89
SETTING UP THE SYSTEM
The settings for dehumidification can be found at the local dis-
play at
Configuration
DEHU
.
See Table 70.
Dehumidification Configuration (D.SEL)
The dehumidification configuration can be set for the follow-
ing settings (see Table 71):
•
D.SEL
= 0 — No dehumidification and reheat.
•
D.SEL
= 1 — The control will perform both dehumidifica-
tion and reheat with modulating valve (hydronic).
•
D.SEL
= 2 — The control will perform dehumidification
and reheat with staged gas only.
•
D.SEL
= 3 — The control will perform both dehumidifica-
tion and reheat with third party heat via an alarm relay. In
the case of
D.SEL
=3, during dehumidification, the alarm
relay will close to convey the need for reheat. A typical ap-
plication might be to energize a 3-way valve to perform
hot gas reheat.
•
D.SEL
= 4 — The control will use the Humidi-MiZer
®
adaptive dehumidification system.
•
D.SEL
= 5 — The unit will operate in dehumidification
mode (Venting Dehum, Cooling Dehum) but without any
reheat. The unit leaving air temperature will be equal to the
Dehum Cool Setpoint (DHCOOLSP) during both the
Venting Dehum and Cooling Dehum modes. This may re-
sult in over cooling of the conditioned space. With this
configuration, if the unit control attempts to go into Heat-
ing Dehum, the dehumidification function will shut off and
only heating mode will be active.
Dehumidification Sensor (D.SEN)
The sensor can be configured for the following settings:
•
D.SEN
= 1 — Initiated by return air relative humidity sensor.
•
D.SEN
= 2 — Initiated by space relative humidity sensor.
•
D.SEN
= 3 — Initiated by discrete input.
Economizer Disable in Dehum Mode (D.EC.D)
This configuration determines economizer operation during
Dehumidification mode.
•
D.EC.D
= YES — Economizer disabled during dehumidi-
fication (default).
•
D.EC.D
= NO — Economizer not disabled during
dehumidification.
Vent Reheat Set Point Select (D.V.CF)
This configuration determines how the vent reheat set point is
selected.
•
D.V.CF
= 0 — Reheat follows an offset subtracted from
return air temperature (
D.V.RA
).
•
D.V.CF
= 1 — Reheat follows a dehumidification heat set
point (
D.V.HT
).
Vent Reheat RAT Offset (D.V.RA)
Set point offset used only during the vent mode. The air will be
reheated to return-air temperature less this offset.
Vent Reheat Set Point (D.V.HT)
Set point used only during the vent mode. The air will be re-
heated to this set point.
Dehumidify Cool Set Point (D.C.SP)
This is the dehumidification cooling set point.
Table 70 — Dehumidification Configuration
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
DEHU
DEHUMIDIFICATION CONFIG.
D.SEL
Dehumidification Config
0 to 4
DHSELECT
0
D.SEN
Dehumidification Sensor
1 to 3
DHSENSOR
1
D.EC.D
Econ disable in DH mode?
Yes/No
DHECDISA
Yes
D.V.CF
Vent Reheat Setpt Select
0 to 1
DHVHTCFG
0
D.V.RA
Vent Reheat RAT offset
0 to 8
deltaF
DHVRAOFF
0
D.V.HT
Vent Reheat Setpoint
55 to 95
dF
DHVHT_SP
70
D.C.SP
Dehumidify Cool Setpoint
40 to 55
dF
DHCOOLSP
45
D.RH.S
Dehumidify RH Setpoint
10 to 90
%
DHRELHSP
55
HZ.RT
Humidi-MiZer Adjust Rate
5 to 120
sec
HMZRRATE
30
HZ.PG
Humidi-MiZer Prop. Gain
0 to 10
HMZR_PG
0.8
DH.DB
Dehumidify RH Deadband
1 to 30
%
DHSENSDB
5
DH.TG
Dehumidification Discrete Timeguard
10 to 90
seconds
DHDISCTG
30
Table 71 — Dehumidification Heat Source Dependency upon Heating Stages
HT.CF (HEATTYPE)
Heating provided by the system
HT.ST
HTSTGTYP
D.SEL (DHSELECT)
Selected Heat for Dehum
DEHUM
ALLOWED
REHEAT
ALLOWED
0–5
any
N/A
0
None
No
No
0–5
any
N/A
4
Humidi-MiZer
®
Yes
Yes
0–5
any
N/A
5
Dehum without reheat
Yes
No
0
No heat
N/A
3
3rd party heat
Yes
Yes
1
2-stage electric heat
N/A
5
Dehum without reheat
Yes
No
2
2-stage gas heat
0
5
Dehum without reheat
Yes
No
3
Staged or mod gas heat
0–5
2
Stage or mod gas
Yes
Yes
4
Hydronic
N/A
1
Hydronic
Yes
Yes
5
SCR electric
6, 7, 8
5
Dehum without reheat
Yes
No
LEGEND
DHSELECT
— Dehumidification Heat Source
HEATTYPE
— Heating Type
HTSTGTYP
— Heating Stage Type
Содержание Weathermaster 48P2030-100
Страница 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Страница 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Страница 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Страница 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Страница 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Страница 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Страница 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Страница 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Страница 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Страница 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...