Amana ARPT**14 Series Скачать руководство пользователя страница 1

1

Important Safety Instructions ............................................ 1

2

Important Note to the Owner Regarding Product Warranty .. 2

3

Shipping Inspection .......................................................... 3

3.1 Parts .................................................................... 3
3.2 Handling .............................................................. 3

4

Codes & Regulations ........................................................ 3

5

Replacement Parts ........................................................... 3

6

 Pre-Installation Considerations ........................................ 3

6.1 Preparation .......................................................... 3
6.2 System Matches .................................................. 3
6.3 Interconnecting Tubing ........................................ 3
6.4 Clearances .......................................................... 4
6.5 Horizontal Applications ........................................ 4

7

 Installation Location ......................................................... 4

7.1 Upflow Installation ............................................... 4
7.2 Horizontal Left Installation ................................... 4
7.3 Downflow Installation ........................................... 4
7.4 Horizontal Right Installation ................................. 5

8

Refrigerant Lines .............................................................. 7

8.1 Tubing Size .......................................................... 7
8.2 Tubing Preparation .............................................. 7
8.3 Special Instructions ............................................. 7
8.4 Tubing Connections for Flowrator Model ............. 7
8.5 Tubing Connections for TXV Models ................... 8

9

Condensate Drain Lines ................................................. 8

10

Ductwork ......................................................................... 9

10.1 Return Ductwork ................................................ 9

11

Return Air Filters ............................................................. 9

12

Electric Heat ................................................................... 9

12.1 No Electric Heat Installed .................................. 9

13

Electrical and Control Wiring ........................................ 10

13.1 Building Electrical Service Inspection .............. 10
13.2 Wire Sizing ...................................................... 10
13.3 Maximum Overcurrent Protection (MOP) ......... 11
13.4 Electrical Connections – Supply Voltage .......... 11
13.4.1 Air Handler Only (Non-Heat Kit Models) ........ 11
13.4.2 Air Handler - Non-Circuit Breaker Heat Kits .. 11
13.4.3 Air Handler With Circuit Breaker Heat Kit ...... 11
13.5 Low Voltage Connections ................................. 11
13.5.1 Thermostats .................................................. 12
13.6 Speed Tap Adjustment .................................... 12

14

Achieving 2% Low Leakage Rate ................................. 12

15

Start-Up Procedure ....................................................... 12

16

Regular Maintenance ................................................... 12

Airflow Data .......................................................................... 13
Schematics ........................................................................... 15
Wiring Diagrams ................................................................... 21

RECOGNIZE THIS SYMBOL

AS A SAFETY PRECAUTION.

ATTENTION INSTALLING PERSONNEL

Prior to installation, thoroughly familiarize yourself with this Installation Manual.

Observe all safety warnings. During installation or repair, caution is to be observed.

It is your responsibility to install the product safely and to educate the customer on its safe use.

ARUF**14**/ARPT**14**

©

2012 Goodman Manufacturing Company, L.P.

5151 San Felipe, Suite 500, Houston, TX 77056

www.goodmanmfg.com - or - www.amana-hac.com

P/N: IO-427C

Date:  October 2012

1

Important Safety Instructions

The following symbols and labels are used throughout this
manual to indicate immediate or potential safety hazards.  It
is the owner’s and installer’s responsibility to read and com-
ply with all safety information and instructions accompanying
these symbols.  Failure to heed safety information increases
the risk of personal injury, property damage, and/or product
damage.

ASPT**14**/ASUF**14**

AIR HANDLERS
INSTALLATION & OPERATING INSTRUCTIONS

Содержание ARPT**14 Series

Страница 1: ...ircuit Breaker Heat Kits 11 13 4 3 Air Handler With Circuit Breaker Heat Kit 11 13 5 Low Voltage Connections 11 13 5 1 Thermostats 12 13 6 Speed Tap Adjustment 12 14 Achieving 2 Low Leakage Rate 12 15 Start Up Procedure 12 16 Regular Maintenance 12 Airflow Data 13 Schematics 15 Wiring Diagrams 21 RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION ATTENTION INSTALLING PERSONNEL Prior to installation thor...

