2.7 Electrical Connections (Single Phase) Cont.
2.7.2 Model UH-200 Only
WARNING:
The installation of electrical supplies and controls must conform to local codes or, in the
absence of local codes, the National Electrical Code and good trade practices.
WARNING:
When working on the dishwasher, disconnect the electrical service and place a red tag
at the disconnect switch to indicate work is being done on that circuit.
!! ATTENTION INSTALLER !!
Use flexible conduit or cable to connect incoming power to the dishwasher to allow the machine
to be pulled out 5 ft. [1524mm] for servicing. A service loop is recommended. Service enters at
the right rear corner of the machine. The main connection block is located on the right side of the
dishwasher. See Section 1.4, page 4.
1.
A qualified electrician
must compare the electrical power supply with the machine
electrical specifications stamped on the MACHINE ELECTRICAL CONNECTION
PLATE before connecting to the incoming service through a fused disconnect switch or
circuit breaker (supplied by others). The plate is located near the main terminal block.
2. Model UH-200 utilizes a 120VAC power supply.
Power cord and plug are supplied by others.
Voltage
Machine
Hz
FLA
Phase
120/60/1
23.4
25/25
Single Phase Power Requirements
Models UH-200 Only
Min. Wire
Ampacity/
Max. Fuse Size
Содержание UH-200
Страница 109: ...108 Part 9 REPLACEMENT PARTS Figure 9 4 Door and Door Safety Switch Assembly All Models 1 2 3 4 4 5 6 7 8 9 7 6 10 11 ...
Страница 117: ...116 Part 9 REPLACEMENT PARTS Figure 9 8 Spray Arm Assembly UH 200B UH 200 Upper Spray Arm Assembly 1 2 2 6 7 8 3 4 5 5 ...
Страница 123: ...122 Part 9 REPLACEMENT PARTS Figure 9 11 Wash Pump Motor Assembly All Models 12 13 1 2 3 5 4 6 7 8 9 10 14 11 ...
Страница 127: ...126 Part 9 REPLACEMENT PARTS Figure 9 13 Solid State Controls All Models ...
Страница 135: ...134 Part 9 REPLACEMENT PARTS Figure 9 17 Dishracks Line Strainer PRV All Models 2 3 4 1 ...