40
2.13
Master/Slave menu
The Master/Slave function is used to manage several units (maximum of 8) supplying air to the same room and providing
automatic weekly rotation (168 hours). This is done to ensure uniform wearing of the AHUs.
A backup/additional function is also available.
m0
Additional ----
Unit within network ----
Additional
:
Without, With
(Authorisation of the Additional function for the rotation of the units)
Unit within network
:
Without, With
(Authorisation of "autonomous" operation after break with bus or absence of power for rotating
the units)
m1
Only on the unit whose address is '1'.
Unit rotation
U1: -
U2: -
U3: -
U4: -
U5: -
U6: -
U1
:
With rotation
(unit linked and integrated into a rotation loop)
, Without rotation
(unit linked and outside of the rotation loop)
, Not
present
(unit not linked and outside of the rotation loop)
U2
:
With rotation, Without rotation, Not present
U3
:
With rotation, Without rotation, Not present
U4
:
With rotation, Without rotation, Not present
U5
:
With rotation, Without rotation, Not present
U6
:
With rotation, Without rotation, Not present
m2
Only on the unit whose address is '1'.
U7: -
U8: -
Unit(s) on standby -
1 rotation per 168h
U7
:
With rotation, Without rotation, Not present
U8
:
With rotation, Without rotation, Not present
Unit(s) on standby
:
1 to 7
(according to the total number of units linked and integrated into a rotation loop – 1)
1 rotation per
:
0 to 999h
(when the value 0 is applied, this allows the rotation to be checked as it will be carried out every 5
minutes)
3
Managing a network of controllers
The pLAN network is the name of the physical network that links controllers to remote HMI terminals.
pLAN =
p
ersonal
L
ocal
A
rea
N
etwork
The connection of the controllers via the pLAN network allows the datapoints of one controller to be exchanged for another,
following the logic set out by the program, i.e. the direction that these datapoints must follow and that from which they come. As a
consequence, they are not programmed by the user, who must only carry out the electrical connection.
3.1
pLAN electrical connections
3.1.1
Connecting controllers to the pLAN
The electrical connection between the controllers under the pLAN network (RS485) is carried out using an AWG20/22 shielded
cable composed of a twisted pair and a shield. The cards must be connected in parallel using the J11 connector.
The first and last controller must be no more than
500m
apart.