Страница 2: ...man brand products visit www goodmanmfg com and for Amana brand product visit www amana hac com IMPORTANT To register your Goodman brand unit go to www goodmanmfg com and click Warranty Registration Complete registration as prompted HIGH VOLTAGE Failure to do so may cause property damage personal injury or death Disconnect ALL power before servicing Multiple power sources may be present Installati...

Страница 3: ...gned and manufactured to comply with applicable national codes Installation in accordance with such codes and or prevailing local codes regulations is the respon sibility of the installer The manufacturer assumes no respon sibility for equipment installed in violation of any codes or regu lations The United States Environmental Protection Agency EPA has issued various regulations regarding the in ...

Страница 4: ...However service clearance must take precedence A minimum of 24 in front of the unit for service clear ance is required Additional clearance on one side or top will be required for electrical wiring connections Con sult all appropriate regulatory codes prior to determining final clearances When installing this unit in an area that may become wet such as crawl spaces elevate the unit with a sturdy n...

Страница 5: ... together during this procedure Remove and retain the seven 7 screws securing the coil access panel to the cabinet and the six 6 screws securing the blower access panel to the cabinet 2 Slide the coil assembly out using the drain pan to pull the assembly from the cabinet NOTE DO NOT USE MANIFOLDS OR FLOWRATOR TO PULL OUT THE COIL ASSEMBLY FAILURE TO DO SO MAY RESULT IN BRAZE JOINT DAMAGE AND LEAKS...

Страница 6: ...rain Port for Upflow Downflow Application Secondary Drain Port for Horizontal Application Blower Access Panel Coil Access Panel Tubing Panel Thumb Screw EXTERNAL PART TERMINOLOGY Figure 6 Coil Slides on the downflow bracket IMPORTANT NOTE Ensure coil slides on the rails along the groove provided on the drain pan side walls Failure to do so will result in improper condensate drainage COIL INSTALLAT...

Страница 7: ... appropriate heat level for the size of the tube being brazed CAUTION 8 3 Special Instructions Units without a factory installed TXV come equipped with a flowrator piston for refrigerant expansion For most installations with matching applications no change to the flowrator piston is required However in mix matched applications a flowrator piston change may be required See the Goodman piston kit ch...

Страница 8: ... line located inside the building Use Armaflex or similar material A secondary condensate drain connection has been provided for areas where the building codes require it Pitch all drain lines a minimum of 1 4 per foot to provide free drainage Provide required support to the drain line to prevent bowing If the secondary drain line is required run the line separately from the primary drain and end ...

Страница 9: ...ter rails a nominal 16x20x1 20x20x1 or 24x20x1 actual dimension must be less than 23 x20 filter can be installed on a B C and D cabinet respectively the cabinet size is the seventh letter of the model number 12 Electric Heat Refer to the installation manual provided with the electric heat kit for the correct installation procedure All electric heat must be field installed If installing this option...

Страница 10: ...ble applies to ARUF 14 ARPT 14 ASPT 14 Table 5 MINIMUM CFM REQUIRED FOR HEATER KITS 3 5 6 8 10 15 19 20 25 49 1170 1170 1170 1170 1345 1345 59 1590 1590 1590 1590 1715 1715 1715 ASUF HEATER kW Table applies to ASUF 14 Table 6 MINIMUM CFM REQUIRED FOR HEATER KITS 13 Electrical and Control Wiring IMPORTANT All routing of electrical wiring must be made through provided electrical knockouts Do not cut...

Страница 11: ...own in Figure 13 If the knockouts on the cabinet sides are used for electri cal conduit an adapter ring must be used in order to meet UL1995 safety requirements An NEC or CEC approved strain relief is to be used at this entry point Some codes municipalities require the supply wire to be enclosed in conduit Consult your local codes Side of Cabinet Top of Cabinet KNOCK OUT FOR ELECTRICAL CONNECTIONS...

