APPENDIX B — CCN TABLES
Table L — STATUS DISPLAY TABLES (cont)
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
ECONOMZR
Economizer Act.Curr.Pos.
%
ECONOPOS
Economizer 2 Act.Curr.Pos.
%
ECON2POS
Economizer Act.Cmd.Pos.
%
ECONOCMD
forcible
Economizer Active ?
ECACTIVE
Economizer Control Point
dF
ECONCPNT
Outside Air Temperature
dF
OAT
forcible
Evaporator Discharge Tmp
dF
EDT
Controlling Return Temp
dF
RETURN_T
forcible
Econo Current Min. Pos.
%
ECMINPOS
Econo Current Min. CFM
CFM
ECMINCFM
Outside Air CFM
CFM
OACFM
GENERAL
Occupied ?
YES/NO
OCCUPIED
forcible
Static Pressure
" H2O
SP
Building Pressure
" H2O
BP
Outside Air CFM
CFM
OACFM
Return Air CFM
CFM
RACFM
Supply Air CFM
CFM
SACFM
Outside Air Rel.Humidity
%
OARH
forcible
Return Air Rel.Humidity
%
RARH
forcible
Space Relative Humidity
%
SPRH
forcible
Space Temperature Offset
^F
SPTO
forcible
Supply Air Setpnt. Reset
^F
SASPRSET
forcible
Static Pressure Reset
SPRESET
forcible
IAQ - PPM Return CO2
IAQ
forcible
OAQ - PPM Return CO2
OAQ
forcible
IAQ Min.Pos.Override
%
IAQMINOV
forcible
GENERIC
20 points dependent upon the configura-
tion of the “generics” table in the Service-
Config section on page 190
HEATING
HVAC Mode…………..:
ascii text strings
Control Mode………..:
ascii text strings
Heat Control Type……:
ascii text strings
Re-Heat Control Type...:
ascii text strings
Heating Mode………..:
ascii text strings
Requested Heat Stage
HT_STAGE
Ht.Coil Act.Current Pos.
%
HTCLRPOS
Heating Control Point
dF
HEATCPNT
Heat Relay 1
HS1
Modulating Heat Capacity
%
HTMG_CAP
Heat Relay 2
HS2
Relay 3 W1 Gas Valve 2
HS3
Relay 4 W2 Gas Valve 2
HS4
Relay 5 W1 Gas Valve 3
HS5
Relay 6 W2 Gas Valve 3
HS6
Heat Interlock Relay
HIR
forcible
HMZR
HVAC Mode…………..:
ascii text strings
Humidimizer Capacity
%
HMZRCAPC
Condenser EXV Position
%
COND_EXV
Bypass EXV Position
%
BYP_EXV
Humidimzer 3-Way Valve
On/Off
HUM3WVAL
Cooling Control Point
dF
COOLCPNT
Evaporator Discharge Tmp
dF
EDT
Heating Control Point
dF
HEATCPNT
Leaving Air Temperature
dF
LAT
MODEDISP
System Mode…………:
ascii text strings
HVAC Mode…………..:
ascii text strings
Control Mode………..:
ascii text strings
Currently Occupied
On/Off
MODEOCCP
Timed Override in effect
On/Off
MODETOVR
DCV resetting min pos
On/Off
MODEADCV
Supply Air Reset
On/Off
MODESARS
Demand Limit in Effect
On/Off
MODEDMLT
Temp.Compensated Start
On/Off
MODETCST
Содержание Weathermaster 48P2030-100
Страница 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Страница 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Страница 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Страница 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Страница 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Страница 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Страница 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Страница 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Страница 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Страница 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...