53
bit 1
Return air motor alarm
bit 2
Not used
bit 3
Supply air filter 1 dirty alarm
bit 4
Supply air filter 1 blocked alarm
bit 5
Not used
bit 6
Return air filter 2 dirty alarm
bit 7
Return air filter 2 blocked alarm
bit 8
Additional filter 3 dirty alarm
bit 9
Not used
bit 10
Not used
bit 11
Not used
bit 12
Not used
bit 13
Fire alarm
bit 14
Antifreeze alarm
bit 15
Electric heater safety thermostat alarm
DGT
--
nvo_alarm_17_32
83
output
Alarm 2 value:
bit 0
Low supply air temperature alarm
bit 1
High supply air temperature alarm
bit 2
Low ambient or return air temperature alarm
bit 3
High ambient or return air temperature alarm
bit 4
Humidifier alarm
bit 5
Heat recovery unit fouled alarm
bit 6
pLAN alarm
bit 7
Clock lithium battery alarm
bit 8
Duct pressure alarm
bit 9
Not used
bit 10
Not used
bit 11
Not used
bit 12
Not used