32
i3
Level 1 access
Supply air fan -
Supply air fan operation check state (C = on; O = off)
Return air fan -
Return air fan operation check state (C = on; O = off)
Fire -
Fire detection sensor check state (F = no fire; O = fire detected)
i4
Level 1 access
Humidif. check -
Humidifier check state (C = no faults; O = fault detected)
Elec heater load shedding -
Load shedding command state (C = Load shedding; O = No load shedding)
Remote control -
Remote control state (F = on; O = off)
i5
Level 1 access
Elec. heater safety -
State of electric heater safety thermostat (C = fault detected; O = no faults)
Antifreeze thermostat -
Frost protection thermostat state (C = fault detected; O = no faults)
Exch. pressure switch -
Plate heat exchanger pressure switch state (C = fault detected, O = no faults)
2.5.2
Outputs
o1
Level 1 access
Fan ---%
Supply air fan variable frequency drive control value
Return air fan ---%
Return air fan variable frequency drive control value
Coil 1 Heating ---%
Water coil 1 valve control value (Heating or Triac)
Coil 2 Cooling ---%
Water coil No.2 valve control value in "Cooling" mode (or Heating)
o2
Level 1 access
Recov. bypass ---
Plate heat exchanger bypass damper control state
o3
Level 1 access
Danger - "Danger" fault summary relay state
Maintenance -
"Maintenance" fault summary relay state