Страница 12: ...cess panels and between the coil access and filter access panels Ensure upon installation that the plastic breaker cover is sitting flush on the blower access panel and all access panels are flush with each other and the cabinet With these requirements satisfied the unit achieves less than 2 air flow leakage when tested in accordance with ASHRAE Stan dard 193 15 Start Up Procedure Prior to start u...

Страница 13: ...0 Low 1480 1420 1350 1290 1185 1100 1045 High 2235 2175 2125 2050 1960 1825 1720 Medium 2030 1970 1885 1800 1690 1600 1495 Low 1615 1535 1455 1355 1270 1185 1090 ARUF18B14 ARUF48D14 ARUF60D14 Static Pressure in w c Model Number Blower Speed ARUF24B14 ARUF30B14 ARUF36C14 ARUF42C14 0 1 0 2 0 3 0 4 0 5 0 6 0 7 High 1185 1125 1065 1010 985 910 780 Medium 900 850 825 785 715 670 610 Low 630 605 560 525...

Страница 14: ...2180 2160 2085 2060 2010 1970 1930 1895 1850 Blower Speed Tap Model Number ASUF49C14 ASUF59D14 Static Pressure in w c 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 1 570 545 525 480 445 410 370 315 280 240 2 655 630 605 565 530 495 465 425 375 330 3 720 690 670 635 600 570 535 500 465 420 4 845 830 810 770 740 705 675 650 620 580 5 1055 1025 1005 990 975 950 920 895 865 840 1 960 905 890 810 760 720 665 6...

Страница 15: ...M THERMOSTAT W Y G R 18 GA 4 WIRES WITH COOLING 3 WIRES WITHOUT R G W Y TO CONDENSING UNIT 24V CONNECTIONS 18 GA 2 WIRES BLUE WHITE GREEN RED CONTACTOR COIL AR UNIT Low Voltage Wiring Diagram for Cooling Unit with optional heat kit 10kW and below W2 GREEN RED WHITE BLUE BROWN 18 GA 4 WIRE WITH COOLING 3 WIRE WITHOUT CONDENSING UNIT 24V CONNECTIONS 18 GA 2 WIRES CONTACTOR COIL AR UNIT Low Voltage W...

Страница 16: ... O C G R E TYPICAL H P ROOM THERMOSTAT HEAT PUMP ARUF 14 ARPT 14 18 60 10 KW BELOW OPTIONAL OUTDOOR THERMOSTAT CLOSE ON TEMPERATURE FALL RED GREEN WHITE BLUE AT AR UNIT R Y O W BL 18 GA 5 WIRE 18 GA 7 WIRE NOTE R G BR W BL R R I B 18 GA 6 WIRE NEEDED WHEN OT IS USED R 18 GA 7 WIRE NEEDED WHEN TWO OT S ARE USED 18 GA 5 WIRE BL O W Y BL NOTE W G BLUE WHITE GREEN TYPICAL H P ROOM THERMOSTAT 18 60 ABO...

Страница 17: ...heating All these configurations can be applied with convenient connections to outdoor ther mostat applications The following sections will be detailed Single Stage Cooling Heat Pump Each diagram details the connections between room ther mostat and ASPT air handlers and the connections between the ASPT air handlers and the Condensing Unit or Heat Pump with optional connections to Outdoor Thermosta...

Страница 18: ...ING OUTDOOR THERMO STAT NOMENCLATURE OT OUTDOOR THERMOSTAT OPTIONAL EHR EMERGENCY HEAT RELAY OPTIONAL COLOR CODES RD RED YL YELLOW BL BLUE BR BROWN OR ORANGE WH WHITE Y G W W2 R COOLING UNIT WITH OPTIONAL HEAT KITS OF 15 kW AND ABOVE AND ROOM THERMOSTAT WITH TWO STAGES OF HEAT C W1 W2 Y2 Y1 O G R TB YL BL CONDENSING UNIT 24V CONNECTION BL YL GR RD 18 GA 5 WIRES WITH COOLING 4 WIRES WITHOUT WH YL B...

