239
APPENDIX G — OPTIONAL MOTORMASTER
®
V CONTROL
Fig. Q — MMV Control Location — 48/50P090,100 Units
Configure Motormaster
®
V Control
The Motormaster V control is configured for proportional inte-
gral (PI) control mode. The Motormaster V control varies the
condenser fan motor speed to maintain a set point of 320 psig
liquid line pressure in response to a 0 to 5 vdc feedback signal
from the liquid line pressure transducer. No additional pro-
gramming is required. See Table AQ. Note that the pressure
transducer must be attached for proper configuration.
Table AQ — Configuration Table
The following
Comfort
Link control configurations must be set
when using a Motormaster V device:
•
Configuration
COOL
M.M.
= YES
•
Configuration
COOL
LLAG
= CIRCUIT A (size 030-
060 units only)
Test Motormaster V Control
To test the control and motor in the test mode, run compressor
no. 1. The Motormaster V electronic control adjusts the fan
speed based on the liquid line pressure input. Ensure that fans
are rotating clockwise (as viewed from above). If rotation is
backward, lock out all power, then swap 2 leads AFTER the
Motormaster V control.
START-UP
The Motormaster V electronic control will be powered up as
long as unit voltage is present. When the system calls for cool-
ing, the Motormaster relay (MMR) will be energized to initiate
the start-up sequence for the Motormaster V electronic control.
The LED (light-emitting diode) will display the speed of the mo-
tor. The display range will be 8 to 60 Hz. The Motormaster V
electronic control will start the condenser fan when the compres-
sor engages. The control will adjust the fan speed to maintain ap-
proximately 320 psig. Above that pressure, the fan should oper-
ate at full speed.
For size 030-060 units, the Motormaster V control uses a 0 to
5 vdc signal input from a pressure transducer attached to the
liquid line service valve gage port on circuit A.
For size 070-100 units, two Motormaster V devices are used,
one for each circuit. The circuit A Motormaster V control uses a
0 to 5 vdc signal input from a pressure transducer attached to the
liquid line service valve gage port on circuit A. The circuit B
Motormaster V control uses a 0 to 5 vdc signal input from a
pressure transducer attached to the liquid line service valve gage
port on circuit B.
The pressure transducer(s) are connected to terminals 2, 5 and
6 on the controller. See Fig. R. The controller is configured by
jumper wires and sensor input types. No field programming is
required. If controller does not function properly, the informa-
tion provided in the Troubleshooting section can be used to
program and troubleshoot the drive.
MOTORMA
S
TER A
CONTROL
MOTORMA
S
TER B
CONTROL
NOMINAL
VOLTAGE
(V-Ph-Hz)
MODE
CONTROL INPUT
(Pin 5)
START
CONTACTS
230-3-60
460-3-60
575-3-60
1
Internal PI control,
0-5V feedback
TB 1,2
208-3-60
380-3-60
2
TB 13A,2
400-3-50
4
TB 13C,2
Содержание Weathermaster 48P2030-100
Страница 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Страница 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Страница 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Страница 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Страница 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Страница 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Страница 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Страница 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Страница 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Страница 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...