Table 67 — Indoor Air Quality Configuration
IAQ Discrete Fan Config (Configuration
IAQ
AQ.CF
IQ.I.F)
This is used to configure the operation of the fan during an
IAQ demand condition. It has the following configurations:
•
IQ.I.F
= 0 (No Fan Start) — IAQ demand will never over-
ride normal indoor fan operation during occupied or unoc-
cupied period and turn it on.
•
IQ.I.F
= 1 (Fan On If Occupied) — IAQ demand will
override normal indoor fan operation and turn it on (if off)
only during the occupied period (CV operation with auto-
matic fan).
•
IQ.I.F
= 2 (Fan On Occupied/Unoccupied) — IAQ de-
mand will always override normal indoor fan operation
and turn it on (if off) during both the occupied and unoccu-
pied period.
Economizer Min Position (Configuration
IAQ
DCV.C
EC.MN)
This is the fully occupied minimum economizer position.
IAQ Demand Vent Min Pos. (Configuration
IAQ
DCV.C
IAQ.M)
This configuration will be used to set the minimum damper po-
sition in the occupied period when there is no IAQ demand.
IAQ Econo Override Pos (Configuration
IAQ
AQ.SP
IQ.O.P)
This configuration is the position that the economizer goes to
when override is in effect.
OAQ Lockout Value (Configuration
IAQ
AQ.SP
OAQ.L)
This is the maximum OAQ level above which demand ventila-
tion will be disabled.
Diff. Air Quality Lo Limit (Configuration
IAQ
AQ.SP
DAQ.L)
This is the differential CO
2
level at which IAQ control of the
dampers will be initiated.
Diff. Air Quality Hi Limit (Configuration
IAQ
AQ.SP
DAQ.H)
This is the differential CO
2
level at which IAQ control of the
dampers will be at maximum and the dampers will be at the
Configuration
IAQ
DCV.C
EC.MN
.
DAQ ppm Fan On Set Point (Configuration
IAQ
AQ.SP
D.F.ON)
This is the CO
2
level at which the indoor fan will be turned on.
DAQ ppm Fan Off Set Point (Configuration
IAQ
AQ.SP
D.F.OF)
This is the CO
2
level at which the indoor fan will be turned off.
IAQ Low Reference (Configuration
IAQ
AQ.S.R
IQ.R.L)
This is the reference that will be used with a to non-Carrier
IAQ sensor that may have a different characteristic curve. It
represents the CO
2
level at 4 mA.
IAQ High Reference (Configuration
IAQ
AQ.SR
IQ.R.H)
This is the reference that will be used with a non-Carrier IAQ
sensor that may have a different characteristic curve. It rep-
resents the CO
2
level at 4 mA.
OAQ Low Reference (Configuration
IAQ
AQ.S.R
OQ.R.L)
This is the reference that will be used with a non-Carrier OAQ
sensor that may have a different characteristic curve. It rep-
resents the CO
2
level at 4 mA.
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
DCV.C
DCV ECONOMIZER SETPOINTS
EC.MN
Economizer Min.Position
0 to 100
%
ECONOMIN
5
IAQ.M
IAQ Demand Vent Min.Pos.
0 to 100
%
IAQMINP
0
O.C.MX
Economizer Min.Flow
0 to 20000
CFM
OACFMMAX
2000
O.C.MN
IAQ Demand Vent Min.Flow
0 to 20000
CFM
OACFMMIN
0
O.C.DB
Econ.Min.Flow Deadband
200 to 1000
CFM
OACFM_DB
400
AQ.CF
AIR QUALITY CONFIGS
IQ.A.C
IAQ Analog Sensor Config
0 to 4
IAQANCFG
0
IQ.A.F
IAQ 4-20 ma Fan Config
0 to 2
IAQANFAN
0
IQ.I.C
IAQ Discrete Input Config
0 to 2
IAQINCFG
0
IQ.I.F
IAQ Disc.In. Fan Config
0 to 2
IAQINFAN
0
OQ.A.C
OAQ 4-20ma Sensor Config
0 to 2
OAQANCFG
0
AQ.SP
AIR QUALITY SETPOINTS
IQ.O.P
IAQ Econo Override Pos.
0 to 100
%
IAQOVPOS
100
IQ.O.C
IAQ Override Flow
0 to 31000
CFM
IAQOVCFM
10000
DAQ.L
Diff.Air Quality LoLimit
0 to 1000
DAQ_LOW
100
DAQ.H
Diff. Air Quality HiLimit
100 to 2000
DAQ_HIGH
700
D.F.OF
DAQ PPM Fan Off Setpoint
0 to 2000
DAQFNOFF
200
D.F.ON
DAQ PPM Fan On Setpoint
0 to 2000
DAQFNON
400
IAQ.R
Diff. AQ Responsiveness
–5 to 5
IAQREACT
0
OAQ.L
OAQ Lockout Value
0 to 2000
OAQLOCK
0
OAQ.U
User Determined OAQ
0 to 5000
OAQ_USER
400
AQ.S.R
AIR QUALITY SENSOR RANGE
IQ.R.L
IAQ Low Reference
0 to 5000
IAQREFL
0
IQ.R.H
IAQ High Reference
0 to 5000
IAQREFH
2000
OQ.R.L
OAQ Low Reference
0 to 5000
OAQREFL
0
OQ.R.H
OAQ High Reference
0 to 5000
OAQREFH
2000
IAQ.P
IAQ PRE-OCCUPIED PURGE
IQ.PG
IAQ Purge
Yes/No
IAQPURGE
No
IQ.P.T
IAQ Purge Duration
5 to 60
min
IAQPTIME
15
IQ.P.L
IAQ Purge LoTemp Min Pos
0 to 100
%
IAQPLTMP
10
IQ.P.H
IAQ Purge HiTemp Min Pos
0 to 100
%
IAQPHTMP
35
IQ.L.O
IAQ Purge OAT Lockout
35 to 70
dF
IAQPNTLO
50
Содержание Weathermaster 48P2030-100
Страница 130: ...130 Fig 19 Typical Power Schematic Sizes 040 075 Shown ...
Страница 131: ...131 Fig 20 Main Base Board Input Output Connections ...
Страница 132: ...132 Fig 21 RXB EXB CEM SCB Input Output Connections ...
Страница 133: ...133 Fig 22 Typical Gas Heat Unit Control Wiring 48P030 100 Units Shown ...
Страница 134: ...134 Fig 23 Typical Electric Heat Wiring 50P030 100 Units Shown ...
Страница 135: ...135 Fig 24 Typical Power Wiring 115 V ...
Страница 136: ...136 Fig 25 Typical Gas Heat Section Size 030 050 Units Shown ...
Страница 138: ...138 Fig 27 Component Arrangement Size 030 035 Units ...
Страница 139: ...139 Fig 28 Component Arrangement Size 040 075 Units ...
Страница 140: ...140 Fig 29 Component Arrangement Size 090 100 Units ...