206
APPENDIX B — CCN TABLES
Table P — MAINTENANCE DISPLAY TABLES
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
ALARMS01
Active Alarm
ascii
ALARM_01
------------------------
ascii
Active Alarm
ascii
ALARM_02
------------------------
ascii
Active Alarm
ascii
ALARM_03
------------------------
ascii
Active Alarm
ascii
ALARM_04
------------------------
ascii
follow same format for…
ALARMS02 to ALARMS05
BEL_ACTU
Economizer Act.Curr.Pos.
0-100
%
ECONOPOS
Economzr 2 Act.Curr.Pos.
0-100
%
ECON2POS
Economizer Act.Cmd.Pos.
0-100
%
ECONOCMD
forcible
Economzr 2 Act.Curr.Pos.
0-100
%
ECN2RPOS
Econ Command Position
0-100
%
ECN2CPOS
Humidifer Act.Curr.Pos.
0-100
%
HUMDRPOS
Humidifier Command Pos.
0-100
%
HUMDCPOS
Ht.Coil Act.Current Pos.
0-100
%
HTCLRPOS
Ht.Coil Command Position
0-100
%
HTCLCPOS
BP 1 Actuator Curr.Pos.
0-100
%
BP1_RPOS
BP 1 Command Position
0-100
%
BP1_CPOS
BP 2 Actuator Curr.Pos.
0-100
%
BP2_RPOS
BP 2 Command Position
0-100
%
BP2_CPOS
COMPRESR
Compressor A1 Relay
On/Off
CMPA1
Compressor A1 Capacity
%
CMPA1CAP
Circ A High Press.Switch
On/Off
CIRCAHPS
Compressor A1 Feedback
On/Off
CSB_A1
Curr.Sens.Brd. A1 Status
ascii
CSBA1ASC
CSB A1 Feedback Alarm
Enable/Disable
CSB_A1EN
config
Comp A1 Locked Out ?
Yes/No
CMPA1LOK
Compressor A1 Strikes
CMPA1STR
Enable Compressor A1
Enable/Disable
CMPA1ENA
config
Compressor A2 Relay
On/Off
CMPA2
Compressor A2 Feedback
On/Off
CSB_A2
Curr.Sens.Brd. A2 Status
ascii
CSBA2ASC
CSB A2 Feedback Alarm
Enable/Disable
CSB_A2EN
config
Comp A2 Locked Out ?
Yes/No
CMPA2LOK
Compressor A2 Strikes
CMPA2STR
Enable Compressor A2
Enable/Disable
CMPA2ENA
config
Compressor A3 Relay
On/Off
CMPA3
Compressor A3Feedback
On/Off
CSB_A3
Curr.Sens.Brd. A3 Status
ascii
CSBA3ASC
CSB A3 Feedback Alarm
Enable/Disable
CSB_A3EN
config
Comp A3 Locked Out ?
Yes/No
CMPA3LOK
Compressor A3 Strikes
CMPA3STR
Enable Compressor A3
Enable/Disable
CMPA3ENA
config
Compressor B1 Relay
On/Off
CMPB1
Circ B High Press.Switch
On/Off
CIRCBHPS
Compressor B1 Feedback
On/Off
CSB_B1
Curr.Sens.Brd. B1 Status
ascii
CSBB1ASC
CSB B1 Feedback Alarm
Enable/Disable
CSB_B1EN
config
Comp B1 Locked Out ?
Yes/No
CMPB1LOK
Compressor B1 Strikes
CMPB1STR
Enable Compressor B1
Enable/Disable
CMPB1ENA
config
Compressor B2 Relay
On/Off
CMPB2
Compressor B2 Feedback
On/Off
CSB_B2
Curr.Sens.Brd. B2 Status
ascii
CSBB2ASC
CSB B2 Feedback Alarm
Enable/Disable
CSB_B2EN
config
Comp B2 Locked Out ?
Yes/No
CMPB2LOK
Compressor B2 Strikes
CMPB2STR
Enable Compressor B2
Enable/Disable
CMPB2ENA
config
Compressor B3 Relay
On/Off
CMPB3
Compressor B3 Feedback
On/Off
CSB_B3
Curr.Sens.Brd. B3 Status
ascii
CSBB3ASC
Содержание Weathermaster 48P2030-100
Страница 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Страница 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Страница 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Страница 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Страница 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Страница 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Страница 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Страница 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Страница 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Страница 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...