Fire ----
Fan management
:
Without, Flow rate (
constant flows and independent setpoints)
or Pressure (
Constant supply air duct pressure
and identical fan speed values)
Free Cooling
:
Without, With
Fire
:
Without, With
Содержание AirCompact Control
Страница 1: ...NA 13 12 B 03 2015 AirCompact Control AirCompact Control manual...
Страница 61: ...61...
Страница 68: ...68...