The KSet software for configuring the group addresses is provided alongside the Carel_plugin_21.PR4 file for the ETS3 software
tool (not provided) (Carel_plugin_30.PR5 file for the ETS4 software (not provided)) and the CTA-V30.XML file for the database
below:
Description
Datapoint
Name
Datapoint
TypeName
Datapoint
TypeCode
IN/OUT
Index
TYPE
Supply air filter CF1
fouling level
Filtre1
DPT_Value_Temp
9.001
OUT
1112
REG
Supply air duct
pressure
PressionGaine
DPT_Value_Temp
9.001
OUT
1110
REG
Supply air
temperature
TemperatureSoufflage
DPT_Value_Temp
9.001
OUT
1100
REG
Return air temperature
TemperatureReprise
DPT_Value_Temp
9.001
OUT
1111
REG
Return air filter CF1
fouling level
Filtre2
DPT_Value_Temp
9.001
OUT
1113
REG
Fresh air or outdoor
temperature
TemperatureNeuf
DPT_Value_Temp
9.001
OUT
1103
REG
Ambient temperature
TemperatureAmbiante
DPT_Value_Temp
9.001
OUT
1102
REG
Supply air fan flow
rate
DebitVentilSoufflage
DPT_Value_Temp
9.001
OUT
1108
REG
Return air fan flow
rate
DebitVentilReprise
DPT_Value_Temp
9.001
OUT
1109
REG
CO
2
air quality
QualiteAir
DPT_Value_Temp
9.001
OUT
1116
REG
Network water
temperature
TemperatureReseau
DPT_Value_Temp
9.001
OUT
1104
REG
Water coil valve No. 1
Batterie1
DPT_Value_Temp
9.001
OUT
1142
REG
Supply air fan control
VitesseVentilSoufflage
DPT_Value_Temp
9.001
OUT
1140
REG
Return air fan control
VitesseVentilReprise
DPT_Value_Temp
9.001
OUT
1141
REG
Water coil valve No. 2
Batterie2
DPT_Value_Temp
9.001
OUT
1143
REG
Mixing damper
Melange
DPT_Value_Temp
9.001
OUT
1169
REG
Supply air fan Comfort
flow rate control
setpoint
WVentSConfort
DPT_Value_Temp
9.001
IN
400
REG
Supply air fan Comfort
flow rate control
setpoint return
WVentSConfort
DPT_Value_Temp
9.001
OUT
400
REG
Return air fan Comfort
flow rate control
setpoint
WVentRConfort
DPT_Value_Temp
9.001
IN
401
REG
Return air fan Comfort
flow rate control
setpoint return
WVentRConfort
DPT_Value_Temp
9.001
OUT
401
REG
Supply air fan Eco
flow control setpoint
WVentSEco
DPT_Value_Temp
9.001
IN
402
REG
Supply air fan Eco
flow rate control
setpoint return
WVentSEco
DPT_Value_Temp
9.001
OUT
402
REG
Return air fan Eco
flow control setpoint
WVentREco
DPT_Value_Temp
9.001
IN
403
REG
Return air fan Eco
flow rate control
setpoint return
WVentREco
DPT_Value_Temp
9.001
OUT
403
REG
Comfort pressure
control setpoint for
the Supply air duct
WPressionConfort
DPT_Value_Temp
9.001
IN
405
REG
Comfort pressure
control setpoint return
for the Supply air duct
WPressionConfort
DPT_Value_Temp
9.001
OUT
405
REG
Eco pressure control
setpoint for the
Supply air duct
WPressionEco
DPT_Value_Temp
9.001
IN
406
REG
Eco pressure control
setpoint return for the
Supply air duct
WPressionEco
DPT_Value_Temp
9.001
OUT
406
REG
Control setpoint for
the monitored
Comfort temperature
in "Precision" mode
WTempRegulConfort
DPT_Value_Temp
9.001
IN
410
REG
Control setpoint
return for the
monitored Comfort
temperature in
WTempRegulConfort
DPT_Value_Temp
9.001
OUT
410
REG