6921413
13
TROUBLESHOOTING
RR0545.eps
3.5
Rotation Function
There are six potential problems that could affect the
ROTATE function:
• Incorrect load handling. Refer to the
Operator's Guide
(part no. 6892529)
for suggested procedures.
• Incorrect hydraulic pressure or flow from the lift truck.
• External leaks.
• Solenoid equipped –
Electrical circuit faults, defective
solenoid coil or valve.
• Worn/defective hydraulic rotator motor.
• Worn/defective drive box or rotation bearing assembly.
3.5-1
Supply Circuit Test
1
Check the pressure supplied by the truck at the carriage
hose terminal. Pressure must be within the range
shown in Specifications, Section 5.1.
PRESSURE TO
THE ATTACHMENT MUST NOT EXCEED 3500 psi
(250 bar).
2
Check the flow volume at the carriage hose terminal.
Flow must be within the range shown in Specifications,
Section 5.1.
3
Rotate clockwise (CW) or counterclockwise (CCW) to
the stops. Hold the lever in the ROTATE position for a
few seconds. Release the lever and check for external
leaks at fittings, hoses, revolving connection and valve.
CL3032.eps
2
Flow Meter
WARNING
: Before removing any hoses,
relieve pressure in the hydraulic system.
With the truck off, open the truck auxiliary
control valve(s) several times in both
directions.
Back (Driver's) View
3.5-2
Rotation Circuit Test without
Load
1
Solenoid equipped –
Press the solenoid button and
listen for a 'click' at the solenoid valve. If no sound
is heard, first check the fuse, wiring and coil. Make
sure that the solenoid valve is not jammed. Repair as
necessary, refer to Section 4.11.
IMPORTANT:
Solenoid operated valves must be
plumbed so that the solenoid is
not energized
during
the ROTATE function.
2
Turn the truck off. Connect a 5000 psi (345 bar) pressure
gauge to each rotator drive control valve fitting, as
shown.
3
Rotate the attachment without a load and note pressure
readings of both gauges.
• If the attachment rotates in one direction faster
than the other or rotates in one direction only, the
rotator drive control valve may need repair. Refer to
Section 4.7.
• If the lower gauge reading
exceeds
500 psi (35 bar),
there is excessive back pressure in the supply circuit.
Check for restrictions such as numerous fittings,
90 degree fittings or hose sizes less than No. 8.
Pressure Gauges
Содержание 14J Series
Страница 2: ...BLANK...