Heating Control
The P Series
Comfort
Link controls offer control for five differ-
ent types of heating systems to satisfy general space heating re-
quirements: 2-stage gas heat, 2-stage electric heat, multiple-
stage gas heat, modulating gas heat, and hydronic heat. Heat-
ing control also provides tempering and reheat functions.
These functions are discussed in separate sections. Reheat is
discussed under Dehumidification functions on page 88.
Variable air volume (VAV) type applications (
C.TYP
= 1 or 2)
require that the space terminal positions be commanded to
open to minimum heating positions when gas or electric heat
systems are active, to provide for the unit heating system’s
Minimum Heating Airflow rate.
Also, for VAV applications, the heat interlock relay (HIR)
function provides the switching of a control signal intended for
use by the VAV terminals. This signal must be used to com-
mand the terminals to open to their Heating Open positions.
The HIR is energized whenever the Heating mode is active, an
IAQ pre-occupied force is active, or if fire smoke modes, pres-
surization, or smoke purge modes are active.
Hydronic heating applications that use the unit’s control re-
quire the installation of a communicating actuator on the hy-
dronic heating coil’s control valve. This actuator (with or with-
out matching control valve) may be separately shipped for field
installation.
All heating systems are available as factory-installed options.
The hydronic heating coil may also be field-supplied and field-
installed; the actuator is still required if unit control will be
used to manage this heating sequence.
SETTING UP THE SYSTEM
The essential heating configurations are located at the local
display under
Configuration
HEAT
.
See Table 40.
Heating Control Type (HT.CF)
The heating control types available are selected/configured
with this variable.
0 = No Heat
1 = Electric Heat
2 = 2 Stage Gas Heat
3 = Staged Gas Heat or Modulating Gas Heat
4 = Hydronic Heat
5 = SCR Electric Heat
Heating Supply Air Set Point (HT.SP)
In a low heat mode for either staged gas, modulating gas, SCR
electric, or hydronic heat, this is the supply air set point for
heating.
Occupied Heating Enable (OC.EN)
This configuration only applies when the unit’s control type
(
Configuration
UNIT
C.TYP
) is configured for 1 (VAV-
RAT) or 2 (VAV-SPT). If the user wants to have the capability
of performing heating throughout the entire occupied period,
then this configuration needs to be set to “YES.” Most installa-
tions do not require this capability, and if heating is installed, it
is used to heat the building up in the morning. In this case, set
OC.EN
to “NO.”
NOTE: This unit does not support simultaneous heating and cool-
ing. If significant simultaneous heating and cooling demand is ex-
pected, it may be necessary to provide additional heating or cool-
ing equipment and a control system to provide occupants with
proper comfort.
NOTE: If the user does not relocate this sensor for the 2-stage
electric or gas heating types and is under CCN Linkage, then the
control will send a heating mode (if present) unconditionally to the
linkage coordinator in the CCN zoning system regardless of the
leaving-air temperature.
Table 40 — Heating Configuration
*Some defaults are model number dependent.
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
HEAT
HEATING CONFIGURATION
HT.CF
Heating Control Type
0 to 5
HEATTYPE
0*
HT.SP
Heating Supply Air Setpt
80 to 120
dF
SASPHEAT
85
OC.EN
Occupied Heating Enabled
Yes/No
HTOCCENA
No
LAT.M
MBB Sensor Heat Relocate
Yes/No
HTLATMON
No
SG.CF
STAGED HEAT CONFIGS
HT.ST
Staged Heat Type
0 to 8
HTSTGTYP
0*
CAP.M
Max Cap Change per Cycle
5 to 45
HTCAPMAX
45*
M.R.DB
St.Ht DB min.dF/PID Rate
0 to 5
HT_MR_DB
0.5
S.G.DB
St.Heat Temp. Dead Band
0 to 5
^F
HT_SG_DB
2
RISE
Heat Rise dF/sec Clamp
0.05 to 0.2
HTSGRISE
0.06
LAT.L
LAT Limit Config
0 to 20
^F
HTLATLIM
10
LIM.M
Limit Switch Monitoring?
Yes/No
HTLIMMON
Yes
SW.H.T
Limit Switch High Temp
80 to 210
dF
HT_LIMHI
170*
SW.L.T
Limit Switch Low Temp
80 to 210
dF
HT_LIMLO
160*
HT.P
Heat Control Prop. Gain
0 to 1.5
HT_PGAIN
1
HT.D
Heat Control Derv. Gain
0 to 1.5
HT_DGAIN
1
HT.TM
Heat PID Rate Config
30 to 300
sec
HTSGPIDR
90*
HH.CF
HYDRONIC HEAT CONFIGS
HW.P
Hydronic Ctl.Prop. Gain
0 to 1.5
HW_PGAIN
1
HW.I
Hydronic Ctl.Integ. Gain
0 to 1.5
HW_IGAIN
1
HW.D
Hydronic Ctl.Derv. Gain
0 to 1.5
HW_DGAIN
1
HW.TM
Hydronic PID Rate Config
15 to 300
sec
HOTWPIDR
90
ACT.C
HYDR.HEAT ACTUATOR CFGS.
SN.1
Hydronic Ht.Serial Num.1
0 to 9999
HTCL_SN1
0
SN.2
Hydronic Ht.Serial Num.2
0 to 6
HTCL_SN2
0
SN.3
Hydronic Ht.Serial Num.3
0 to 9999
HTCL_SN3
0
SN.4
Hydronic Ht.Serial Num.4
0 to 254
HTCL_SN4
0
C.A.LM
Hydr.Ht.Ctl.Ang.Lo Limit
0 to 90
HTCLCALM
85
Содержание Weathermaster 48P2030-100
Страница 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Страница 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Страница 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Страница 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Страница 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Страница 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Страница 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Страница 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Страница 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Страница 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...