Страница 19: ...OT 1 SHOULD BE THE FIRST TO CLOSE AND THE LAST TO OPEN 2 JUMPER W1 AND W2 TOGETHER IF OT 2 IS NOT USED 3 REMOVE WIRE WHEN USING OUTDOOR THERMO STAT NOMENCLATURE OT OUTDOOR THERMOSTAT OPTIONAL EHR EMERGENCY HEAT RELAY OPTIONAL COLOR CODES RD RED YL YELLOW BL BLUE BR BROWN OR ORANGE WH WHITE G C R HEAT PUMP UNIT WITH OPTIONAL HEAT KITS OF 15 kW AND ABOVE C W1 W2 Y2 Y1 O G R TB 18 GA 7 WIRE O Y C W2 ...

Страница 20: ...EATKIT MOTOR The Electronic Blower Time Delay Relay provides power to the blower motor with a delay of 7 seconds after 24VAC is applied to G After 24VAC is removed from G the blower motor output is de energized after a delay of 65 seconds Normal Time Delays 60Hz 50Hz Turn On Delay 7 0 SEC 1 8 4 SEC 1 Turn Off Delay 65 0 SEC 1 78 0 SEC 1 Field test mode Shorting the speedup quick connect to C decre...

Страница 21: ...E SPEED MOTOR WIRING SELECT MODELS ONLY SEE NOTE 3 NOTE WHEN INSTALLING HEATER KIT ENSURE SPEED TAP IS NOT BELOW MINIMUM BLOWER SPEED MBS SPECIFIED FOR THE AIR HANDLER HEATER KIT COMBINATION ON THIS UNITS SERIAL PLATE AFTER INST ALLING OPTIONAL HEAT KIT MARK A X IN THE PROVIDED ABOVE MARK ACCORDING TO THE NUMBER OF HEATER ELEMENT ROWS INSTALLED NO MARK INDICATES NO HEAT KIT INSTALLED 5 ELEMENT ROW...

Страница 22: ...OM TERMINAL 4 OF CR RELAY TO APPROPRIATE TAP AT TB 4 BROWN AND WHITE WIRES ARE USED FOR HEAT KITS ONLY DELAY RELAY RELAY EVAPORATOR MOTOR ELECTRONIC BLOWER TIME TERMINAL BOARD R EM EBTDR TB BK RD BL YL BLUE BLACK RED YELLOW COMPONENT CODE BROWN PURPLE GREEN PU BR GR FEMALE PLUG CONNECTOR MALE PLUG CONNECTOR TRANSFORMER HIGH VOLTAGE LOW VOLTAGE HIGH VOLTAGE LOW VOLTAGE PLF 2 COLOR CODE TR 6 5 PLM 4...

Страница 23: ...YL YELLOW WIRING CODE HIGH VOLTAGE LOW VOLTAGE COMPONENT CODE PC 9 PIN CONNECTOR HTR HEATER ELEMENT TL THERMAL LMT RS RELAY SEQUENCER TB TERMINAL BLOCK CB CIRCUIT BREAKER CC CONTACTOR FL FUSE LINK TR TRANSFORMER SR STRAIN RELIEF EM EVAPORATOR MOTOR EBTDR ELEC BLOWER TIME DELAY RC RUN CAPACITOR GR GREEN OR ORANGE PU PURPLE 0140M00274 A NOTE WHEN INSTALLING HEATER KIT ENSURE SPEED TAP MUST EXCEED OR...

Страница 24: ...he airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cause a large loss of refrigerant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a condensing unit cover to protect the outdoor unit during the winter unless ...

Отзывы: