Demand Limit In Effect
MODEDMLT
R
0 to 1
BV:31
modedmlt_1
Demand Limit Sw.1 Setpt.
DLSWSP1
W
%
80
0 to 100
AV:53
dlswsp1_1
Demand Limit Sw.2 Setpt.
DLSWSP2
W
%
50
0 to 100
AV:54
dlswsp2_1
Demand Limit Switch 1
DMD_SW1
W
0 to 1
BV:1006
dmd_sw1_1
Demand Limit Switch 2
DMD_SW2
W
0 to 1
BV:1007
dmd_sw2_1
DEW - OA Dewpt.Lockout?
DEW_STAT
R
0 to 1
BV:32
dew_stat_1
Diff.Air Quality in PPM
DAQ
R
0 to 5000
AV:56
daq_1
Dmd Level Low Cool ON
DMDLCON
W
^F
1.5
0 to 2
AV:63
dmdlcon_1
Dmd Level Low Heat ON
DMDLHON
W
^F
1.5
0 to 2
AV:64
dmdlhon_1
Dmd Level(-) Low Cool OFF
DMDLCOFF
W
^F
1
0.5 to 2
AV:59
dmdlcoff_1
Dmd Level(-) Low Heat OFF
DMDLHOFF
W
^F
1
0.5 to 2
AV:60
dmdlhoff_1
Dmd Level(+) Hi Cool ON
DMDHCON
W
^F
0.5
0.5 to 20
AV:61
dmdhcon_1
Dmd Level(+) Hi Heat ON
DMDHHON
W
^F
0.5
0.5 to 20
AV:62
dmdhhon_1
Econ Act. Unavailable?
ECONUNAV
R
0 to 1
BV:34
econunav_1
Econ Command Position
ECN2CPOS
W
%
0 to 100
AV:41
ecn2cpos_1
Econ disable in DH mode?
DHECDISA
W
Yes
0 to 1
BV:35
dhecdisa_1
Econ Recovery Hold Off?
ECONHELD
R
0 to 1
BV:42
econheld_1
Econo Current Min. CFM
ECMINCFM
R
CFM
0 to 20000
AV:42
ecmincfm_1
Econo Current Min. Pos.
ECMINPOS
R
%
0 to 100
AV:45
ecminpos_1
Economizer Act. Curr. Pos
ECONOPOS
R
%
0 to 100
AV:1028
econ_pos_1
Economizer Act.Cmd Pos
ECONOCMD
W
%
0 to 100
AV:67
econocmd_1
Economizer Active?
ECACTIVE
R
0 to 1
BV:36
ecactive_1
Economizer Control Point
ECONCPNT
R
dF
0 to 180
AV:68
econpnt_1
Economizer Forced ?
ECONFORC
R
0 to 1
BV:38
econforc_1
Economizer Max.Position
ECONOMAX
W
%
98
0 to 100
AV:70
economax_1
Economizer Min.Flow
OACFMMAX
W
CFM
2000
0 to 20000
AV:46
oacfmmax_1
Economizer Min.Position
ECONOMIN
W
%
5
0 to 100
AV:4005
econ_min_1
EDT Sensor Bad ?
EDT_STAT
R
0 to 1
BV:44
edt_stat_1
Element Comm Status
R BV:2999
element_stat_1
Element Communications Alarm
R
BV:105
comm_lost_alm_1
Emergency Stop
EMSTOP
W
0 to 1
BV:45
emstop_1
Enth. Switch Read High ?
ENTH
W
0 to 1
BV:40
enth_1
Equipment Alarm
R
BV:127
element_alarm_1
Evacuation Input
EVAC
W
0 to 1
BV:1060
smk_evac_1
Evaporator Discharge Tmp
EDT
R
dF
-40 to 240
AV:76
edt_1
Exhaust Fan VFD Speed
EFAN_VFD
R
%
0 to 100
AV:2075
ef_vfd_output_1
Fan Fail Shuts Down Unit
SFS_SHUT
W
No
0 to 1
BV:50
sfs_shut_1
Fan Mode
FAN_MODE
W
1
0 to 1
AV:77
fan_mode_1
Fan request from IGC
IGCFAN
R
0 to 1
BV:11
igcfan_1
Fan Track Control D.CFM
DELTACFM
R
CFM
–20000
to 20000
AV:47
deltacfm_1
Fan Track Internal RAM
DCFM_RAM
W
CFM
0
–20000
to 20000
AV:48
dcfm_ram_1
Fan Track Max Clamp
DCFM_MAX
W
CFM
4000
0 to 20000
AV:51
dcfm_max_1
Fan Track Max Correction
DCFM_ADJ
W
CFM
1000
0 to 20000
AV:52
dcfm_adj_1
Filter Status Input
FLTS
W
0 to 1
BV:1052
filter_status_1
Fire Shutdown Input
FSD
W
0 to 1
BV:1005
firedown_status_1
Freeze Status Switch
FRZ
W
0 to 1
BV:41
frz_1
Heat Interlock Relay
HIR
W
0 to 1
BV:1026
heat_interlock_relay_1
Heat Relay 1
HS1
R
0 to 1
BV:52
hs1_1
Heat Relay 2
HS2
R
0 to 1
BV:53
hs2_1
Heat-Cool Setpoint Gap
HCSP_GAP
W
deltaF
2 to 10
AV:83
hcsp_gap_1
Heating Control Point
HEATCPNT
R
–20 to 140
AV:1025
heat_ctrl_point_1
Heating Occupied Setpoint
OHSP
W
dF
40 to 99
AV:3002
occ_ht_stpt_1
Heating Supply Air Setpt
SASPHEAT
W
dF
85
80 to 120
AV:85
saspheat_1
Heating Unoccupied Setpoint
UHSP
W
dF
40 to 99
AV:3004
unocc_ht_stpt_1
Hi Limit Switch Tmp Mode
LIMTMODE
R
0 to 1
BV:55
limtmode_1
High OAT Lockout Temp
OAT_LOCK
W
dF
60
–40 to 120
AV:9008
econ_oat_lockout_1
Ht.Coil Command Position
HTCLCPOS
R
%
0 to 100
AV:55
htclcpos_1
Humidifier Relay
HUMIDRLY
R
0 to 1
BV:46
humidrly_1
HumidiMiZer 3-way Valve
HUM3WVAL
R
0 to 1
BV:47
hum3wval_1
HumidiMiZer Capacity
HMZRCAPC
R
%
0 to 100
AV:57
hmzrcapc_1
HVAC Mode Numerical Form
MODEHVAC
R
0 to 40
AV:1022
hvac_mode_1
IAQ - Discrete Input
IAQIN
W
0 to 1
BV:1050
iaq_status_1
IAQ - PPM Indoor CO2
IAQ
W
0 to 5000
AV:1009
iaq_1
IAQ Demand Vent Min.Flow
OACFMMIN
W
CFM
0
0 to 20000
AV:58
oacfmmin_1
IAQ Pre-Occ Purge Active
MODEIQPG
R
0 to 1
BV:56
modeiqpg_1
IAQ Purge Duration
IAQPTIME
W
min
15
5 to 60
AV:98
iaqptime_1
IAQ Purge OAT Lockout
IAQPNTLO
W
dF
50
35 to 70
AV:101
iaqpntlo_1
LAT Cutoff Mode
LATCMODE
R
0 to 1
BV:58
latcmode_1
Leaving Air Temperature
LAT
R
dF
–40 to 240
AV:1027
lvg_air_temperature_1
Local Machine Disable
UNITSTOP
W
0 to 1
BV:59
unitstop_1
Local Schedule
R
n/a
BV:5
schedule_1
Low Temp Cap Override
LOW_TEMP
R
0 to 1
BV:61
low_temp_1
Mech Cooling Locked Out
MODELOCK
R
0 to 1
BV:63
modelock_1
APPENDIX F — UPC OPEN CONTROLLER
Table AP — NETWORK POINTS LIST (cont)
POINT DESCRIPTION
CCN POINT
NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET OBJECT
NAME
Содержание Weathermaster 48P2030-100
Страница 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Страница 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Страница 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Страница 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Страница 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Страница 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Страница 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Страница 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Страница 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Страница 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...