101
Daylight Savings Start Week (DS.ST
ST.WK)
This is the start week of the month for daylight savings. The
week can be set from 1 to 5.
Daylight Savings Start Day (DS.ST
ST.DY)
This is the start day of the week for daylight savings. The day
can be set from 1 to 7 (Sunday=1, Monday=2, etc.).
Daylight Savings Minutes To Add (DS.ST
MIN.A)
This is the amount of time that will be added to the time clock
for daylight savings.
DAYLIGHT SAVINGS STOP (
DS.SP
)
This submenu configures the end date and time for daylight
savings.
Daylight Savings Stop Month (DS.SP
SP.MN)
This is the stop month for daylight savings time. The numbers
1 to 12 correspond to the months of the year (e.g., January = 1).
Daylight Savings Stop Week (DS.SP
SP.WK)
This is the stop week of the month for daylight savings. The
week can be set from 1 to 5.
Daylight Savings Stop Day (DS.SP
SP.DY)
This is the stop day of the week for daylight savings. The day
can be set from 1 to 7 (Sunday=1, Monday=2, etc.).
Daylight Savings Minutes To Subtract (DS.SP
MIN.S)
This is the amount of time that will be removed from the time
clock after daylight savings ends.
Table 83 — Time Clock Menu
ITEM
EXPANSION
RANGE
CCN POINT
DEFAULT
TIME
TIME OF DAY
HH.MM
Hour and Minute
00:00
TIME
DATE
MONTH,DATE,DAY AND YEAR
MNTH
Month of Year
multi-text strings
MOY
DOM
Day of Month
0 to 31
DOM
DAY
Day of Week
multi-text strings
DOWDISP
YEAR
Year
e.g. 2012
YOCDISP
SCH.L
LOCAL TIME SCHEDULE
PER.1
PERIOD 1
PER.1
DAYS
DAY FLAGS FOR PERIOD 1
Period 1 only
PER.1
DAYS
MON
Monday in Period
YES/NO
PER1MON
Yes
PER.1
DAYS
TUE
Tuesday in Period
YES/NO
PER1TUE
Yes
PER.1
DAYS
WED
Wednesday in Period
YES/NO
PER1WED
Yes
PER.1
DAYS
THU
Thursday in Period
YES/NO
PER1THU
Yes
PER.1
DAYS
FRI
Friday in Period
YES/NO
PER1FRI
Yes
PER.1
DAYS
SAT
Saturday in Period
YES/NO
PER1SAT
Yes
PER.1
DAYS
SUN
Sunday in Period
YES/NO
PER1SUN
Yes
PER.1
DAYS
HOL
Holiday in Period
YES/NO
PER1HOL
Yes
PER.1
OCC
Occupied from
00:00
PER1_OCC
00:00
PER.1
UNC
Occupied to
00:00
PER1_UNC
24:00
Repeat for periods 2-8
HOL.L
LOCAL HOLIDAY SCHEDULES
HD.01
HOLIDAY SCHEDULE 01
HD.01
MON
Holiday Start Month
0 to 12
HOL_MON1
HD.01
DAY
Start Day
0 to 31
HOL_DAY1
HD.01
LEN
Duration (Days)
0 to 99
HOL_LEN1
Repeat for holidays 2-30
DAY.S
DAYLIGHT SAVINGS TIME
DS.ST
DAYLIGHT SAVINGS START
DS.ST
ST.MN
Month
1 to 12
STARTM
4
DS.ST
ST.WK
Week
1 to 5
STARTW
1
DS.ST
ST.DY
Day
1 to 7
STARTD
7
DS.ST
MIN.A
Minutes to Add
0 to 90
MINADD
60
DS.SP
DAYLIGHTS SAVINGS STOP
DS.SP
SP.MN
Month
1 to 12
STOPM
10
DS.SP
SP.WK
Week
1 to 5
STOPW
5
DS.SP
SP.DY
Day
1 to 7
STOPD
7
DS.SP
MIN.S
Minutes to Subtract
0 to 90
MINSUB
60
Содержание Weathermaster 48P2030-100
Страница 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Страница 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Страница 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Страница 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Страница 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Страница 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Страница 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Страница 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Страница 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Страница 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...