24
Comfort w5
Indication of the operating mode for T° regulation in "Energy optimisation" mode
Level 1 access
Supply air Cooling 16.0°c
Cooling Comfort Supply air temperature control setpoint
(Regulated T° ≠ Supply air) (0 to 50.0°C)
Eco 18.0°c
Cooling Eco Supply air temperature control setpoint (Regulated T° ≠ Supply air) (0 to 50.0°C)
Supply air Heating 26.0°c
Heating Comfort Supply air temperature
control setpoint (Regulated T° ≠ Supply air) (0 to 50.0°C)
Eco 24.0°c
Heating Eco Supply air temperature control setpoint (Regulated T° ≠ Supply air) (0 to 50.0°C)
U :01 w6
Level 2 access
Frost protection 17.0°c
Unit reactivation setpoint in "Standby" mode when there is an ambient temperature sensor
w7
Level 2 access
Night cooling 17.0°c
Control setpoint in "Night cooling" mode
Duct 200Pa
Supply air duct pressure control setpoint for night cooling
Supply air 02000m3/h
Supply air fan Comfort flow rate control setpoint for night cooling
Return air 02000m3/h
Return air fan Comfort flow rate control setpoint for night cooling
w8
Level 3 access
Electric heater
Off On
Stage 1 000.0% 050.0%
Stage 1 on and off setpoint for the electric heater
Stage 2 050.0% 066.6%
Stage 2 on and off setpoint for the electric heater
w10
Free cooling 17.0°c
Outdoor temperature limit value for authorisation of free cooling (
Level 3 Access)
Min fresh air ctrl 000%
Fresh air minimum value (
Level 2 Access)
w12
Level 3 access
Min. th-Tune setpoint
15.0°c
Min. temperature setpoint value regulated via the room terminal
Max. th-Tune setpoint
30.0°c
Max. temperature setpoint value regulated via the room terminal